Trane RT-PRC005 manual Table PD-48, Table PD-49

Page 41

Performance

(7½Ton)

Data

High Efficiency

 

 

 

 

Table PD-48 — Belt Drive Evaporator Fan Performance — 7½-Ton — THC092A3,A4,AW — Downflow Airflow

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

.10

 

.20

 

.30

 

.40

.50

 

.60

 

 

.70

 

 

.80

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

2-HP Standard Motor & Field Supplied

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Static Drive (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2400

583

0.50

627

0.61

669

0.72

 

708

0.83

743

0.95

776

1.08

808

1.21

2700

611

0.60

653

0.71

693

0.83

 

731

0.95

768

1.07

801

1.20

832

1.33

3000

604

0.61

643

0.71

682

0.83

719

0.95

 

755

1.08

791

1.21

824

1.35

856

1.48

3300

599

0.63

639

0.74

678

0.86

713

0.97

748

1.09

 

783

1.23

815

1.37

848

1.52

880

1.66

3600

601

0.68

640

0.79

675

0.89

713

1.02

748

1.14

780

1.26

 

811

1.40

844

1.55

874

1.70

904

1.86

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-HP Standard Motor & Drive

 

 

 

For Standard Evaporator Fan Speed (RPM), reference Table PD-50.

NOTES:

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories 2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750

1. Field Supplied Fan Sheave AK79 and Belt AX38 required.

Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-48— Continued

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

1.10

 

1.20

 

1.30

 

1.40

1.50

1.60

 

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

2-HP Standard Motor & Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2400

839

1.34

868

1.48

898

1.61

926

1.75

953

1.89

980

2.04

1006

2.18

1032

2.34

1056

2.49

1080

2.64

2700

862

1.48

891

1.62

918

1.77

946

1.92

971

2.07

998

2.23

1023

2.38

1049

2.54

1074

2.70

1097

2.86

3000

886

1.63

915

1.78

942

1.93

968

2.09

994

2.25

1019

2.42

1044

2.59

1067

2.75

1092

2.93

1115

3.09

3300

910

1.81

939

1.96

967

2.12

993

2.28

1019

2.45

1043

2.62

1066

2.79

1091

2.98

1113

3.15

1136

3.34

3600

933

2.01

962

2.17

990

2.33

1016

2.49

1042

2.66

1067

2.84

1091

3.02

1114

3.21

1137

3.39

1158

3.58

 

 

 

 

 

 

 

 

 

3-HP Oversized Motor & Drive

 

 

 

 

 

 

 

Table PD-49 — Belt Drive Evaporator Fan Performance — 7½-TonTHC092A3,A4,AW—Horizontal Airflow

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

.10

 

.20

 

.30

 

.40

.50

 

.60

 

 

.70

 

 

.80

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

2-HP Standard Motor & Field Supplied

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Static Drive (1)

 

 

 

 

 

 

 

 

 

 

 

 

2400

603

0.52

653

0.63

707

0.75

754

0.88

 

792

0.99

825

1.09

857

1.19

886

1.30

2700

595

0.56

644

0.66

686

0.77

732

0.89

780

1.03

 

824

1.17

863

1.30

895

1.42

925

1.54

3000

605

0.65

644

0.73

684

0.82

726

0.94

765

1.06

806

1.20

 

849

1.35

891

1.51

929

1.66

962

1.80

3300

658

0.84

694

0.93

728

1.02

767

1.15

805

1.28

840

1.40

 

876

1.55

916

1.71

955

1.89

991

2.06

3600

711

1.07

746

1.18

776

1.27

 

809

1.38

846

1.52

880

1.66

 

912

1.80

943

1.95

980

2.13

1016

2.30

 

 

 

 

 

 

 

 

 

 

2-HP Standard Motor & Drive

 

 

 

 

 

 

 

For Standard Evaporator Fan Speed (RPM), reference Table PD-50.

NOTES:

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories 2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.

3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750

1. Field Supplied Fan Sheave AK79 and Belt AX38 required..

Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-49 — Continued

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

1.10

 

1.20

 

1.30

 

1.40

1.50

1.60

 

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

2-HP Standard Motor & Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

2400

913

1.40

941

1.51

966

1.61

991

1.71

1017

1.82

1040

1.92

1064

2.04

1087

2.14

1110

2.26

1132

2.37

2700

954

1.66

981

1.77

1006

1.89

1030

2.00

1054

2.12

1077

2.24

1100

2.36

1121

2.47

1144

2.60

1164

2.71

3000

992

1.94

1019

2.07

1045

2.20

1069

2.32

1094

2.46

1116

2.58

1138

2.71

1160

2.84

1181

2.97

1202

3.10

3300

1025

2.22

1055

2.38

1082

2.53

1108

2.67

1132

2.82

1156

2.96

1178

3.11

1200

3.25

1221

3.39

3600

1052

2.50

1085

2.69

1117

2.88

1144

3.05

1170

3.21

1193

3.37

 

 

 

 

3-HP Oversized Motor & Drive

 

 

 

 

 

 

 

 

 

 

 

 

RT-PRC005-EN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41

Image 41
Contents Packaged Cooling with Electric Heat Rooftop Units American Standard Inc. All rights reserved IntroductionContents Features and Benefits Single-Side Service Easy Access LowVoltageTerminal BoardStandardized Components LowVoltage ConnectionsAccess Hinged Access DoorsClogged Filter/Fan Fail Switches EconomizerWe test designs at our factory not on our customers Quality And ReliabilityTestingVariTrac ReliaTelCondensateTrap Barometric ReliefClearance Requirements Unit PitchCooling Capacity Step Selection ProcedureHeating Capacity Step Air Delivery Selection036 11 12,13 Model Number Description5Ton GeneralData Table GD 1 General DataTable GD 2- General Data 10TonEER2 Outdoor Sound Rating dB4 Outdoor Coil -TypeSeer / EER2 Table GD 3 General DataOptional Hot Gas Reheat Coil -Type Refrigerant Charge Lbs of R-224Motor RPM Standard/Oversized 1750 Table GD 4- General DataIntegrated Part LoadValue IPLV3 4Ton PerformanceTSC048A1 MBH SHC MBH MBH SHC MBH SHC MBH SHCMBH SHC MBHMBH SHC MBH ½Ton½, 8½Ton 10 Ton MBH SHC MBH SHC MBH 24.8 51.4 45.6 AmbientTemperature F 105 11569.3 34.7 53.7 60.162.9 65.3 57.2 10001300 68.2 73.8 51.7 56.6 73.6 42.572.2 74.5 61.4 74.7 75.3 70.6½, 10 Ton 113.2 40.0 118.4107.6 79.7ESP BHP ESPTSC036A TSC048ATable PD-21 3TonTable PD-22 HP Standard Motor Field Supplied High Static DriveHP Standard Motor Table PD-23Table PD-26 Table PD-25CFM RPM BHP BHP RPM BHP RPM BHP HP Standard Motor & Field SuppliedTable PD-27 TonTable PD-28 HP Oversized Motor & DriveHP Standard Motor & High Static Drive Table PD-29Table PD-30 Table PD-31 ½ TonTable PD-32 HP Oversized MotorHP Standard Motor & Drive HP Oversized Motor & Drive Table PD-33Table PD-34 HP Standard Motor & Field Supplied Low Static Drive Table PD-35Table PD-36 CFM ESP BHP THC060ATable PD-39 Table PD-38Table PD-41 Table PD-40HP Standard Motor & Field Supplied High Static Drive HP Standard Motor Field Supplied High Static Drive2Table PD-42 Static Drive Accessory Kit Motor & DrivePD-43 HP Standard Motor & Low HPStandardTable PD-45 Table PD-44Table PD-47 Table PD-46HP Standard Motor & Drive Or 2 HP Oversized Motor & DriveTable PD-49 Table PD-48HP Standard Motor & Field Supplied LowStaticDrive1 Table PD-50Table PD-51 Table PD-53 HP Standard Motor & Low Static Drive Accessory KitTable PD-52 Table PD-54 Static DriveAccessory KitTable PD-55 HP Standard Motor & LowPerformance Data Table PD-59- Outdoor Sound Power Level dB ref -12WattsTable PD-56- Standard Motor & Sheave/Fan Speed Rpm Table PD-58- Oversized Motor & Drive Sheave/Fan Speed RpmTHC036A TSC060AK Table PD-62- Auxiliary Electric Heat CapacityTSC090AK TSC102AKScfm Table PD-65- Hot Gas ReheatTemperature Rise3Tons 10TonsZone Controls Humidity Sensor Field installed, wall-mountedRemote Sensor Automatic Changeover One HeatDataEfficiency Table ED-1 UnitWiring Standard EfficiencyElectrical Standard Electrical High Table ED-2 UnitWiring High Efficiency208/230 Volts Three Phase 208/230 Volts Single PhaseVolts Three Phase Volts Three Phase 208/230 Volts Single Phase BAYHTRT354A ElectricalBAYHTRT454A Electrical DataBAYHTRRW06A THC036AW BAYHTRRW12A BAYHTRR110A BAYHTRR114A BAYHTRR105A FLA LRA 3450 11.3 3450TSC036A4 460 3450 575 3450Table ED-15- Electrical Characteristics Power Exhaust Jobsite Connections Power Wires + 1 Ground Wire three phaseData3-5Tons DimensionalData3-5Tons Downflow Duct Connections Field Fabricated Data6-10Tons 10Tons Unit Clearance and Roof Opening 10Tons Downflow Duct Connections Field Fabricated 10Tons Roof CurbSwing Diameter for Hinged Doors Option DimensionalData Accessories 10Tons Options THC048A WeightsTableW-2 Factory-installed Options Net Weights Lbs1,2 Mechanical Specifications Accessories/Options Control Options PL-UN-RT-TSC/THC 3-10TONS-PRC005-EN-02-03 PL-UN-RT-TSC/THC 3-10TONS-PRC005-EN-03-03