Bryant 551A operation manual Discharge Air Thermistor DAT, CO2 Control Setup

Page 13

SENSOR

OUTSIDE AIR SENSOR

COVER

 

Fig. 19 — Seal Strip Location

(Air Hood Cross-Sectional View)

BAFFLE (180 AND 240 ONLY)

LOWER FILTER

RETAINER

FILTER SUPPORT

BRACKET

HOOD SIDE

PANELS (2)

HOOD TOP PANEL

BAFFLE

(180 AND

240 ONLY)

LOWER

FILTER

RETAINER

FILTER SUPPORT

BRACKET

HOOD DRAIN PAN

UPPER FILTER RETAINER

NOTE: The outdoor-air hood comes with a baffle which is used on 180 and 240 units only; discard baffle for 155 units.

Fig. 20 — Outdoor-Air Hood Details

C. Commissioning

The EconoMi$er saves energy when it uses outdoor air to provide free cooling instead of mechanical air conditioning. The EconoMi$er switchover strategy determines if the out- door air is suitable for free cooling. The EconoMi$er chooses the switchover strategy with the most energy savings, pro- vided that the required sensors are connected and function- ing normally.

IMPORTANT: If a sensor stops functioning normally (becomes unreliable), the EconoMi$er switches to the next best strategy.

Fig. 21 — Outdoor-Air Sensor Location

MOUNTING SCREW

SENSOR

WIRING

CONNECTIONS

MOUNTING

SCREW

WIRING

HARNESS

Fig. 22 — Outdoor-Air Sensor Details

Refer to Table 5 to determine the sensors required for each strategy.

Differential Enthalpy Switchover Strategy

The differential enthalpy switchover strategy must be selected manually, if required. To enable, press and hold the CONFIG button for 30 seconds, then release. The LED will flash twice to indicate the change of configuration.

To return to single enthalpy mode, press and hold the CON- FIG button for 30 seconds. The LED will flash once to indi- cate the change of configuration.

D. Discharge Air Thermistor (DAT)

The discharge air thermistor is factory-mounted on the supply-fan housing in the fan section of the unit. The DAT is factory-wired to the EconoMi$er Control Module.

E. CO2 Control Setup

If a CO2 sensor is not being used, proceed to the next section. If a CO2 sensor is being used, perform the following:

1.Determine the value at which you want the minimum position of the dampers to begin opening to allow a greater amount of outdoor air to enter. The range is 800 to 1,400 ppm.

2.Locate the CO2 SP (PPM) potentiometer and adjust to the desired set point. See Fig. 16.

13

Image 13
Contents Safety Considerations ContentsInstallation Provide Unit Support II. RIG and Place UnitRoof Curb Details Ft-in 155 Unit Maximum Dimensions Shipping Weight180 240551A Unit STD Unit ECONOMI$ER Corner DIM a DIM B DIM C WeightFt-in 155 1575 714 36.3 407 185 375 170 383 174 410 1039 1054 559 180 1650 748 36.3 375 170 449 204 452Base Unit Dimensions, 551A240 155 180 240 Physical DataIV. Make Unit Duct Connections III. Field Fabricate DuctworkTrap Condensate Drain 551A180 and 240 Shown 551A155 ShownUnit Voltage Field Control WiringNEC FLA LRA MCA MOCP† Electrical DataUnit Electric Resistance Heater DataHeater Maximum Minimum Heater Amps PEROptional Non-Fused Disconnect VII. Make OUTDOOR-AIR Inlet AdjustmentsOptional Convenience Outlet Manual Outdoor-Air DamperVIII. Install OUTDOOR-AIR Hood Heat Anticipator SettingsOutdoor Air Enthalpy Sensor Installation Unit StageDischarge Air Thermistor DAT CO2 Control SetupEconoMi$er Switchover Control Strategy Dry Bulb Changeover Set UpDefault Potentiometer Settings Mechanical Cooling LockoutIX. Install ALL Accessories Ventilation Air Minimum Position Set UpMotormaster I Control Installation 551A155 and 180 Only Wind Baffle Details Motormaster III Control Installation 551A240 OnlyLPS LlsvInternal Wiring III. Refrigerant Service PortsXI. Accessory ECONOMI$ER Adjustment START-UPUnits With Perfect Humidity Dehumidification Package Freeze Protection ThermostatsFan Performance 551A155 With Standard Indoor Fan Motor Watts Bhp Cfm Rpm Watts BhpWatts Bhp Rpm 3750 4800 551A180 15 Tons5100 5700Watts Bhp Rpm 551A240 20 TonsBhp Rpm Watts 000 500Drop Accessory/FIOP Static Pressure in. wgEvaporator Fan Motor Specifications Fan RPM at Motor Pulley SettingsIV. Evaporator FAN Service and Replacement Service CleaningII. Lubrication Belt Tension Adjustment Evaporator-Fan Pulley Alignment AdjustmentVII. ECONOMI$ER Adjustment VI. CONDENSER-FAN AdjustmentIX. Refrigerant Charge VIII. Power FailureFilter Drier XI. Protective DevicesXVI. Optional Hinged Access Doors XIV. Replacement PartsXII. Relief Devices XIII. Control CircuitTypical Wiring Schematic 551A180, 460v Shown Typical Component Arrangement 551A180 Shown Cooling Service Analysis TroubleshootingProblem Cause Remedy Problem Potential Cause Remedy EconoMi$er TroubleshootingPage Electrical TemperaturesGeneral
Related manuals
Manual 170 pages 34.1 Kb