DMP Electronics XR500 manual Bell Options

Page 41

bell Options

Bell Options

10.1

BELL OPTIONS

Bell Options

This section allows you to program the panel bell output functions.

10.2

BELL CUTOFF: 15

Bell Cutoff Time

Enter the maximum time from 1 to 99 minutes the Bell Output remains on. If the area is disarmed, the cutoff time resets. Enter 0 (zero) to provide continuous bell output. The default is 15 minutes.

Note: To support the Alarm Verify feature on an All/Perimeter or Home/Sleep/Away system, set the Bell Cutoff Time to greater than 0.

Note: For SIA CP-01 False Alarm Reduction Installations, the Bell Cutoff Time must be set to a minimum of six (6) minutes.

10.3

10.4

Automatic Bell Test

Bell tst No YES Select YES to turn on the Bell Output for 2 seconds each time the system is completely­ armed from a keypad. This test is delayed until the Closing Wait acknowledge is received (if programmed). If the Closing Wait acknowledge is not received within 90 seconds, the bell test does not occur. Arming performed from an Arming zone or from Remote Link™ does not activate the Bell Test.

 

 

Bell Output

 

 

Bell outPUT:

0

Enter the output number when needed to follow the panel Bell Output operation for

 

 

all action and off conditions. Enter 0 (zero) to disable.

 

 

 

 

Note: When BELL ACTION is set to T for Temporal Code 3, the Bell Output action for

 

 

an LX-Bus output is pulse.

10.5

Bell ACTION . . . . .

Bell Action

This section defines the type of Bell Output for zone alarms. Press COMMAND to display the default Bell Output for each zone type. Press any Select key and enter S for a Steady Bell Output, P for a Pulsed output, T for a Temporal Code 3 output, and N for no Bell Output.

Note: Trouble conditions do not activate the Bell Output.

10.5.1

10.5.2

10.5.3

10.5.4

10.5.5

10.5.6

10.5.7

 

 

 

Fire Bell Action

 

 

 

Fire

Type:

p

Defines Bell Action for Fire Type zones. The default is P.

 

 

 

Burglary Bell Action

 

 

 

 

 

 

Burglary Type:

S

Defines Bell Action for Burglary Type zones and Exit Error output. The default is S.

 

 

 

Supervisory Bell Action

 

 

 

 

 

 

Suprvsry Type:

N

Defines Bell Action for Supervisory Type zones. The default is N.

 

 

 

Panic Bell Action

 

 

 

 

 

 

Panic

Type:

N

Defines Bell Action for Panic Type zones. The default is N.

 

 

 

Emergency Bell Action

 

 

 

 

 

 

Emergncy Type:

N

Defines Bell Action for Emergency Type zones. The default is N.

 

 

 

Auxiliary 1 Bell Action

 

 

 

 

 

 

Auxlry 1 Type:

N

Defines Bell Action for Auxiliary 1 Type zones. The default is N.

 

 

 

Auxiliary 2 Bell Action

 

 

 

 

 

 

Auxlry 2 Type:

N

Defines Bell Action for Auxiliary 2 Type zones. The default is N.

 

 

 

 

Digital Monitoring Products

XR500 Series Canadian Programming Guide

32

Image 41
Contents Programming Guide Industry Canada Notice Table Of Contents Messaging Setup Bell Options System ReportsOutput Groups Area Information Zone InformationStop Feature UpgradeThis page intentionally left blank Getting Started IntroductionBefore you Begin Encrypted Communications XR500N/XR500E only Reset TimeoutProgrammer Operation Programmer Lockout CodesSpecial Keys Power UpKeypads Entering Non-Alpha Characters Entering Alpha CharactersKeypad Displays Current Programming Special CharactersDevices Areas Multiple DisplaysAsterisks in Programming Initialization Clear Communication and Remote Options Set to Factory DefaultsCommunication Test Report Path TypeTest Frequency Test DayFirst Telephone Number Receiver PortSecond Telephone Number Advanced ProgrammingAlarm Switch Setup StringDuplicate Alarms Retry SecondsDoor Access Report Alarm ReportsSupervisory/Trouble Reports Opening/Closing and User ReportsGateway Address Local IP AddressSubnet Mask DNS ServerMessaging Setup Destination 3 User Number Smtp PasswordEmail Communication Type Smtp ServerDevice Setup User Action Allowed Display AreasStatus Display Allowed Options and Actions Not AffectedStrike Time Strike DelayFire Exit Release Output Group15.1 15.2 Relock on Zone 2 Fault?Program 734 Options Activate Zone 2 ShuntActivate Onboard Speaker 15.6 15.7 15.8Card Options Custom Card DefinitionsRequire Site Code 15.915.9 15.10 Site Code DisplayRemote Options PC Modem Manufacturer AuthorizationAllow Network Remote Network Programming PortEntré Backup TCP Port Entré Backup IP AddressEntré Checkin Entré PassphraseSystem Reports Panic Test Communication XR500N/XR500E only AmbushSystem Options Entry DelaySystem Instant ArmingCross Zone Time Reset Swinger BypassSwgrbyps Trips 1 Swinger Bypass Trips Time Zone ChangesProgramming Menu Language Latch Supervisory ZonesUser Menu and Status List Language City/Time ZoneBypass Limit Detect Wireless JammingCard Plus PIN XR500E only House CodeEnable Keypad Panic Keys Wireless Audible AnnunciationOccupied Premises Enhanced Zone TestBell Options Output Options Sensor Reset Output Panic Alarm Output11.6 11.7 11.811.15 Arm-Alarm OutputClosing Wait Output 11.16Output Information Output Groups Menu Display Status List Burglary Zones 15.5 15.6Supervisory Zones Panic ZonesPrinter Reports PC Log Reports 17.10 Door Acs no YES Door Access Reports17.11 17.12 PC Log Real-Time StatusArea Information Closing Check 18.5 18.6 18.7 18.8 18.9 18.10Closing Code Any BypassHome/Sleep/Away Programming 18.10.2Area Name Automatic ArmingArmed Output Number Late Arm DelayLate Output Number Bank Safe & Vault XR500N/XR500E only19.1 Zone InformationZone Number Zone Name19.5 Zone Type SpecificationsArea Assignment 19.6Arming Zone Area Assignment 19.7 19.8Style Arming Zone OperationWireless DMP Wireless19.9 Next Zone19.10.3 19.10.4 19.10.5 19.10.6 19.10.7 19.10.8 Disarm/DisableLED Operation PIR Pulse Count19.11.1 19.11.2 19.11.3 Series Key FobsKey Fob User Number Key Fob Serial NumberButton Action 19.11.719.11.8 Button Press TimeOutput Action 19.11.10 19.11.11 19.11.12Alarm Action FA Series Wireless 19.1219.12.1 19.12.2 19.12.3 Check-in TimeReport to Transmit 19.15 19.16 19.17Presignal Keypad Addresses Zone Retard Delay19.23 19.24Priority 19.2519.26 Fire Panel Slave InputSet Lockout Code Stop21.1 Set Lockout CodeFeature Upgrade Appendix False Alarm ReductionDiagnostics function Network Results Successful Display Failure Display Cellular Results Successful Display Failure DisplayEmail Results Successful Display Failure Display Successful Display Failure DisplayKeypad Displays Using the 984 Command FunctionWalk Test Using the Walk TestZone Types Trip Counter For Walk TestTest End Warning Trip Counter For DMP Wireless Check-in Test WLSFailed Zones Display Keypad Speaker OperationCross Zoning Report Type Immediately Delayed23.7 Events Manager 23.8 User ProfilesCross Talk FA Series Transmitter InformationKeypad Bus and LX-Bus Zone Type Descriptions Wireless Check-in and Supervision DefinitionsZone Type Specifications Keypad Bus Zone Information Keypad Bus Zone Type DefaultsZone Type Defaults LX-Bus Zone Type DefaultsCommon Keypad Messages Message Meaning Possible SolutionsArea Account Number Messages Revisions to This Document Listings and Approvals Intrusion Fire Access Networks

XR500 specifications

DMP Electronics has made significant waves in the tech industry with its innovative XR500 device, a cutting-edge solution that caters to both professional and consumer needs. The XR500 combines advanced technologies with a user-friendly design to deliver an exceptional user experience.

One of the standout features of the XR500 is its powerful processing capabilities. Equipped with a high-performance processor, the device ensures seamless multitasking and quick access to applications. This allows users to handle demanding tasks such as gaming, content creation, and data analysis without experiencing lag or slowdown.

In terms of display, the XR500 boasts a stunning high-resolution screen that enhances visual clarity and color accuracy. Whether you are watching videos, playing immersive games, or editing images, the vibrant colors and sharp details make every experience enjoyable. The device also supports high refresh rates, providing fluid motion essential for fast-paced gaming.

Another critical characteristic of the XR500 is its versatility. It features multiple connectivity options including USB-C, HDMI, and Bluetooth, enabling users to connect a wide range of peripherals and accessories. This flexibility makes the XR500 suitable for various applications, whether you're in a creative professional environment or simply enjoying media at home.

DMP has also focused on the XR500's audio quality. Equipped with advanced sound technologies, the device delivers an immersive audio experience. Clear and rich sound enhances gaming and movie-watching experiences, ensuring that every detail is heard. The integrated speakers are supplemented by options for external sound systems, catering to audiophiles and casual listeners alike.

Battery life is a crucial consideration for any electronic device, and the XR500 does not disappoint. It features a robust battery that supports extended usage times, making it ideal for users who are constantly on the move. Additionally, fast-charging capabilities ensure that the device can be quickly recharged, minimizing downtime.

Lastly, the XR500 is designed with a sleek and modern aesthetic, combining form and function. Its lightweight and portable design make it easy to transport, ideal for professionals who need to work on the go. With an emphasis on user experience, the XR500 is not just a deviceā€”it's a comprehensive solution that meets the diverse needs of modern users. Whether you are a professional seeking performance or a consumer looking for quality, the DMP Electronics XR500 is a compelling choice that stands out in the market.