Bryant 551A operation manual Field Control Wiring, Unit Voltage, Nec

Page 8

Fig. 10 — Condensate Drain Piping Details

VI. STEP 6 — MAKE ELECTRICAL CONNECTIONS A. Field Power Supply

Unit is factory wired for voltage shown on nameplate.

When installing units, provide a disconnect, per NEC (National Electrical Code) requirements, of adequate size (Table 2). Electrical heater data is shown in Table 3.

All field wiring must comply with NEC and local require- ments.

Route power lines through control box access panel or unit basepan (Fig. 4 and 5) to connections as shown on unit wir- ing diagram and Fig. 11.

Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, volt- ages between phases must be balanced within 2% and the current must be balanced within 10%.

CAUTION: The correct power phasing is critical in the operation of the scroll compressors. An incorrect phasing will cause the compressor to rotate in the wrong direction. This may lead to premature compres- sor failure.

Use the following formula to determine the percentage of voltage imbalance.

Percentage of Voltage Imbalance

=100 x max voltage deviation from average voltage average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

455 + 464 + 455

Average Voltage =

3

= 1371 3

= 457

Determine maximum deviation from average voltage:

(AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v

(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent voltage imbalance:

Percentage of Voltage Imbalance = 100 x 7457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.

B. Field Control Wiring

Install a Bryant-approved accessory thermostat assembly according to the installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature.

Route thermostat cable or equivalent single leads of colored wire from subbase terminals through conduit in unit to low- voltage connections as shown on unit label wiring diagram and in Fig. 12.

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

Set heat anticipator settings as indicated in Table 4. Settings may be changed slightly to provide a greater degree of com- fort for a particular installation.

TB1 MAXIMUM WIRE SIZE

 

UNIT

 

 

 

 

VOLTAGE

 

 

 

 

 

551A

 

 

 

208/230

 

 

 

460

 

 

All

 

 

 

350 kcmil

 

 

 

2/0

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

EQUIP — Equipment

 

NEC —

National Electrical

 

 

GND — Ground

 

 

 

 

 

Code

 

 

 

 

kcmil — Thousand Circular

TB

Terminal Block

 

 

 

 

Mils

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 11 — Field Power Wiring Connections

 

 

 

 

 

 

THERMOSTAT ASSEMBLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REMOVABLE JUMPER

 

 

 

 

 

 

 

 

 

 

RH RC

Y1

Y2

W1

W2

G

C

L

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

Y1

Y2

W1

W2

G

C

 

X

 

 

RED

 

BLU

PNK

ORN

 

VIO

BLK

BRN

 

WHT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT LOW-VOLTAGE CONNECTIONS

Fig. 12 — Field Control Thermostat Wiring

8

Image 8
Contents Contents Safety ConsiderationsInstallation Provide Unit Support II. RIG and Place UnitRoof Curb Details Unit Maximum Dimensions Shipping Weight Ft-in 155180 240Unit STD Unit ECONOMI$ER Corner DIM a DIM B DIM C Weight 551AFt-in 155 1575 714 36.3 407 185 375 170 383 174 410 1039 1054 559 180 1650 748 36.3 375 170 449 204 452Base Unit Dimensions, 551A240 Physical Data 155 180 240III. Field Fabricate Ductwork IV. Make Unit Duct ConnectionsTrap Condensate Drain 551A180 and 240 Shown 551A155 ShownNEC Field Control WiringUnit Voltage Electrical Data FLA LRA MCA MOCP†Electric Resistance Heater Data UnitHeater Maximum Minimum Heater Amps PERVII. Make OUTDOOR-AIR Inlet Adjustments Optional Non-Fused DisconnectOptional Convenience Outlet Manual Outdoor-Air DamperHeat Anticipator Settings VIII. Install OUTDOOR-AIR HoodOutdoor Air Enthalpy Sensor Installation Unit StageCO2 Control Setup Discharge Air Thermistor DATDry Bulb Changeover Set Up EconoMi$er Switchover Control StrategyDefault Potentiometer Settings Mechanical Cooling LockoutMotormaster I Control Installation 551A155 and 180 Only Ventilation Air Minimum Position Set UpIX. Install ALL Accessories Motormaster III Control Installation 551A240 Only Wind Baffle DetailsLlsv LPSIII. Refrigerant Service Ports Internal WiringXI. Accessory ECONOMI$ER Adjustment START-UPFreeze Protection Thermostats Units With Perfect Humidity Dehumidification PackageFan Performance 551A155 With Standard Indoor Fan Motor Watts Bhp Rpm 3750 Cfm Rpm Watts BhpWatts Bhp 551A180 15 Tons 48005100 5700551A240 20 Tons Watts Bhp RpmBhp Rpm Watts 000 500Accessory/FIOP Static Pressure in. wg DropFan RPM at Motor Pulley Settings Evaporator Fan Motor SpecificationsII. Lubrication Service CleaningIV. Evaporator FAN Service and Replacement Evaporator-Fan Pulley Alignment Adjustment Belt Tension AdjustmentVI. CONDENSER-FAN Adjustment VII. ECONOMI$ER AdjustmentVIII. Power Failure IX. Refrigerant ChargeFilter Drier XI. Protective DevicesXIV. Replacement Parts XVI. Optional Hinged Access DoorsXII. Relief Devices XIII. Control CircuitTypical Wiring Schematic 551A180, 460v Shown Typical Component Arrangement 551A180 Shown Problem Cause Remedy TroubleshootingCooling Service Analysis EconoMi$er Troubleshooting Problem Potential Cause RemedyPage General TemperaturesElectrical
Related manuals
Manual 170 pages 34.1 Kb