NOTE: Circuit board programming will not allow spa operation without both the temperature and high limit sensors being properly connected to the circuit board.
7.Once topside panel operation is verified. Turn off power, disconnect the extension loom from the circuit board and GENTLY route through conduit to complete installation.
NOTE: This loom and its connector are not meant to withstand heavy pull- ing. Make sure, when routing the extension loom and temperature sensor lines through conduit, you exercise extreme caution.
Once properly run through the conduit, repeat steps 5 and 6 above.
In-Ground Spa Light Installation Instructions
On spas ordered with
Always read and follow light manufacturer’s safety and installation instruc- tions prior to installation and operation. Incorrect installation may damage the light and void its warranty.
The light circuit must be on a GFCI protected service (alone or with a switch).
The water resistant junction box (or for 12 volt models, the low voltage transformer) must be located:
•at least 8” (20 cm) above water level
•at least 4” (10 cm) above ground level, and
•at least 48” (121 cm) away from the spa.
See figure below.