Bryant 551A operation manual Ventilation Air Minimum Position Set Up, IX. Install ALL Accessories

Page 15

H. Ventilation Air (Minimum Position Set Up)

If ventilation air is not required, skip this section. If ventila- tion air is required, perform the following:

1.The indoor fan must be on to set the ventilation air. Either put the thermostat in the continuous fan mode or jumper the R and G terminals at the rooftop unit connection board.

2.Locate the minimum position (MIN POS) potentiome- ter. Turn the potentiometer full CCW to fully close the outdoor air dampers. Turn the potentiometer gradually clockwise (CW) to the desired position. See Fig. 16.

3.Replace the filter access panel. See Fig. 18. Ensure the filter access panel is securely engaged.

4.Calculate the minimum airflow across the EconoMi$er.

a.Calculate % of outside air using the following formula.

% Outdoor air through EconoMi$er

% Outdoor

=

Mixture Temp – Return Air Temp

air

Outdoor Temp – Return Air Temp

 

b.Multiply total CFM by percentage outdoor air, this gives outdoor air volume in CFM.

WARNING: Personal Injury Hazard. Avoid possible injury by keeping fingers away from damper blades.

IX. STEP 9 — INSTALL ALL ACCESSORIES

After all the factory-installed options have been adjusted, install all field-installed accessories. Refer to the accessory installation instructions included with each accessory.

A. Motormaster® I Control Installation (551A155 and 180 Only)

Install Field-Fabricated Wind Baffles

Wind baffles must be field-fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures. See Fig. 25 for baffle details. Use 20-gage, galvanized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should be 1/4-in. diameter and 5/8-in. long. Drill required screw holes for mounting baffles.

CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care when drilling holes.

Unoccupied Control (Part number on the control

must be AD-DME1701-1 or AD-DME1711-1.)

Outdoor Air Enthalpy

 

 

 

CROUTENT001A00

 

Unoccupied

 

 

 

Contact

470 ohm

 

 

 

5 watt

 

T

Violet

Resistor

C

 

O

 

 

O

U

 

 

M

T T

 

 

 

PW

 

 

 

 

Tan

OAT

 

Violet

COM

 

W hite

 

 

24 VAC must be present on BI for the system to be unoccupied.

OAH

 

Red

 

+15V

 

 

 

 

 

 

 

 

 

Tan

 

 

 

 

 

 

 

 

 

RAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Violet

COM

 

 

 

 

 

 

 

 

 

 

RAH

 

 

 

 

 

 

 

 

W hite

 

 

Red

+15V

 

 

 

 

 

 

 

 

 

 

 

 

 

CO 2(+)

 

 

 

 

 

 

 

 

 

 

CO 2

 

 

 

 

 

COM

 

 

 

 

 

DAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REM

 

POT

 

 

 

 

COM

 

 

 

 

LED

 

 

 

 

 

 

 

 

COM

 

 

 

 

Violet

C TO

O U

M T T

PW

Remote

Minimum Position

1k ohm Potentiometer

20 mA LED

Remote

LED

Field-supplied W iring

Return Air Enthalpy

CRRETENT001A00

CO2 Sensors:

CRCDXSEN004A00

 

 

2 to 10 VDC at

 

 

0 to 2000 ppm

NOT 2 USED

VAC24 VA20

Line

 

 

 

 

Voltage

1

 

 

-

 

 

W iring Included

Fig. 24 — Typical EconoMi$er Sensor Wiring

15

Image 15
Contents II. RIG and Place Unit ContentsSafety Considerations Installation Provide Unit SupportRoof Curb Details 240 Unit Maximum Dimensions Shipping WeightFt-in 155 1801039 1054 559 180 1650 748 36.3 375 170 449 204 452 Unit STD Unit ECONOMI$ER Corner DIM a DIM B DIM C Weight551A Ft-in 155 1575 714 36.3 407 185 375 170 383 174 410Base Unit Dimensions, 551A240 155 180 240 Physical Data551A180 and 240 Shown 551A155 Shown III. Field Fabricate DuctworkIV. Make Unit Duct Connections Trap Condensate DrainField Control Wiring Unit VoltageNEC FLA LRA MCA MOCP† Electrical DataPER Electric Resistance Heater DataUnit Heater Maximum Minimum Heater AmpsManual Outdoor-Air Damper VII. Make OUTDOOR-AIR Inlet AdjustmentsOptional Non-Fused Disconnect Optional Convenience OutletUnit Stage Heat Anticipator SettingsVIII. Install OUTDOOR-AIR Hood Outdoor Air Enthalpy Sensor InstallationDischarge Air Thermistor DAT CO2 Control SetupMechanical Cooling Lockout Dry Bulb Changeover Set UpEconoMi$er Switchover Control Strategy Default Potentiometer SettingsVentilation Air Minimum Position Set Up IX. Install ALL AccessoriesMotormaster I Control Installation 551A155 and 180 Only Wind Baffle Details Motormaster III Control Installation 551A240 OnlyLPS LlsvSTART-UP III. Refrigerant Service PortsInternal Wiring XI. Accessory ECONOMI$ER AdjustmentUnits With Perfect Humidity Dehumidification Package Freeze Protection ThermostatsFan Performance 551A155 With Standard Indoor Fan Motor Cfm Rpm Watts Bhp Watts BhpWatts Bhp Rpm 3750 5700 551A180 15 Tons4800 5100500 551A240 20 TonsWatts Bhp Rpm Bhp Rpm Watts 000Drop Accessory/FIOP Static Pressure in. wgEvaporator Fan Motor Specifications Fan RPM at Motor Pulley SettingsService Cleaning IV. Evaporator FAN Service and ReplacementII. Lubrication Belt Tension Adjustment Evaporator-Fan Pulley Alignment AdjustmentVII. ECONOMI$ER Adjustment VI. CONDENSER-FAN AdjustmentXI. Protective Devices VIII. Power FailureIX. Refrigerant Charge Filter DrierXIII. Control Circuit XIV. Replacement PartsXVI. Optional Hinged Access Doors XII. Relief DevicesTypical Wiring Schematic 551A180, 460v Shown Typical Component Arrangement 551A180 Shown Troubleshooting Cooling Service AnalysisProblem Cause Remedy Problem Potential Cause Remedy EconoMi$er TroubleshootingPage Temperatures ElectricalGeneral
Related manuals
Manual 170 pages 34.1 Kb