Performance | (10 Ton) |
Data | High Efficiency |
|
|
|
|
Table
|
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
| ||||
| .10 |
|
| .20 |
| .30 |
| .40 |
| .50 |
| .60 |
| .70 | .80 |
| .90 |
| 1.00 | |
CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
3200 | — | — | — | — | — | — | — | — | 734 | 1.03 | 770 | 1.17 | 804 | 1.31 | 839 | 1.45 | 871 | 1.60 | 901 | 1.74 |
3600 | — | — | — | — | 714 | 1.02 | 749 | 1.14 | 782 | 1.27 | 815 | 1.41 | 847 | 1.57 | 879 | 1.73 | 909 | 1.89 | 939 | 2.04 |
4000 | — | — | 734 | 1.16 | 768 | 1.30 | 803 | 1.44 | 834 | 1.58 | 863 | 1.72 | 894 | 1.87 | 923 | 2.04 | 952 | 2.21 | 979 | 2.39 |
4400 | 764 | 1.36 | 795 | 1.49 | 825 | 1.63 | 857 | 1.79 | 888 | 1.95 | 916 | 2.10 | 943 | 2.25 | 970 | 2.41 | 997 | 2.59 | 1024 | 2.78 |
4800 | 828 | 1.74 | 857 | 1.88 | 884 | 2.02 | 913 | 2.18 | 942 | 2.36 | 970 | 2.53 | 996 | 2.70 | 1021 | 2.86 | 1045 | 3.03 | 1070 | 3.22 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
For Standard Evaporator Fan Speed (RPM), reference Table
NOTES:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table
1.Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-52 — Continued
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
|
| |||||
|
| 1.10 |
| 1.20 |
| 1.30 |
| 1.40 | 1.50 | 1.60 |
| 1.70 | 1.80 | 1.90 |
| 2.00 | |||||
CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP |
| RPM | BHP |
| |||||||||||||||||||||
3200 | 931 | 1.89 | 959 | 2.06 | 986 | 2.22 | 1012 | 2.39 | 1037 | 2.56 | 1061 | 2.74 | 1084 | 2.91 | 1108 | 3.09 | 1131 | 3.28 |
| 1153 | 3.46 |
3600 | 969 | 2.21 | 997 | 2.37 | 1024 | 2.54 | 1050 | 2.72 | 1074 | 2.89 | 1098 | 3.08 | 1122 | 3.27 | 1145 | 3.46 | 1166 | 3.65 |
| 1188 | 3.85 |
4000 | 1007 | 2.57 | 1034 | 2.74 | 1062 | 2.93 | 1087 | 3.11 | 1112 | 3.29 | 1136 | 3.47 | 1159 | 3.66 | 1182 | 3.86 | 1204 | 4.07 |
| 1226 | 4.28 |
4400 | 1050 | 2.97 | 1075 | 3.17 | 1101 | 3.36 | 1126 | 3.55 | 1150 | 3.75 | 1173 | 3.94 | 1198 | 4.15 | 1219 | 4.34 | 1241 | 4.54 |
| 1264 | 4.77 |
4800 | 1095 | 3.42 | 1119 | 3.62 | 1143 | 3.83 | 1166 | 4.05 | 1189 | 4.26 | 1212 | 4.47 | 1235 | 4.68 | 1258 | 4.90 | 1280 | 5.12 |
| 1300 | 5.32 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Table
|
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
| |||||
|
| .10 |
| .20 |
| .30 | .40 |
|
| .50 |
| .60 |
|
| .70 |
| .80 | .90 |
| 1.00 |
|
CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | |
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
| Static Drive Accessory Kit (1) |
|
|
| Static Drive Accessory Kit (2) | |||||||||
2000 | — | — | — | — | — | — | 568 | 0.43 | 613 | 0.53 | 653 | 0.64 |
| 691 | 0.75 | 727 | 0.86 | 763 | 0.98 | 797 | 1.10 |
2400 | — | — | — | — | — | — | 606 | 0.56 | 650 | 0.67 | 691 | 0.78 |
| 728 | 0.90 | 763 | 1.02 | 796 | 1.16 | 826 | 1.29 |
2800 | — | — | 564 | 0.50 | 607 | 0.60 | 649 | 0.71 | 689 | 0.83 | 728 | 0.95 |
| 766 | 1.08 | 801 | 1.21 | 833 | 1.35 | 864 | 1.50 |
3200 | 576 | 0.57 | 618 | 0.67 | 659 | 0.79 | 697 | 0.90 | 734 | 1.03 | 770 | 1.17 |
| 804 | 1.31 | 839 | 1.45 | 871 | 1.60 | 901 | 1.74 |
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils. Data does not include pressure drop due to reheat coil.
1.BAYLSDR010ARequired.
2.BAYLSDR010ARequired.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will notbeaffected.
Table PD-53 — Continued
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
|
| |||||
|
| 1.10 |
| 1.20 |
| 1.30 |
| 1.40 | 1.50 | 1.60 | 1.70 | 1.80 | 1.90 | 2.00 |
| ||||||
CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | |
|
|
|
|
|
|
|
|
|
| 3 HP Standard Motor & Drive |
|
|
|
|
|
|
|
| |||
2000 | 828 | 1.22 | 859 | 1.35 | 888 | 1.48 | 917 | 1.61 | 945 | 1.75 | 971 | 1.88 | 998 | 2.03 | 1023 | 2.19 | 1048 | 2.35 | 1072 | 2.50 |
|
2400 | 858 | 1.43 | 888 | 1.56 | 916 | 1.70 | 945 | 1.85 | 972 | 1.99 | 998 | 2.14 | 1023 | 2.29 | 1050 | 2.45 | 1073 | 2.60 | 1097 | 2.76 |
|
2800 | 894 | 1.65 | 921 | 1.79 | 949 | 1.95 | 975 | 2.11 | 1001 | 2.27 | 1027 | 2.43 | 1051 | 2.59 | 1076 | 2.75 | 1100 | 2.92 | 1123 | 3.09 |
|
3200 | 931 | 1.89 | 959 | 2.06 | 986 | 2.22 | 1012 | 2.39 | 1037 | 2.56 | 1061 | 2.74 | 1084 | 2.91 | 1108 | 3.09 | 1131 | 3.28 | — | — |
|
43 |