Trane RT-PRC005 manual Control Options

Page 75

Mechanical Specifications

Supply and/or Return Air Smoke Detector —With this option factory- installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models. See the Installation, Operation, and Maintenance (IOM) manual for the models affected and the minimum allowable airflow required.This option is available for microprocessor controlled units.

Black Epoxy Coated Condenser Coil — The coil provides corrosion protection to condenser coils for seacoast application. The protection is a factory-applied thermoset vinyl coating, bonded to normal aluminum fin stock.The uniform thickness of the bonded vinyl layer exhibits excellent corrosion protection in salt spray tests performed in accordance with ASTM B117.

Dehumidification Option —The dehumidification (hot gas reheat) option shall be a factory-installed option that provides increased dehumidification.The option shall consist of a hot-gas reheat coil located on the leaving air side of the evaporator coil prepiped and circuited.

The option shall be equipped with crankcase heater(s), low pressure switch(es), Frostat™, and a thermostatic expansion valve(s) (TXV) as standard.

Control Options

Trane Communication Interface — This factory or field-installed option shall be provided to interface microprocessor controlled units with theTrane Integrated ComfortTM systems.

LonTalk® Communication Interface — This factory or field-installed option shall be provided to allow the unit to communicate as aTracer™LCI-R device or directly with generic LonTalk Network Building Automation System Controls.

Zone Sensor —This field-installed control shall be provided to interface with the Micro equipped units and shall be available in either manual, automatic programmable with night setback, with system malfunction lights, or remote sensor options.

Thermostat —Two stage heating and cooling operation or one stage heating and cooling shall be available, for field installation, in either manual or automatic changeover. Automatic programmable electronic with night set back shall also be available.

Differential Pressure Switches —These factory or field-installed sensors allow individual fan failure and dirty filter indication for microprocessor controlled units.The fan failure switch will disable all unit functions and “flash” the Service LED on the zone sensor.The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation.

Enthalpy Control — Replaces the dry bulb control with a wet bulb changeover controller which has a fully adjustable set point. Enthalpy control offers a higher level of comfort control, along with energy savings potential, than the standard dry bulb control. This is due to the additional wet bulb sensing capability.This option shall be available for microprocessor controlled units. It can be field-installed, or factory-installed with the factory-installed economizer.

Differential Enthalpy — Replaces the standard dry bulb control with two enthalpy sensors that compare total heat content of the indoor air and outdoor air to determine the most efficient air source.This control option offers the highest level of comfort control, plus energy efficiency, available.This option shall be available for microprocessor controlled units. It can be field-installed, or factory-installed with the factory- installed economizer.

Low Ambient Cooling — All microprocessor units shall have cooling capabilities down to 0°F as standard. Electromechanical models have cooling capabilites to 40°F as built, or to 0°F by adding the optional low ambient (frostat) control.

Thermal ExpansionValve — All units shall have a short orifice refrigerate control metering device. For more exact refrigerant flow, when using unit in low airflow applications, aThermal ExpansionValve option shall be available.

Novar Unit Controls — Optional Novar rooftop unit controls shall be factory installed and tested. The Novar electronic thermostat module will interface to the unit microprocesser and will control the unit to the desired stage of cooling or heating.

Novar Return Air Sensor —This option, when used in conjunction with Novar Controls, will contain a factory provided and wired zone temperature snesor located in the return air stream.

CO2 Sensing —The CO2 sensor shall have the ability to to monitor space occupancy levels within the building by measuring the parts per million of CO2 (Carbon Dioxide) in the air. As the CO2 levels increase, the outside air damper modulates to meet the CO2 space ventilation requirements.The CO2 accessory shall be available as field installed.

Ventilation Override Accessory —With theVentilation Override Accessory installed, the unit can be set to transition to up to 3 different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust.The transition occurs when a binary input on the RTOM is closed (shorted).This would typically be a hard wired relay output from a smoke detector of fire control panel.The ventilation override accessory shall be available as field installed.

Humidity Sensor (BAYSENS036) —Field installed, wall-mounted humidity sensor is used to control activation of the hot gas reheat dehumidification option.The humidity sensor can be set for humidity levels between 40% and 60% relative humidity by adjusting the ReliaTel Options Module.

Humidity Sensor (BAYSENS037) —Field installed, duct-mounted humidity sensor is used to control activation of the hot gas reheat dehumidification option.The humidity sensor can be set for humidity levels between 40% and 60% relative humidity by adjusting the ReliaTel Options Module.

RT-PRC005-EN

75

Image 75
Contents Packaged Cooling with Electric Heat Rooftop Units American Standard Inc. All rights reserved IntroductionContents Features and Benefits LowVoltage Connections Easy Access LowVoltageTerminal BoardSingle-Side Service Standardized ComponentsEconomizer Hinged Access DoorsAccess Clogged Filter/Fan Fail SwitchesReliaTel Quality And ReliabilityTestingWe test designs at our factory not on our customers VariTracUnit Pitch Barometric ReliefCondensateTrap Clearance RequirementsAir Delivery Selection Selection ProcedureCooling Capacity Step Heating Capacity Step036 11 12,13 Model Number DescriptionTable GD 1 General Data General5Ton DataOutdoor Sound Rating dB4 Outdoor Coil -Type 10TonTable GD 2- General Data EER2Refrigerant Charge Lbs of R-224 Table GD 3 General DataSeer / EER2 Optional Hot Gas Reheat Coil -TypeTable GD 4- General Data Integrated Part LoadValue IPLV3Motor RPM Standard/Oversized 1750 MBH SHC MBH MBH SHC MBH SHC MBH SHC Performance4Ton TSC048A1MBH SHC MBHMBH SHC MBH ½Ton½, 8½Ton 10 Ton MBH SHC MBH SHC MBH 60.1 AmbientTemperature F 105 11524.8 51.4 45.6 69.3 34.7 53.71000 130062.9 65.3 57.2 74.7 75.3 70.6 56.6 73.6 42.568.2 73.8 51.7 72.2 74.5 61.4½, 10 Ton 79.7 118.4113.2 40.0 107.6TSC048A ESPESP BHP TSC036AHP Standard Motor Field Supplied High Static Drive 3TonTable PD-21 Table PD-22HP Standard Motor Table PD-23HP Standard Motor & Field Supplied Table PD-25Table PD-26 CFM RPM BHP BHP RPM BHP RPM BHPHP Oversized Motor & Drive TonTable PD-27 Table PD-28Table PD-29 Table PD-30HP Standard Motor & High Static Drive HP Oversized Motor ½ TonTable PD-31 Table PD-32Table PD-33 Table PD-34HP Standard Motor & Drive HP Oversized Motor & Drive Table PD-35 Table PD-36HP Standard Motor & Field Supplied Low Static Drive CFM ESP BHP THC060ATable PD-39 Table PD-38HP Standard Motor Field Supplied High Static Drive2 Table PD-40Table PD-41 HP Standard Motor & Field Supplied High Static DriveHP Standard Motor & Low HPStandard Static Drive Accessory Kit Motor & DriveTable PD-42 PD-43Table PD-45 Table PD-44Motor & Drive Or 2 HP Oversized Motor & Drive Table PD-46Table PD-47 HP StandardTable PD-49 Table PD-48Table PD-50 Table PD-51HP Standard Motor & Field Supplied LowStaticDrive1 HP Standard Motor & Low Static Drive Accessory Kit Table PD-52Table PD-53 HP Standard Motor & Low Static DriveAccessory KitTable PD-54 Table PD-55Table PD-58- Oversized Motor & Drive Sheave/Fan Speed Rpm Table PD-59- Outdoor Sound Power Level dB ref -12WattsPerformance Data Table PD-56- Standard Motor & Sheave/Fan Speed RpmTHC036A TSC102AK Table PD-62- Auxiliary Electric Heat CapacityTSC060AK TSC090AK10Tons Table PD-65- Hot Gas ReheatTemperature Rise3Scfm TonsAutomatic Changeover One Heat Humidity Sensor Field installed, wall-mountedZone Controls Remote SensorTable ED-1 UnitWiring Standard Efficiency Electrical StandardDataEfficiency Electrical High Table ED-2 UnitWiring High Efficiency208/230 Volts Three Phase 208/230 Volts Single PhaseVolts Three Phase Volts Three Phase 208/230 Volts Single Phase BAYHTRT354A ElectricalBAYHTRT454A Electrical DataBAYHTRRW06A THC036AW BAYHTRRW12A BAYHTRR110A BAYHTRR114A BAYHTRR105A FLA LRA 575 3450 34503450 11.3 TSC036A4 460 3450Table ED-15- Electrical Characteristics Power Exhaust Jobsite Connections Power Wires + 1 Ground Wire three phaseData3-5Tons DimensionalData3-5Tons Downflow Duct Connections Field Fabricated Data6-10Tons 10Tons Unit Clearance and Roof Opening 10Tons Downflow Duct Connections Field Fabricated 10Tons Roof CurbDimensional Data AccessoriesSwing Diameter for Hinged Doors Option 10Tons Options Weights TableW-2 Factory-installed Options Net Weights Lbs1,2THC048A Mechanical Specifications Accessories/Options Control Options PL-UN-RT-TSC/THC 3-10TONS-PRC005-EN-02-03 PL-UN-RT-TSC/THC 3-10TONS-PRC005-EN-03-03