Desa (V)KC42PE Continued, Ground Floor Installation, Square Termination, Vertical

Page 12
GROUND FLOOR INSTALLATION

Venting Installation

instructions

Continued

 

Minimum Pipe

Siding Standoff

Overlap 11/4"

 

Direct-Vent

 

Pipe

Screws

 

 

Wall

 

 

 

 

 

 

Firestop

 

 

 

Maintain 1"

 

 

 

 

Minimum Air

 

 

 

 

Space Around

 

 

High Wind

Outer Pipe When

Termination

Penetrating a Wall

Apply

 

 

 

 

 

 

 

 

 

 

 

 

Mastic to

10

3

4

3

4

"

Outside

 

/ " x 10

 

/

Edge of

Framed Opening

Standoff

 

 

 

 

 

 

 

 

Exterior Wall with Vinyl Siding

Figure 13 - Typical Horizontal Termination Cap Mounting with Additional Siding Standoff Installed

Horizontal Termination Configurations Figures 14 through 18 show different configura- tions and alternatives for venting with horizontal termination. Each figure includes a chart with critical minimum and maximum dimensions which MUST be met. IMPORTANT: If using a venting configuration of only horizontal venting with no vertical run, a 1/4" rise for every 12" of run toward the termination is required.

NOTICE: Do not seal termination cap to vent pipe. Cap must be removable for vent inspection and maintenance.

Square Termination WARNING: Never run vent downward as this may cause excessive temperatures which could cause a fire. Operation of improperly installed and main- tained venting system could result in serious injury, property damage or loss of life.

GROUND FLOOR INSTALLATION

Recommended Applications:

Installation using cabinet surrounds

Through the wall using round or square termina- tion (up to 12" horizontal pipe)

NOT FOR CORNER INSTALLATION

Adjustable

Horizontal Pipe 12" Max. 45° Elbow

High Wind

Square

Termination

Wall Firestop

 

 

 

Square Termination

Vertical (V)

Horizontal (H)

32

3

/ " min.

17" max.

 

 

4

 

 

 

 

45° Elbow

 

 

 

Exterior Portion of

 

 

 

 

 

Wall

 

 

 

Wall Firestop (Round

 

 

 

Termination Only)

Firestop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal

Round

Termination

Round Termination

*If installing this fireplace at altitudes of

4000 feet and above, it is recommended that an additional vertical height of 6" be added to the vent system.

Figure 14 - Horizontal Termination Configuration for Square or Round Terminations

12

www.desatech.com

116240-01E

Image 12
Contents WHAT TO DO IF YOU SMELL GAS Table of Contents Safety InformationDANGER Carbon monoxide poisoning may lead to deathSafety information ContinuedSafety information ProductIdentification Local CodesProduct Features Pre-Installation PreparationFigure 3 - Fireplace Bottom Dimensions Location and space requirementsContinued ClearancesPre-Installation InstallationPreparation ContinuedLocation of Termination Cap D E B LFigure 7 - Minimum Clearances for Termination Cap Venting Installation Instructions Venting Installation instructions INSTALLATION PLANNINGContinued Figure 8 - Vent Pipe ConnectionsFigure 10 - Installing Horizontal Vent Cap Figure 11 - Installing Siding StandoffFigure 12 - Connecting Vent Cap with ContinuedGROUND FLOOR INSTALLATION ContinuedSquare Termination VerticalCORNER INSTALLATION SNORKEL TERMINATION INSTALLATIONContinued 90 ElbowHORIZONTAL SYSTEM INSTALLATION USING TWO 90 ELBOWSContinued with Termination at 90 with Fireplaceinstallation for vertical termination Flat Ceiling InstallationFigure 20 - Installing Firestop ContinuedConfiguration Using Two 90 Elbows Configuration Using One 90 ElbowContinued Figure 21 - Vertical VentingConfiguration Using Two 90 Elbows Configuration With No Horizontal RunContinued Vertical Ventingparts list for venting kits and components ContinuedDESA 5/8 Pipe & Vent Kits Number Description Number DescriptionFireplace Installation Installing optional blower accessoriesCHECK GAS TYPE Model BKT Installation ContinuedFigure 28 - Blower Model BKT Installing Gas Piping to Fireplace Location Blower Wiring DiagramInstallation Items Needed Installation Items Needed ContinuedFigure 30 - External Regulator with Vent Pointing Down Propane/LP OnlyContinued CHECKING GAS CONNECTIONSPressure Testing Fireplace Gas Connections Removing Louver PanelsFigure 36 - Removing Louver Panel Removing Glass DoorInstalling lava rock and glowing embers Installing Lava Rock and Glowing Embers, page Figure 40 - Installing the WRC Remote ReceiverFigure 39 - Installing Rear Brick Panel Figure 41 - Installing Battery into Back ofIGNITOR LEAD PILOT24V AC 120V ACfor your safety Read before lighting Operating Fireplacelighting instructions TO TURN OFF GAS TO APPLIANCEsee Troubleshooting, page see Troubleshooting, pageContinued Figure 44 - Correct Pilot Flame PatternCleaning and Maintenance CAUTION Do not vacuum if pieces are hotCleaning and Maintenance TroubleshootingOBSERVED PROBLEM venting systemTROUBLESHOOTING Wiring Diagram, pageContinued WARNING If you smell gas Shut off gas supply Replacement Parts Service HintsTechnical Service SpecificationsAccessories 24 22 23 4 1 9 11 3 14 16 7 8116240-01E PARTS LIST illustrated parts breakdown Burner Pan Assembly Warranty Information KEEP THIS WARRANTYLIMITED WARRANTY DIRECT-VENTFIREPLACE