Bryant 551A Mechanical Cooling Lockout, Dry Bulb Changeover Set Up, Changeover Set Points

Page 14

F. Mechanical Cooling Lockout

Determine the outdoor-air temperature at which you want the mechanical cooling (compressors) to be disabled. Locate the mechanical cooling lockout (MECH CLG LOCKOUT) potentiometer. To disable this feature, turn the potentiome- ter counterclockwise (CCW) to the OFF position. Otherwise, set the value between 10 and 60 F. Mechanical cooling will not operate when the outdoor air temperature is below this value. See Fig. 16.

G. Dry Bulb Changeover Set Up

Determine the dry bulb changeover set point from Table 6. The settings are A, B, C and D. Locate the ECON SP potenti- ometer and set the dry bulb changeover set point. See Fig. 16. When the OAT is above this set point, the damper is limited to minimum position setting.

If a potentiometer fails, its setting will default to the values in Table 7.

Table 5 — EconoMi$er Switchover Control Strategy

ECONOMI$ER SWITCHOVER STRATEGY

 

SENSORS REQUIRED

 

Outdoor Air Temperature

Outdoor Air Enthalpy

Return Air Temperature

Return Air Enthalpy

 

Dry Bulb

X

 

 

 

 

 

 

 

 

Single Enthalpy

 

X

 

 

 

 

 

 

 

Differential Temperature

X

 

X

 

 

 

 

 

 

Differential Enthalpy*

 

X

 

X

 

 

 

 

 

*Must be selected manually.

Table 6 — Changeover Set Points

SETTINGS

A

B

C

D

Dry Bulb (°F)

73

69

66

63

Single Enthalpy* (Btu/lb)

27

25

24

22

Differential Temperature*

2

2

2

2

(°F, Not Adjustable)

 

 

 

 

Differential Enthalpy*

1

1

1

1

(Btu/lb, Not Adjustable)

 

 

 

 

*Field-installed accessory.

 

 

 

 

Table 7 — Default Potentiometer Settings

POTENTIOMETER

DEFAULT SETTING

CO2 SP (PPM)

1,000

MECH CLG LOCKOUT

50 F

ECON SP

D

MIN POS (%)

20

LEGEND

COM — Common

DAT — Discharge Air Thermistor

DM — Damper Motor

GND — Ground

OAH — Outdoor-Air Enthalpy Sensor

OAT — Outdoor-Air Temperature Sensor

POT — Potentiometer

RAH — Return-Air Enthalpy Sensor

RAT — Return-Air Temperature Sensor

REM — Remote

*OAT sensor shipped with economizer option. OAH, RAT, RAH and CO2 are field-installed accessories.

Fig. 23 — Typical EconoMi$er Wiring

14

Image 14
Contents Installation Provide Unit Support ContentsSafety Considerations II. RIG and Place UnitRoof Curb Details 180 Unit Maximum Dimensions Shipping WeightFt-in 155 240Ft-in 155 1575 714 36.3 407 185 375 170 383 174 410 Unit STD Unit ECONOMI$ER Corner DIM a DIM B DIM C Weight551A 1039 1054 559 180 1650 748 36.3 375 170 449 204 452Base Unit Dimensions, 551A240 Physical Data 155 180 240Trap Condensate Drain III. Field Fabricate DuctworkIV. Make Unit Duct Connections 551A180 and 240 Shown 551A155 ShownNEC Field Control WiringUnit Voltage Electrical Data FLA LRA MCA MOCP†Heater Maximum Minimum Heater Amps Electric Resistance Heater DataUnit PEROptional Convenience Outlet VII. Make OUTDOOR-AIR Inlet AdjustmentsOptional Non-Fused Disconnect Manual Outdoor-Air DamperOutdoor Air Enthalpy Sensor Installation Heat Anticipator SettingsVIII. Install OUTDOOR-AIR Hood Unit StageCO2 Control Setup Discharge Air Thermistor DATDefault Potentiometer Settings Dry Bulb Changeover Set UpEconoMi$er Switchover Control Strategy Mechanical Cooling LockoutMotormaster I Control Installation 551A155 and 180 Only Ventilation Air Minimum Position Set UpIX. Install ALL Accessories Motormaster III Control Installation 551A240 Only Wind Baffle DetailsLlsv LPSXI. Accessory ECONOMI$ER Adjustment III. Refrigerant Service PortsInternal Wiring START-UPFreeze Protection Thermostats Units With Perfect Humidity Dehumidification PackageFan Performance 551A155 With Standard Indoor Fan Motor Watts Bhp Rpm 3750 Cfm Rpm Watts BhpWatts Bhp 5100 551A180 15 Tons4800 5700Bhp Rpm Watts 000 551A240 20 TonsWatts Bhp Rpm 500Accessory/FIOP Static Pressure in. wg DropFan RPM at Motor Pulley Settings Evaporator Fan Motor SpecificationsII. Lubrication Service CleaningIV. Evaporator FAN Service and Replacement Evaporator-Fan Pulley Alignment Adjustment Belt Tension AdjustmentVI. CONDENSER-FAN Adjustment VII. ECONOMI$ER AdjustmentFilter Drier VIII. Power FailureIX. Refrigerant Charge XI. Protective DevicesXII. Relief Devices XIV. Replacement PartsXVI. Optional Hinged Access Doors XIII. Control CircuitTypical Wiring Schematic 551A180, 460v Shown Typical Component Arrangement 551A180 Shown Problem Cause Remedy TroubleshootingCooling Service Analysis EconoMi$er Troubleshooting Problem Potential Cause RemedyPage General TemperaturesElectrical
Related manuals
Manual 170 pages 34.1 Kb