General | (3 - 5Ton) |
Data | High Efficiency |
|
|
|
|
Table GD - 3 — General Data
| 3Ton | 4Ton |
| 5Ton |
| Convertible Units | Convertible Units | Convertible Units | |
| THC036A1,A3,A4,AW | THC048A1,A3,A4,AW | THC060A1 | THC060A3,A4,AW |
Cooling Performance1 |
|
|
|
|
Gross Cooling Capacity | 38,000 | 49,800 | 62,100 | 62,400 |
SEER / EER2 | 12.5/— | 12.0/— | 11.8/— | 12.0/ — |
Nominal CFM / ARI Rated CFM | 1,200/1,200 | 1,600/1,600 | 2,000/2,000 | 2,000/2,000 |
ARI Net Cooling Capacity | 36,600 | 47,500 | 59,000 | 59,500 |
System Power (kW) | 3.33 | 4.48 | 5.73 | 5.56 |
Compressor |
|
|
|
|
No./Type | 1/Climatuff Scroll | 1/Climatuff Scroll | 1/Climatuff Scroll | 1/Climatuff Scroll |
Outdoor Sound Rating (dB)3 | 83 | 85 | 84 | 84 |
Outdoor Coil | Lanced | Lanced | Lanced | Lanced |
Tube Size (in.) O.D. | 0.3125 | 0.3125 | 0.3125 | 0.3125 |
Face Area (sq ft) | 7.19 | 9.59 | 10.96 | 10.96 |
Rows/FPI | 2/17 | 3/17 | 3/17 | 3/17 |
Indoor Coil | Lanced | Lanced | Lanced | Lanced |
Tube Size (in.) | 0.3125 | 0.3125 | 0.3125 | 0.3125 |
Face Area (sq ft) | 6.68 | 6.68 | 7.71 | 7.71 |
Rows/FPI | 3/16 | 4/16 | 4/16 | 4/16 |
Refrigerant Control | Short Orifice | Short Orifice | Short Orifice | Short Orifice9 |
Drain Connection No./Size (in.) | 1/¾ NPT | 1/¾ NPT | 1/¾ NPT | 1/¾ NPT |
Outdoor Fan | Propeller | Propeller | Propeller | Propeller |
No. Used/Diameter (in.) | 1/22 | 1/22 | 1/22 | 1/22 |
DriveType/No. Speeds | Direct/1 | Direct/1 | Direct/1 | Direct/110 |
CFM | 2550 | 3050 | 3170 | 3370 |
No. Motors/HP | 1/.20 | 1/.33 | 1/.33 | 1/.33 |
Motor RPM | 1115 | 1115 | 1115 | 1115 |
Direct Drive Indoor Fan | FC Centrifugal | FC Centrifugal | FC Centrifugal | FC Centrifugal |
No. Used | 1 | 1 | 1 | 1 |
Diameter xWidth (in.) | 10 x 10 | 11 x 11 | 11 x 11 | 11 x 11 |
DriveType/No. Speeds | Direct/2 | Direct/2 | Direct/2 | Direct/2 |
No. Motors | 1 | 1 | 1 | 1 |
Motor HP (Standard/Oversized) | .33/.50 | .60/.80 | .90/1.00 | .90/1.00 |
Standard Motor RPM (Low/High Speed) | 950/1060 | 930/1000 | 985/1100 | 985/1100 |
Oversized Motor RPM (Low/High Speed) | 1100/1145 | 1000/1100 | 1080/1135 | 1080/1135 |
Motor Frame Size (Standard/Oversized) | 48/48 | 48/48 | 48/48 | 48/48 |
Belt Drive Indoor Fan | FC Centrifugal | FC Centrifugal | — | FC Centrifugal |
No. Used | 1 | 1 | — | 1 |
Diameter xWidth (in.) | 11 x 11 | 11 x 11 | — | 11 x 11 |
DriveType/No. Speeds | Belt/Variable Speed 6 | Belt/Variable Speed 6 | — | Belt/Variable Speed |
No. Motors | 1 | 1 | — | 1 |
Motor HP | 1.00 | 1.00 | — | 1.00 |
Standard Motor RPM | 1750 | 1750 | — | 1750 |
Motor Frame Size | 56 | 56 | — | 56 |
Filters | Throwaway | Throwaway | Throwaway | Throwaway |
(No.) Size Recommended (in.) | (2) 20 x 25 x 1 | (2) 20 x 25 x 1 | (2) 20 x 30 x 1 | (2) 20 x 30 x 111 |
Optional Hot Gas Reheat Coil | — | — | — | Lanced |
Tube Size (in.) OD | — | — | — | 0.375 |
Face Area (sq. ft) | — | — | — | 2.22 |
Rows/FPI | — | — | — | 2/18 |
Refrigerant Charge (Lbs of |
|
|
|
|
Standard | 5.38 | 7.75 | 7.9 | 8.4 |
Optional Hot Gas Reheat Coil | — | — | — | 10.7 |
NOTES:
1.Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary
2.EER and SEER are rated at ARI conditions and in accordance with DOE test procedures.
3.Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table
4.Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5.Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 8.1.
6.Belt Drive Motor is not available for THC036A1, THC048A1.
7.Optional 2” Pleated Filters also available.
8.Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 4.5.
9.TXV is supplied from the factory as standard with the Dehumidification (Hot Gas Reheat) option.
10.With Dehumidification (Hot Gas Reheat) option: Direct/2.
11.2" pleated filters is a factory installed option. 2" pleated filters is standard with the Dehumidification (Hot Gas Reheat) option.
13 |