General | (3 - 5Ton) |
Data | Standard Efficiency |
|
|
|
|
Table GD - 1 — General Data
| 3Ton Convertible Units | 4Ton Convertible Units | 5Ton Convertible Units |
| |||
TSC036A1, A3, A4, AW | TSC048A1 | TSC048A3, A4, AW | TSC060A1 | TSC060A3, A4, AW |
| TSC060AK | |
Cooling Performance1 |
|
|
|
|
|
|
|
Gross Cooling Capacity | 37,400 | 50,300 | 49,200 | 63,100 | 63,100 |
| 63,100 |
SEER2 | 10.75 | 10.1 | 10.0 | 9.9 | 10.2 |
| 10.2 |
Nominal CFM / ARI Rated CFM | 1,200/1,200 | 1,600/1,600 | 1,600/1,600 | 2,000/2,000 | 2,000/2,000 |
| 2,000/2,000 |
ARI Net Cooling Capacity | 36,000 | 48,000 | 47,000 | 60,000 | 60,000 |
| 60,000 |
System Power (kW) | 3.918 | 5.28 | 5.40 | 6.86 | 6.78 |
| 6.78 |
Compressor |
|
|
|
|
|
|
|
No./Type | 1/Recip. | 1/Scroll | 1/Scroll | 1/Scroll | 1/Scroll |
| 1/Scroll |
Outdoor Sound Rating (dB)3 | 83 | 86 | 82 | 84 | 84 |
| 84 |
Outdoor Coil | Lanced | Lanced | Lanced | Lanced | Lanced |
| Lanced |
Tube Size (in.) O.D. | 0.3125 | 0.3125 | 0.3125 | 0.3125 | 0.3125 |
| 0.3125 |
Face Area (sq ft) | 7.19 | 6.17 | 9.59 | 8.81 | 8.81 |
| 8.81 |
Rows/FPI | 2/17 | 2/17 | 1/17 | 2/17 | 2/17 |
| 2/17 |
Indoor Coil | Lanced | Lanced | Lanced | Lanced | Lanced |
| Lanced |
Tube Size (in.) | 0.3125 | 0.3125 | 0.3125 | 0.3125 | 0.3125 |
| 0.3125 |
Face Area (sq ft) | 5.67 | 6.68 | 6.17 | 5.00 | 5.00 |
| 5.00 |
Rows/FPI | 2/16 | 3/16 | 3/16 | 3/16 | 3/16 |
| 3/16 |
Refrigerant Control | Short Orifice | Short Orifice | Short Orifice | Short Orifice | Short Orifice |
| Short Orifice |
Drain Connection No./Size (in.) | 1/¾ NPT | 1/¾ NPT | 1/¾ NPT | 1/¾ NPT | 1/¾ NPT |
| 1/¾ NPT |
Outdoor Fan | Propeller | Propeller | Propeller | Propeller | Propeller |
| Propeller |
No. Used/Diameter (in.) | 1/22 | 1/22 | 1/22 | 1/22 | 1/22 |
| 1/22 |
DriveType/No. Speeds | Direct/1 | Direct/1 | Direct/1 | Direct/1 | Direct/1 |
| Direct/1 |
CFM | 2550 | 2850 | 3610 | 3470 | 3470 |
| 3470 |
No. Motors/HP | 1/.20 | 1/.33 | 1/.33 | 1/.33 | 1/.33 |
| 1/.40 |
Motor RPM | 1115 | 1115 | 1115 | 1115 | 1115 |
| 1115 |
Direct Drive Indoor Fan | FC Centrifugal | FC Centrifugal | FC Centrifugal | FC Centrifugal | FC Centrifugal | FC Centrifugal | |
No. Used | 1 | 1 | 1 | 1 | 1 |
| 1 |
Diameter xWidth (in.) | 10 x 10 | 11 x 11 | 11 x 11 | 11 x 11 | 11 x 11 |
| 12x11/– |
DriveType/No. Speeds | Direct/2 | Direct/2 | Direct/2 | Direct/2 | Direct/2 |
| Direct/2 |
No. Motors | 1 | 1 | 1 | 1 | 1 |
| 1 |
Motor HP (Standard/Oversized) | .33/.50 | .60/.80 | .60/.80 | .90/1.00 | .90/1.00 |
| 1.0/– |
Motor RPM (Low/High Speed) | 950/1060 | 930/1000 | 930/1000 | 985/1100 | 985/1100 |
| 935/1100 |
Oversized Motor RPM |
|
|
|
|
|
|
|
(Low/High Speed) | 1100/1145 | 1000/1100 | 1000/1100 | 1080/1135 | 1080/1135 |
| — |
Motor Frame Size |
|
|
|
|
|
|
|
(Standard/Oversized) | 48/48 | 48/48 | 48/48 | 48/48 | 48/48 |
| 48/— |
Belt Drive Indoor Fan | FC Centrifugal | — | FC Centrifugal | — | FC Centrifugal |
| — |
No. Used | 1 | — | 1 | — | 1 |
| — |
Diameter xWidth (in.) | 11 x 11 | — | 11 x 11 | — | 11 x 11 |
| — |
DriveType/No. Speeds | Belt/Variable Speed6 | — | Belt/Variable Speed | — | Belt/Variable Speed | — | |
No. Motors | 1 | — | 1 | — | 1 |
| — |
Motor HP | 1.00 | — | 1.00 | — | 1.00 |
| — |
Motor RPM | 1750 | — | 1750 | — | 1750 |
| — |
Motor Frame Size | 56 | — | 56 | — | 56 |
| — |
Filters | Throwaway | Throwaway | Throwaway | Throwaway | Throwaway |
| Throwaway |
(No.) Size Recommended (in.) | (2) 20 x 25 x 1 | (2) 20 x 25 x 1 | (2) 20 x 25 x 1 | (2) 20 x 25 x 1 | (2) 20 x 25 x 1 | (2) 20 x 25 x 1 | |
Refrigerant Charge (Lbs of | 3.8 | 4.4 | 3.8 | 4.7 | 4.9 |
| 4.9 |
NOTES:
1.Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary
2.SEER is rated at ARI conditions and in accordance with DOE test procedures.
3.Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table
4.Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5.TSC036A1 SEER is 10.5.
6.Belt Drive Motor is not available for TSC036A1.
7.Optional 2” Pleated Filters also available.
8.TSC036A1 System Power (kW) is 3.79.