Mechanical Specifications

General

The units shall be convertible airflow. The operating range shall be between 115°F and 0°F in cooling as standard from the factory for units with microprocessor controls. Operating range for units with electromechanical controls shall be between 115°F and 40°F. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-22, and 100 percent run tested to check cooling operation, fan and blower rotation, and control sequence before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/CAN/CSA No. 236-M90 for Central Cooling Air Conditioners. Canadian units shall be CSA Certified.

Casing

Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit’s surface shall be tested 1000 hours in a salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. Service panels shall have lifting handles and be removed and reinstalled by removing only a single fastener while providing a water and air tight seal. All exposed vertical panels and top covers in the indoor air section shall be insulated with a cleanable foil-faced, fire-retardent permanent, odorless glass fiber material. The base of the unit shall be insulated with 1/2 inch, 1 pound density foil-faced, closed-cell material. All insulation edges shall be either captured or sealed.The unit’s base pan shall have no penetrations within the perimeter of the curb other than the raised 11/8 inch high downflow supply/ return openings to provide an added water integrity precaution, if the condensate drain backs up.The base of the unit shall have provisions for forklift and crane lifting, with forklift capabilities on three sides of the unit.

RT-PRC005-EN

UnitTop

The top cover shall be one piece construction or where seams exist, it shall be double-hemmed and gasket- sealed. The ribbed top adds extra strength and prevents water from pooling on unit top.

Filters

One inch, throwaway filters shall be standard on all 3-5 ton units.The filter rack can be converted to two inch capability.Two inch filters shall be factory supplied on all 6-10 ton units. Optional 2- inch pleated filters shall be available.

Compressors

All 3 ton standard units shall have direct- drive, hermetic, reciprocating type compressors.The reciprocating type compressors have a centrifugal oil pump providing positive lubrication to moving parts. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Crankcase heater, internal temperature, and current- sensitive motor overloads shall be included for maximum protection. Compressors shall have internal spring isolation and sound muffling to minimize vibration transmission and noise. Low pressure switches shall be standard.

3 ton high efficiency and 4-10 ton standard and high efficiency units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas- cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Internal overloads shall be provided with the scroll compressors.

Refrigerant Circuits

Each refrigerant circuit offers a choice of independent fixed orifice expansion devices or thermal expansion valve. Service pressure ports, and refrigerant line filter driers are factory-installed as standard. An area shall be provided for replacement suction line driers.

Evaporator and Condenser Coils Internally finned, 5/16” copper tubes mechanically bonded to a configured aluminum plate fin shall be standard. Coils shall be leak tested at the factory to ensure the pressure integrity.The evaporator coil and condenser coil shall

be leak tested to 200 psig and pressure tested to 450 psig.The condensor coil shall have a patent pending 1 + 1 + 1 hybrid coil designed with slight gaps for ease of cleaning. A removeable, reversible, double-sloped condensate drain pan with provision for through the base condensate drain is standard.

Outdoor Fans

The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position.The fan motor shall be permanently lubricated and shall have built-in thermal overload protection.

Indoor Fan

All 3-5 ton 3-phase units offer a choice of direct-drive, FC, centrifugal fans or belt driven, FC centrifugal fans with adjustable motor sheaves. 3-5 ton direct drive oversized motors shall be available for high static operations. All 6-10 ton units shall have belt drive motors with an adjustable idler-arm assembly for quick-adjustment to fan belts and motor sheaves. All motors shall be thermally protected. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT).

Controls

Unit shall be completely factory-wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device.

A choice of microprocessor or electromechanical controls shall be available.

Microprocessor controls provide for all

24volt control functions.The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures.The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized Microprocessor shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection.

73

Image 73
Contents Packaged Cooling with Electric Heat Rooftop Units American Standard Inc. All rights reserved IntroductionContents Features and Benefits Single-Side Service Easy Access LowVoltageTerminal BoardStandardized Components LowVoltage ConnectionsAccess Hinged Access DoorsClogged Filter/Fan Fail Switches EconomizerWe test designs at our factory not on our customers Quality And ReliabilityTestingVariTrac ReliaTelCondensateTrap Barometric ReliefClearance Requirements Unit PitchCooling Capacity Step Selection ProcedureHeating Capacity Step Air Delivery Selection036 11 12,13 Model Number Description5Ton GeneralData Table GD 1 General DataTable GD 2- General Data 10TonEER2 Outdoor Sound Rating dB4 Outdoor Coil -TypeSeer / EER2 Table GD 3 General DataOptional Hot Gas Reheat Coil -Type Refrigerant Charge Lbs of R-224Integrated Part LoadValue IPLV3 Table GD 4- General DataMotor RPM Standard/Oversized 1750 4Ton PerformanceTSC048A1 MBH SHC MBH MBH SHC MBH SHC MBH SHCMBH SHC MBHMBH SHC MBH ½Ton½, 8½Ton 10 Ton MBH SHC MBH SHC MBH 24.8 51.4 45.6 AmbientTemperature F 105 11569.3 34.7 53.7 60.11300 100062.9 65.3 57.2 68.2 73.8 51.7 56.6 73.6 42.572.2 74.5 61.4 74.7 75.3 70.6½, 10 Ton 113.2 40.0 118.4107.6 79.7ESP BHP ESPTSC036A TSC048ATable PD-21 3TonTable PD-22 HP Standard Motor Field Supplied High Static DriveHP Standard Motor Table PD-23Table PD-26 Table PD-25CFM RPM BHP BHP RPM BHP RPM BHP HP Standard Motor & Field SuppliedTable PD-27 TonTable PD-28 HP Oversized Motor & DriveTable PD-30 Table PD-29HP Standard Motor & High Static Drive Table PD-31 ½ TonTable PD-32 HP Oversized MotorTable PD-34 Table PD-33HP Standard Motor & Drive HP Oversized Motor & Drive Table PD-36 Table PD-35HP Standard Motor & Field Supplied Low Static Drive CFM ESP BHP THC060ATable PD-39 Table PD-38Table PD-41 Table PD-40HP Standard Motor & Field Supplied High Static Drive HP Standard Motor Field Supplied High Static Drive2Table PD-42 Static Drive Accessory Kit Motor & DrivePD-43 HP Standard Motor & Low HPStandardTable PD-45 Table PD-44Table PD-47 Table PD-46HP Standard Motor & Drive Or 2 HP Oversized Motor & DriveTable PD-49 Table PD-48Table PD-51 Table PD-50HP Standard Motor & Field Supplied LowStaticDrive1 Table PD-52 HP Standard Motor & Low Static Drive Accessory KitTable PD-53 Table PD-54 Static DriveAccessory KitTable PD-55 HP Standard Motor & LowPerformance Data Table PD-59- Outdoor Sound Power Level dB ref -12WattsTable PD-56- Standard Motor & Sheave/Fan Speed Rpm Table PD-58- Oversized Motor & Drive Sheave/Fan Speed RpmTHC036A TSC060AK Table PD-62- Auxiliary Electric Heat CapacityTSC090AK TSC102AKScfm Table PD-65- Hot Gas ReheatTemperature Rise3Tons 10TonsZone Controls Humidity Sensor Field installed, wall-mountedRemote Sensor Automatic Changeover One HeatElectrical Standard Table ED-1 UnitWiring Standard EfficiencyDataEfficiency Electrical High Table ED-2 UnitWiring High Efficiency208/230 Volts Three Phase 208/230 Volts Single PhaseVolts Three Phase Volts Three Phase 208/230 Volts Single Phase BAYHTRT354A ElectricalBAYHTRT454A Electrical DataBAYHTRRW06A THC036AW BAYHTRRW12A BAYHTRR110A BAYHTRR114A BAYHTRR105A FLA LRA 3450 11.3 3450TSC036A4 460 3450 575 3450Table ED-15- Electrical Characteristics Power Exhaust Jobsite Connections Power Wires + 1 Ground Wire three phaseData3-5Tons DimensionalData3-5Tons Downflow Duct Connections Field Fabricated Data6-10Tons 10Tons Unit Clearance and Roof Opening 10Tons Downflow Duct Connections Field Fabricated 10Tons Roof CurbData Accessories DimensionalSwing Diameter for Hinged Doors Option 10Tons Options TableW-2 Factory-installed Options Net Weights Lbs1,2 WeightsTHC048A Mechanical Specifications Accessories/Options Control Options PL-UN-RT-TSC/THC 3-10TONS-PRC005-EN-02-03 PL-UN-RT-TSC/THC 3-10TONS-PRC005-EN-03-03