Johnson Controls TM9V MP Specific Safety Rules and Precautions, Safety Requirements

Page 2

438335-UIM-B-0509

Improper installation may create a condition where the operation of the product could cause personal injury or property damage. Improper installation, adjustment, alteration, service or mainte- nance can cause injury or property damage. Failure to carefully read and follow all instructions in this manual can result in fur- nace malfunction, death, personal injury and/or property dam- age. Only a qualified contractor, installer or service agency should install this product.

SPECIFIC SAFETY RULES AND PRECAUTIONS

1.Only Natural gas or Propane (LP) gas are approved for use with this furnace.

2.Install this furnace only in a location and position as specified in these instructions.

3.A gas-fired furnace for installation in a residential garage must be installed as specified in these instructions.

4.Provide adequate combustion and ventilation air to the furnace space as specified in these instructions.

5.Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in SEC- TION VII, "COMBUSTION AIR and VENT SYSTEM" of these instructions.

6.Test for gas leaks as specified in these instructions.

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in serious injury, death or property damage.

Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for detection of leaks to check all connections. A fire or explosion may result causing prop- erty damage, personal injury or loss of life.

7.Always install the furnace to operate within the furnace’s intended temperature rise range. Only connect the furnace to a duct system which has an external static pressure within the allowable range, as specified on the furnace rating plate.

8.When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the fur- nace casing and terminating outside the space containing the fur- nace.

9.It is permitted to use the furnace for heating of buildings or struc- tures under construction where the application and use must com- ply with all manufacturer’s installation instructions including:

Proper vent installation;

Furnace operating under thermostatic control;

Return air duct sealed to the furnace;

Air filters in place;

Set furnace input rate and temperature rise per rating plate marking;

Means for providing outdoor air required for combustion;

Return air temperature maintained between 55ºF (13ºC) and 80ºF (27ºC);

The air filter must be replaced upon substantial completion of the construction process;

Clean furnace, duct work and components upon substantial completion of the construction process, and verify furnace- operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.

10.When installed in a non-HUD-Approved Modular Home or building constructed on-site, combustion air shall not be supplied from occupied spaces.

11.The size of the unit should be based on an acceptable heat loss calculation for the structure. ACCA, Manual J or other approved methods may be used.

SAFETY REQUIREMENTS

This product must be installed in strict compliance with the installa- tion instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes.

Refer to the unit rating plate for the furnace model number, and then see the dimensions page of this instruction for return air ple- num dimensions in Figures 12. The plenum must be installed according to the instructions.

Provide clearances from combustible materials as listed under Clearances to Combustibles.

Provide clearances for servicing ensuring that service access is allowed for both the burners and blower.

These models ARE NOT CSA listed or approved for installation into a HUD Approved Modular Home or a Manufactured (Mobile) Home.

This furnace is not approved for installation in trailers or recre- ational vehicles.

Furnaces for installation on combustible flooring shall not be installed directly on carpeting, tile or other combustible material other than wood flooring.

Check the rating plate and power supply to be sure that the elec- trical characteristics match. All models use nominal 115 VAC, 1 Phase, 60-Hz power supply. DO NOT CONNECT THIS APPLI- ANCE TO A 50-Hz POWER SUPPLY OR A VOLTAGE ABOVE 130 VOLTS.

Furnace shall be installed so the electrical components are pro- tected from water.

Installing and servicing heating equipment can be hazardous due to the electrical components and the gas fired components. Only trained and qualified personnel should install, repair, or service gas heating equipment. Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters. When working on heating equipment, observe precau- tions in the manuals and on the labels attached to the unit and other safety precautions that may apply.

COMBUSTION AIR QUALITY (LIST OF CONTAMINANTS)

The furnace requires OUTDOOR AIR for combustion when the furnace is located in any of the following environments.

Buildings with indoor pools

Chemical exposure

Commercial buildings

Furnaces installed in hobby or craft rooms

Furnaces installed in laundry rooms

Furnaces installed near chemical storage areas

Restricted Environments

The furnace requires OUTDOOR AIR for combustion when the furnace is located in an area where the furnace is being exposed to the follow- ing substances and / or chemicals.

Antistatic fabric softeners for clothes dryers

Carbon tetrachloride

Cements and glues

Chlorinated waxes and cleaners

Chlorine-based swimming pool chemicals

Cleaning solvents (such as perchloroethylene)

De-icing salts or chemicals

Halogen type refrigerants

Hydrochloric acid

Masonry acid washing materials

Permanent wave solutions

Printing inks, paint removers, varnishes, etc.

Water softening chemicals

When outdoor air is used for combustion, the combustion air intake duct system termination must be located external to the building and in an area where there will be no exposure to the substances listed above.

2

Johnson Controls Unitary Products

Image 2
Contents List of Figures Section I SafetyList of Sections List of TablesCombustion AIR Quality List of Contaminants Specific Safety Rules and PrecautionsSafety Requirements Directly BELOW. Keep Clear of ALL OBSTRUC- Tions Codes and StandardsInspection Ductwork General Information Section II DuctworkFurnace Location and Clearances COIL/FURNACE Assembly MC/FC/PC Series Coils Floor Base and Ductwork Installation DownflowCoil Installation Furnace Assembly MC & FC Series CoilsCoil / Furnace Assembly HC Series Coils Furnace Assembly MC Series Coils onlyFurnace Assembly PC Series Coils Coil Size Dimension C InchSuspended Furnace / Crawl Space Installation Downflow Duct Connectors Attic InstallationBottom Return and Attic Installations Horizontal ApplicationSection III Filters Filter InstallationAttempt to install filters inside the furnace Side ReturnSection IV GAS Piping Manifold Pressures in. w.c Manifold Pressures kPa Section V Electrical PowerElectrical Power Connections First Stage Manifold Pressures in. w.cAfue LOW Voltage Control Wiring ConnectionsSupply Voltage Connections LbsAC 9A TWO Stage Variable Speed Furnace OD Models AC 24C Optional HarnessID Models OD Models Humidifier Connection Accessory ConnectionsElectronic AIR Cleaner Connection TwinningCondensate Drain Termination Condensate Drain Trap and Drain Freeze ProtectionWill cause the furnace Airflow Horizontal Left Horizontal Right Inducer AS Received Combustion AIR/VENT Pipe Sizing Combustion AIR and Vent SafetySection VII Combustion AIR and Vent System Fitting Equivalent Length Combustion AIR and Vent Piping AssemblyCombustion AIR / Venting Furnace Vent Connection SizesVent Clearances Home LayoutVenting Multiple Units Vent SystemVent Applications and Termination Combustion Air Source From Outdoors Combustion AIR SupplyOutdoor Combustion Air Ambient Combustion Air SupplyVertical Duct or Air Supply Openings and DuctsFree Area 13 cmVentilated Combustion Air Termination Specially Engineered InstallationsVentilated Combustion Air Vent Blower RotationIgnition System Sequence Section Viii START-UP AdjustmentsGAS Piping Leak Check Calculating the Furnace Input Natural GASRevolution Cu Ft Seconds For Size of Test Dial Revolution Cu FtSeconds For Read the manifold gas pressure Adjustment of Manifold GAS Pressure & Input RateRead the inlet gas pressure Inlet GAS Pressure RangeSection IX Safety Controls Limit Controls Sequence of OperationHot Surface Ignition System TroubleshootingFurnace Control Diagnostics Slow Green Flash Normal operationDiagnostic Fault Code Storage and Retrieval Description Section X Replacement Parts ListReplacement Part Contact Information Section XI Wiring Diagram Johnson Controls Unitary Products York Drive Norman, OK Supersedes 438335-UIM-A-0209

TM9V MP specifications

The Johnson Controls TM9V MP is a cutting-edge variable capacity air conditioning system designed to provide optimal comfort and energy efficiency for residential and light commercial applications. This model is engineered with advanced technologies that cater to the needs of modern consumers who prioritize both performance and sustainability.

One of the standout features of the TM9V MP is its variable-speed compressor. Unlike traditional systems that operate at a fixed speed, this system can adjust its output based on the indoor temperature and humidity levels. This capability allows for precise temperature control and reduces energy consumption, ultimately leading to significant savings on utility bills. By maintaining a more consistent temperature, the TM9V MP enhances overall comfort in living spaces.

Another critical aspect of the TM9V MP is its integration of intelligent control technology. The system comes equipped with a user-friendly interface, which enables homeowners to easily monitor and adjust settings according to their preferences. Smart home integration is also a key feature, allowing for remote access and control through compatible smart devices. This ensures that users can manage their HVAC settings from anywhere, providing convenience and peace of mind.

The TM9V MP is also designed with high-efficiency ratings, often achieving SEER ratings above 18. This excellent performance not only complies with stringent energy efficiency regulations but also qualifies for various rebates and incentives in many regions, making it a financially attractive choice. The unit’s environmentally friendly refrigerant further emphasizes its commitment to sustainability.

In terms of construction and durability, the TM9V MP boasts a rugged design with high-quality components. Its enhanced sound insulation minimizes operational noise, making it suitable for residential settings where quiet operation is essential. The unit is also designed for easy installation and maintenance, which can further reduce lifecycle costs.

Overall, the Johnson Controls TM9V MP represents a blend of advanced engineering, energy efficiency, and user-friendly technology. Its variable speed compressor, smart controls, high-efficiency ratings, and durable construction make it a top choice for anyone seeking an HVAC solution that meets modern comfort and sustainability standards. With the TM9V MP, users can enjoy the benefits of a comfortable indoor environment while contributing to a greener future.