Performance | (7½Ton) |
Data | High Efficiency |
|
|
|
|
Table
|
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
| |||||
| .10 |
| .20 |
| .30 |
| .40 | .50 |
| .60 |
|
| .70 |
|
| .80 | .90 |
| 1.00 | ||
CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
| Low Static Drive (1) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
2400 | — | — | — | — | — | — | 583 | 0.50 | 627 | 0.61 | 669 | 0.72 |
| 708 | 0.83 | 743 | 0.95 | 776 | 1.08 | 808 | 1.21 |
2700 | — | — | — | — | — | — | 611 | 0.60 | 653 | 0.71 | 693 | 0.83 |
| 731 | 0.95 | 768 | 1.07 | 801 | 1.20 | 832 | 1.33 |
3000 | — | — | — | — | 604 | 0.61 | 643 | 0.71 | 682 | 0.83 | 719 | 0.95 |
| 755 | 1.08 | 791 | 1.21 | 824 | 1.35 | 856 | 1.48 |
3300 | — | — | 599 | 0.63 | 639 | 0.74 | 678 | 0.86 | 713 | 0.97 | 748 | 1.09 |
| 783 | 1.23 | 815 | 1.37 | 848 | 1.52 | 880 | 1.66 |
3600 | 601 | 0.68 | 640 | 0.79 | 675 | 0.89 | 713 | 1.02 | 748 | 1.14 | 780 | 1.26 |
| 811 | 1.40 | 844 | 1.55 | 874 | 1.70 | 904 | 1.86 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
For Standard Evaporator Fan Speed (RPM), reference Table
NOTES:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-48— Continued
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
| |||||
|
| 1.10 |
| 1.20 |
| 1.30 |
| 1.40 | 1.50 | 1.60 |
| 1.70 | 1.80 | 1.90 | 2.00 | |||||
CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
2400 | 839 | 1.34 | 868 | 1.48 | 898 | 1.61 | 926 | 1.75 | 953 | 1.89 | 980 | 2.04 | 1006 | 2.18 | 1032 | 2.34 | 1056 | 2.49 | 1080 | 2.64 |
2700 | 862 | 1.48 | 891 | 1.62 | 918 | 1.77 | 946 | 1.92 | 971 | 2.07 | 998 | 2.23 | 1023 | 2.38 | 1049 | 2.54 | 1074 | 2.70 | 1097 | 2.86 |
3000 | 886 | 1.63 | 915 | 1.78 | 942 | 1.93 | 968 | 2.09 | 994 | 2.25 | 1019 | 2.42 | 1044 | 2.59 | 1067 | 2.75 | 1092 | 2.93 | 1115 | 3.09 |
3300 | 910 | 1.81 | 939 | 1.96 | 967 | 2.12 | 993 | 2.28 | 1019 | 2.45 | 1043 | 2.62 | 1066 | 2.79 | 1091 | 2.98 | 1113 | 3.15 | 1136 | 3.34 |
3600 | 933 | 2.01 | 962 | 2.17 | 990 | 2.33 | 1016 | 2.49 | 1042 | 2.66 | 1067 | 2.84 | 1091 | 3.02 | 1114 | 3.21 | 1137 | 3.39 | 1158 | 3.58 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Table
|
|
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
| |||||
| .10 |
| .20 |
| .30 |
| .40 | .50 |
| .60 |
|
| .70 |
|
| .80 | .90 |
| 1.00 | |||
CFM | RPM | BHP | RPM | BHP | RPM | BHP |
| RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
| Low Static Drive (1) |
|
|
|
|
|
|
|
|
|
|
|
| |||
2400 | — | — | — | — | 603 | 0.52 | 653 | 0.63 | 707 | 0.75 | 754 | 0.88 |
| 792 | 0.99 | 825 | 1.09 | 857 | 1.19 | 886 | 1.30 | |
2700 | — | — | 595 | 0.56 | 644 | 0.66 | 686 | 0.77 | 732 | 0.89 | 780 | 1.03 |
| 824 | 1.17 | 863 | 1.30 | 895 | 1.42 | 925 | 1.54 | |
3000 | 605 | 0.65 | 644 | 0.73 | 684 | 0.82 | 726 | 0.94 | 765 | 1.06 | 806 | 1.20 |
| 849 | 1.35 | 891 | 1.51 | 929 | 1.66 | 962 | 1.80 | |
3300 | 658 | 0.84 | 694 | 0.93 | 728 | 1.02 | 767 | 1.15 | 805 | 1.28 | 840 | 1.40 |
| 876 | 1.55 | 916 | 1.71 | 955 | 1.89 | 991 | 2.06 | |
3600 | 711 | 1.07 | 746 | 1.18 | 776 | 1.27 |
| 809 | 1.38 | 846 | 1.52 | 880 | 1.66 |
| 912 | 1.80 | 943 | 1.95 | 980 | 2.13 | 1016 | 2.30 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
For Standard Evaporator Fan Speed (RPM), reference Table
NOTES:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table
1. Field Supplied Fan Sheave AK79 and Belt AX38 required..
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-49 — Continued
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
| |||||
| 1.10 |
| 1.20 |
| 1.30 |
| 1.40 | 1.50 | 1.60 |
| 1.70 | 1.80 | 1.90 | 2.00 | ||||||
CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
2400 | 913 | 1.40 | 941 | 1.51 | 966 | 1.61 | 991 | 1.71 | 1017 | 1.82 | 1040 | 1.92 | 1064 | 2.04 | 1087 | 2.14 | 1110 | 2.26 | 1132 | 2.37 |
2700 | 954 | 1.66 | 981 | 1.77 | 1006 | 1.89 | 1030 | 2.00 | 1054 | 2.12 | 1077 | 2.24 | 1100 | 2.36 | 1121 | 2.47 | 1144 | 2.60 | 1164 | 2.71 |
3000 | 992 | 1.94 | 1019 | 2.07 | 1045 | 2.20 | 1069 | 2.32 | 1094 | 2.46 | 1116 | 2.58 | 1138 | 2.71 | 1160 | 2.84 | 1181 | 2.97 | 1202 | 3.10 |
3300 | 1025 | 2.22 | 1055 | 2.38 | 1082 | 2.53 | 1108 | 2.67 | 1132 | 2.82 | 1156 | 2.96 | 1178 | 3.11 | 1200 | 3.25 | 1221 | 3.39 | — | — |
3600 | 1052 | 2.50 | 1085 | 2.69 | 1117 | 2.88 | 1144 | 3.05 | 1170 | 3.21 | 1193 | 3.37 | — | — | — | — | — | — | — | — |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 41 |