Trane RT-PRC005 manual Selection Procedure, Cooling Capacity Step, Heating Capacity Step

Page 9

Selection Procedure

Cooling Capacity

Step 1

Calculate the building’s total and sensible cooling loads at design conditions. Use theTrane calculation methods or any other standard accepted method.

Factors used in unit selection:

A

Total Cooling Load: 59 MBh

B

Sensible Cooling Load: 40 MBh

C

Airflow: 2000 cfm

D

Electrical Characteristics: 460/60/3

E

Summer Design Conditions: Entering

Evaporator Coil: 80 DB, 67WB Outdoor

Ambient: 95

F

External Static Pressure: 0.45 in. wg

Step 2

As a starting point, a rough determination must be made of the size of the unit.The final selection will be made after examining the performance at the given conditions. Divide the total cooling load by nominal BTUH per ton (12 MBh per ton); then round up to the nearest unit size.

60 MBh / 12 MBh = 5Tons

Step 3

Table PD-4 shows that aTSC060A4 has a gross cooling capacity of 63.1 MBh and

48.2MBh sensible capacity at 2000 cfm and 95 DB outdoor ambient with 80 DB, 67WB air entering the evaporator.

To Find Capacity at Intermediate Conditions Not in theTable

When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity. Note: Extrapolation outside of the table conditions is not recommended.

Step 4

In order to select the correct unit which meets the building’s requirements, the fan motor heat must be deducted from the gross cooling capacity.The amount of heat that the fan motor generates is dependent on the effort by the motor - cfm and static pressure.To determine the total unit static pressure:

External Static (duct system)

0.45 wg

Standard Filter 1 in.

0.15 wg

fromTable PD-59

 

Economizer

0.02 wg

(100% Return Air) fromTable PD-26

Electric Heater Size 6 kW

0.05 wg

fromTable PD-51

 

Total Static Pressure

0.67 wg

Note:The Evaporator Fan Performance Table PD-20 has deducted the pressure drop for a 1 in. filter already in the unit (see note belowTable PD-20).Therefore, the actual total static pressure is 0.67 - 0.15 (fromTable PD - 26) = 0.52 wg.

With 2000 cfm and 0.52 wg.

Table PD-20 shows .90 bhp for this unit. Note below the table gives a formula to calculate Fan Motor Heat,

4.39x bhp = MBH.

4.39x .90 = 3.95 MBH.

Now subtract the fan motor heat from the gross cooling capacity of the unit: NetTotal Cooling Capacity

= 60 MBH - 3.95 = 56.05 MBH.

Net Sensible Cooling Capacity = 48.2 MBH - 3.95 = 44.25 MBH.

Step 5

If the performance will not meet the required load of the building’s total or sensible cooling load, try a selection at the next higher size unit.

Heating Capacity

Step 1

Calculate the building heating load using theTrane calculation form or other standard accepted method.

Step 2

Size the system heating capacity to match the calculated building heating load.The following are building heating requirements:

A

Total heating load of 15 MBH

B

2000 cfm

C

460 volt/3 phase Power Supply

The electric heat accessory capacities are listed inTable PD-62 From the table, a 6 kW heater will deliver 20.48 MBH at 480 volts. In order to determine capacity at 460 volts, the heater voltage correction factor fromTable PD-60 must be used.Therefore, 20.48 MBH x .9118 (voltage correction factor) = 18.80 MBH.

Air Delivery Selection

External static pressure drop through the air distribution system has been calculated to be 0.45 inches of water. FromTable PD-59 static pressure drop through the economizer is 0.02 and the 6 kW heater is 0.05 inches of water (0.45

+0.02 + 0.05). EnterTable PD-20 for a TSC060A4 at 2000 cfm and 0.52 static pressure.The standard direct drive motor at high speed will give the desired airflow at a rated bhp of 0.90.

RT-PRC005-EN

9

Image 9
Contents Packaged Cooling with Electric Heat Rooftop Units American Standard Inc. All rights reserved IntroductionContents Features and Benefits Single-Side Service Easy Access LowVoltageTerminal BoardStandardized Components LowVoltage ConnectionsAccess Hinged Access DoorsClogged Filter/Fan Fail Switches EconomizerWe test designs at our factory not on our customers Quality And ReliabilityTestingVariTrac ReliaTelCondensateTrap Barometric ReliefClearance Requirements Unit PitchCooling Capacity Step Selection ProcedureHeating Capacity Step Air Delivery Selection036 11 12,13 Model Number Description5Ton GeneralData Table GD 1 General DataTable GD 2- General Data 10TonEER2 Outdoor Sound Rating dB4 Outdoor Coil -TypeSeer / EER2 Table GD 3 General DataOptional Hot Gas Reheat Coil -Type Refrigerant Charge Lbs of R-224Table GD 4- General Data Integrated Part LoadValue IPLV3Motor RPM Standard/Oversized 1750 4Ton PerformanceTSC048A1 MBH SHC MBH MBH SHC MBH SHC MBH SHCMBH SHC MBHMBH SHC MBH ½Ton½, 8½Ton 10 Ton MBH SHC MBH SHC MBH 24.8 51.4 45.6 AmbientTemperature F 105 11569.3 34.7 53.7 60.11000 130062.9 65.3 57.2 68.2 73.8 51.7 56.6 73.6 42.572.2 74.5 61.4 74.7 75.3 70.6½, 10 Ton 113.2 40.0 118.4107.6 79.7ESP BHP ESPTSC036A TSC048ATable PD-21 3TonTable PD-22 HP Standard Motor Field Supplied High Static DriveHP Standard Motor Table PD-23Table PD-26 Table PD-25CFM RPM BHP BHP RPM BHP RPM BHP HP Standard Motor & Field SuppliedTable PD-27 TonTable PD-28 HP Oversized Motor & DriveTable PD-29 Table PD-30HP Standard Motor & High Static Drive Table PD-31 ½ TonTable PD-32 HP Oversized MotorTable PD-33 Table PD-34HP Standard Motor & Drive HP Oversized Motor & Drive Table PD-35 Table PD-36HP Standard Motor & Field Supplied Low Static Drive CFM ESP BHP THC060ATable PD-39 Table PD-38Table PD-41 Table PD-40HP Standard Motor & Field Supplied High Static Drive HP Standard Motor Field Supplied High Static Drive2Table PD-42 Static Drive Accessory Kit Motor & DrivePD-43 HP Standard Motor & Low HPStandardTable PD-45 Table PD-44Table PD-47 Table PD-46HP Standard Motor & Drive Or 2 HP Oversized Motor & DriveTable PD-49 Table PD-48Table PD-50 Table PD-51HP Standard Motor & Field Supplied LowStaticDrive1 HP Standard Motor & Low Static Drive Accessory Kit Table PD-52Table PD-53 Table PD-54 Static DriveAccessory KitTable PD-55 HP Standard Motor & LowPerformance Data Table PD-59- Outdoor Sound Power Level dB ref -12WattsTable PD-56- Standard Motor & Sheave/Fan Speed Rpm Table PD-58- Oversized Motor & Drive Sheave/Fan Speed RpmTHC036A TSC060AK Table PD-62- Auxiliary Electric Heat CapacityTSC090AK TSC102AKScfm Table PD-65- Hot Gas ReheatTemperature Rise3Tons 10TonsZone Controls Humidity Sensor Field installed, wall-mountedRemote Sensor Automatic Changeover One HeatTable ED-1 UnitWiring Standard Efficiency Electrical StandardDataEfficiency Electrical High Table ED-2 UnitWiring High Efficiency208/230 Volts Three Phase 208/230 Volts Single PhaseVolts Three Phase Volts Three Phase 208/230 Volts Single Phase BAYHTRT354A ElectricalBAYHTRT454A Electrical DataBAYHTRRW06A THC036AW BAYHTRRW12A BAYHTRR110A BAYHTRR114A BAYHTRR105A FLA LRA 3450 11.3 3450TSC036A4 460 3450 575 3450Table ED-15- Electrical Characteristics Power Exhaust Jobsite Connections Power Wires + 1 Ground Wire three phaseData3-5Tons DimensionalData3-5Tons Downflow Duct Connections Field Fabricated Data6-10Tons 10Tons Unit Clearance and Roof Opening 10Tons Downflow Duct Connections Field Fabricated 10Tons Roof CurbDimensional Data AccessoriesSwing Diameter for Hinged Doors Option 10Tons Options Weights TableW-2 Factory-installed Options Net Weights Lbs1,2THC048A Mechanical Specifications Accessories/Options Control Options PL-UN-RT-TSC/THC 3-10TONS-PRC005-EN-02-03 PL-UN-RT-TSC/THC 3-10TONS-PRC005-EN-03-03