Bryant operation manual 551A240 20 Tons, Watts Bhp Rpm, Bhp Rpm Watts 000, 500, 10,000

Page 23

Table 12 — Fan Performance — 551A240

551A240 (20 TONS)*

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

Cfm

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

6,000

753

2385

2.83

816

2579

3.06

884

2807

3.33

949

3040

3.61

1010

3277

3.89

6,500

793

2738

3.25

861

2959

3.51

925

3186

3.78

987

3418

4.05

1045

3653

4.33

7,000

844

3151

3.74

908

3372

4.00

968

3598

4.27

1026

3828

4.54

1082

4062

4.82

7,500

895

3596

4.27

955

3817

4.53

1013

4042

4.80

1068

4271

5.07

1121

4504

5.34

8,000

947

4073

4.83

1004

4294

5.09

1058

4518

5.36

1111

4747

5.63

1162

4978

5.91

8,500

999

4583

5.44

1053

4803

5.70

1105

5027

5.96

1155

5255

6.23

1204

5485

6.51

9,000

1052

5125

6.08

1103

5345

6.34

1152

5569

6.61

1200

5796

6.88

1247

6025

7.15

9,500

1105

5699

6.76

1153

5919

7.02

1200

6142

7.29

1246

6369

7.56

1291

6598

7.83

10,000

1158

6306

7.48

1204

6526

7.74

1249

6750

8.01

1293

6975

8.27

1336

7203

8.55

 

 

 

 

 

 

 

 

 

 

 

 

 

 

551A240 (20 TONS) (cont)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

Cfm

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

6,000

1069

3517

4.17

1125

3761

4.46

1180

4006

4.75

1232

4255

5.05

1283

4506

5.35

6,500

1102

3891

4.62

1156

4132

4.90

1208

4377

5.19

1259

4623

5.48

1308

4871

5.78

7,000

1136

4299

5.10

1188

4538

5.38

1239

4780

5.67

1288

5025

5.96

1335

5271

6.25

7,500

1173

4739

5.62

1223

4977

5.90

1272

5217

6.19

1319

5460

6.48

1365

5705

6.77

8,000

1211

5212

6.18

1259

5449

6.46

1306

5688

6.75

1352

5929

7.03

1396

6172

7.32

8,500

1251

5718

6.78

1297

5954

7.06

1342

6192

7.35

1386

6431

7.63

1429

6673

7.92

9,000

1292

6257

7.42

1337

6492

7.70

1380

6729

7.98

1423

6967

8.27

1464

7207

8.55

9,500

1335

6830

8.10

1377

7063

8.38

1419

7299

8.66

1460

7536

8.94

1501

7776

9.22

10,000

1378

7434

8.82

1419

7667

9.10

1460

7902

9.37

1499

8138

9.65

1538

8377

9.94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

551A240 (20 TONS) (cont)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

Cfm

 

2.2

 

 

2.4

 

 

2.6

 

 

2.8

 

 

3.0

 

 

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

6,000

1332

4750

5.65

1380

5015

5.95

1427

5272

6.25

1472

5531

6.56

1517

5793

6.87

6,500

1356

5122

6.08

1402

5375

6.38

1447

5630

6.68

1492

5886

6.98

1535

6144

7.29

7,000

1381

5519

6.55

1427

5770

6.84

1471

6022

7.14

1514

6276

7.45

7,500

1409

5951

7.06

1453

6199

7.35

1496

6449

7.65

1538

6701

7.95

8,000

1440

6417

7.61

1482

6663

7.90

1523

6911

8.20

8,500

1471

6916

8.20

1513

7161

8.49

9,000

1505

7449

8.84

1545

7693

9.13

9,500

1540

8016

9.51

10,000

LEGEND

Bhp — Brake Horsepower

FIOP — Factory-Installed Option

Watts — Input Watts to Motor

*Standard low-medium static drive range is 1002 to 1151 rpm. Alternate high-static drive range is 1193 to 1369. Other rpms require a field- supplied drive.

NOTES:

1.Maximum continuous bhp for the standard motor is 9.47 (for 208-v units) and 10.33 (for 230 and 460-v units). The maximum continu- ous watts is 7915 (for 208-v units) and 8640 (for 230 and 460-v units). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.

2.Static pressure losses (i.e., EconoMi$er) must be added to exter- nal static pressure before entering Fan Performance table.

3.Interpolation is permissible. Do not extrapolate.

4.Fan performance is based on wet coils, clean filters, and casing losses. See Table 13 for accessory/FIOP static pressure information.

5.Extensive motor and drive testing on these units ensures that the full bhp and watts range of the motor can be utilized with confi- dence. Using your fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

6.Use of a field-supplied motor may affect wiring size. Contact your Bryant representative for details.

23

Image 23
Contents II. RIG and Place Unit ContentsSafety Considerations Installation Provide Unit SupportRoof Curb Details 240 Unit Maximum Dimensions Shipping WeightFt-in 155 1801039 1054 559 180 1650 748 36.3 375 170 449 204 452 Unit STD Unit ECONOMI$ER Corner DIM a DIM B DIM C Weight551A Ft-in 155 1575 714 36.3 407 185 375 170 383 174 410Base Unit Dimensions, 551A240 155 180 240 Physical Data551A180 and 240 Shown 551A155 Shown III. Field Fabricate DuctworkIV. Make Unit Duct Connections Trap Condensate DrainNEC Field Control WiringUnit Voltage FLA LRA MCA MOCP† Electrical DataPER Electric Resistance Heater DataUnit Heater Maximum Minimum Heater AmpsManual Outdoor-Air Damper VII. Make OUTDOOR-AIR Inlet AdjustmentsOptional Non-Fused Disconnect Optional Convenience OutletUnit Stage Heat Anticipator SettingsVIII. Install OUTDOOR-AIR Hood Outdoor Air Enthalpy Sensor InstallationDischarge Air Thermistor DAT CO2 Control SetupMechanical Cooling Lockout Dry Bulb Changeover Set UpEconoMi$er Switchover Control Strategy Default Potentiometer SettingsMotormaster I Control Installation 551A155 and 180 Only Ventilation Air Minimum Position Set UpIX. Install ALL Accessories Wind Baffle Details Motormaster III Control Installation 551A240 OnlyLPS LlsvSTART-UP III. Refrigerant Service PortsInternal Wiring XI. Accessory ECONOMI$ER AdjustmentUnits With Perfect Humidity Dehumidification Package Freeze Protection ThermostatsFan Performance 551A155 With Standard Indoor Fan Motor Watts Bhp Rpm 3750 Cfm Rpm Watts BhpWatts Bhp 5700 551A180 15 Tons4800 5100500 551A240 20 TonsWatts Bhp Rpm Bhp Rpm Watts 000Drop Accessory/FIOP Static Pressure in. wgEvaporator Fan Motor Specifications Fan RPM at Motor Pulley SettingsII. Lubrication Service CleaningIV. Evaporator FAN Service and Replacement Belt Tension Adjustment Evaporator-Fan Pulley Alignment AdjustmentVII. ECONOMI$ER Adjustment VI. CONDENSER-FAN AdjustmentXI. Protective Devices VIII. Power FailureIX. Refrigerant Charge Filter DrierXIII. Control Circuit XIV. Replacement PartsXVI. Optional Hinged Access Doors XII. Relief DevicesTypical Wiring Schematic 551A180, 460v Shown Typical Component Arrangement 551A180 Shown Problem Cause Remedy TroubleshootingCooling Service Analysis Problem Potential Cause Remedy EconoMi$er TroubleshootingPage General TemperaturesElectrical