Johnson Controls TM9V MP Downflow Duct Connectors Attic Installation, Horizontal Application

Page 7

438335-UIM-B-0509

DOWNFLOW DUCT CONNECTORS

ATTIC INSTALLATION

All downflow installations must use a suitable duct connector approved by the furnace manufacturer for use with this furnace. The duct connec- tors are designed to be connected to the rectangular duct under the floor and sealed. Refer to the instructions supplied with the duct con- nector for proper installation. Refer to the separate accessory parts list at the end of these instructions for the approved accessory duct con- nectors.

FURNACE

Line contact only permissible between lines formed by the intersection of furnace top and two sides and building joists, studs or framing

Filter rack

 

must be a minimum

 

distance

Gas Piping

of 18” (45.7 cm)

 

from the

 

furnace

 

Supply

Air

Vent (Maintain required clearances to combustibles)

 

Sheet metal in

 

front of furnace

 

combustion air

12”

Openings is

 

 

Recommended

12

30” MIN. Work Area

WARM AIR PLENUM

WITH 1” FLANGES

FIBERGLASS

INSULATION

FIBERGLASS TAPE

UNDER FLANGE

COMBUSTIBLE FLOOR

BASE ACCESSORY

FIGURE 8: Combustible Floor Base Accessory

RESIDENTIAL AND MODULAR HOME UPFLOW RETURN PLENUM CONNECTION

Return air may enter the furnace through the side(s) or bottom depend- ing on the type of application. Return air may not be connected into the rear panel of the unit.

BOTTOM RETURN AND ATTIC INSTALLATIONS

Bottom return applications normally pull return air through a base plat- form or return air plenum. Be sure the return platform structure or return air plenum is suitable to support the weight of the furnace.

The internal bottom panel must be removed for this application.

Attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility.

HORIZONTAL APPLICATION

FIGURE 9: Horizontal Application

This furnace may be installed in a horizontal position on either side as shown above. It must not be installed on its back.

Return

AirSediment

Trap

FIGURE 10: Typical Attic Installation

This appliance is certified for line contact when the furnace is installed in the horizontal left or right position. The line contact is only permissible between lines that are formed by the intersection of the top and two sides of the furnace and the building joists, studs or framing. This line may be in contact with combustible material. Refer to Figures 10.

When a furnace is installed in an attic or other insulated space, keep all insulating materials at least 12” (30.5 cm) away from fur- nace and burner combustion air openings.

SUSPENDED FURNACE / CRAWL SPACE INSTALLATION

The furnace can be hung from floor joists or installed on suitable blocks or pad. Blocks or pad installations shall provide adequate height to ensure the unit will not be subject to water damage. Units may also be suspended from rafters or floor joists using rods, pipe angle supports or straps. Angle supports should be placed at the supply air end and near the blower deck. Do not support at return air end of unit. All four sus- pension points must be level to ensure quite furnace operation. When suspending the furnace use a secure platform constructed of plywood or other building material secured to the floor joists. Refer to for typical crawl space installation.

Support

Rod

Support

Angle (x3)

Maintain 6” minimum clearance between support rods and front of furnace

FIGURE 11: Typical Suspended Furnace / Crawl Space Installation

Johnson Controls Unitary Products

7

Image 7
Contents List of Tables Section I SafetyList of Sections List of FiguresSafety Requirements Specific Safety Rules and PrecautionsCombustion AIR Quality List of Contaminants Inspection Codes and StandardsDirectly BELOW. Keep Clear of ALL OBSTRUC- Tions Furnace Location and Clearances Section II DuctworkDuctwork General Information Furnace Assembly MC & FC Series Coils Floor Base and Ductwork Installation DownflowCoil Installation COIL/FURNACE Assembly MC/FC/PC Series CoilsCoil Size Dimension C Inch Furnace Assembly MC Series Coils onlyFurnace Assembly PC Series Coils Coil / Furnace Assembly HC Series CoilsHorizontal Application Downflow Duct Connectors Attic InstallationBottom Return and Attic Installations Suspended Furnace / Crawl Space InstallationSide Return Filter InstallationAttempt to install filters inside the furnace Section III FiltersSection IV GAS Piping First Stage Manifold Pressures in. w.c Section V Electrical PowerElectrical Power Connections Manifold Pressures in. w.c Manifold Pressures kPaLbs LOW Voltage Control Wiring ConnectionsSupply Voltage Connections AfueAC 9A TWO Stage Variable Speed Furnace OD Models Optional Harness AC 24CID Models OD Models Twinning Accessory ConnectionsElectronic AIR Cleaner Connection Humidifier ConnectionCondensate Drain Trap and Drain Freeze Protection Condensate Drain TerminationWill cause the furnace Airflow Horizontal Left Horizontal Right Inducer AS Received Section VII Combustion AIR and Vent System Combustion AIR and Vent SafetyCombustion AIR/VENT Pipe Sizing Furnace Vent Connection Sizes Combustion AIR and Vent Piping AssemblyCombustion AIR / Venting Fitting Equivalent LengthHome Layout Vent ClearancesVent Applications and Termination Vent SystemVenting Multiple Units Ambient Combustion Air Supply Combustion AIR SupplyOutdoor Combustion Air Combustion Air Source From Outdoors13 cm Air Supply Openings and DuctsFree Area Vertical Duct orVent Blower Rotation Specially Engineered InstallationsVentilated Combustion Air Ventilated Combustion Air TerminationCalculating the Furnace Input Natural GAS Section Viii START-UP AdjustmentsGAS Piping Leak Check Ignition System SequenceSeconds For Seconds For Size of Test Dial Revolution Cu FtRevolution Cu Ft Inlet GAS Pressure Range Adjustment of Manifold GAS Pressure & Input RateRead the inlet gas pressure Read the manifold gas pressureSection IX Safety Controls Sequence of Operation Limit ControlsSlow Green Flash Normal operation TroubleshootingFurnace Control Diagnostics Hot Surface Ignition SystemDiagnostic Fault Code Storage and Retrieval Replacement Part Contact Information Section X Replacement Parts ListDescription Section XI Wiring Diagram Supersedes 438335-UIM-A-0209 Johnson Controls Unitary Products York Drive Norman, OK

TM9V MP specifications

The Johnson Controls TM9V MP is a cutting-edge variable capacity air conditioning system designed to provide optimal comfort and energy efficiency for residential and light commercial applications. This model is engineered with advanced technologies that cater to the needs of modern consumers who prioritize both performance and sustainability.

One of the standout features of the TM9V MP is its variable-speed compressor. Unlike traditional systems that operate at a fixed speed, this system can adjust its output based on the indoor temperature and humidity levels. This capability allows for precise temperature control and reduces energy consumption, ultimately leading to significant savings on utility bills. By maintaining a more consistent temperature, the TM9V MP enhances overall comfort in living spaces.

Another critical aspect of the TM9V MP is its integration of intelligent control technology. The system comes equipped with a user-friendly interface, which enables homeowners to easily monitor and adjust settings according to their preferences. Smart home integration is also a key feature, allowing for remote access and control through compatible smart devices. This ensures that users can manage their HVAC settings from anywhere, providing convenience and peace of mind.

The TM9V MP is also designed with high-efficiency ratings, often achieving SEER ratings above 18. This excellent performance not only complies with stringent energy efficiency regulations but also qualifies for various rebates and incentives in many regions, making it a financially attractive choice. The unit’s environmentally friendly refrigerant further emphasizes its commitment to sustainability.

In terms of construction and durability, the TM9V MP boasts a rugged design with high-quality components. Its enhanced sound insulation minimizes operational noise, making it suitable for residential settings where quiet operation is essential. The unit is also designed for easy installation and maintenance, which can further reduce lifecycle costs.

Overall, the Johnson Controls TM9V MP represents a blend of advanced engineering, energy efficiency, and user-friendly technology. Its variable speed compressor, smart controls, high-efficiency ratings, and durable construction make it a top choice for anyone seeking an HVAC solution that meets modern comfort and sustainability standards. With the TM9V MP, users can enjoy the benefits of a comfortable indoor environment while contributing to a greener future.