Desa HDCFTP, HDCFTN, CGCFTP, CGCFTN installation manual Natura L, Accessories

Page 15

INSTALLation

Continued

CAUTION:Neverconnectpro- pane/LP fireplace directly to the propane/LPsupply.Thisfireplace requires an external regulator (notsupplied).Installtheexternal regulator between the fireplace and propane/LP supply.

WARNING: Never connect natural gas fireplace to private (non-utility) gas wells. This gas is commonly known as wellhead gas.

For propane/LP units, installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11" and 14" of water. If you do not reduce incoming gas pressure, fireplace regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 18. Pointing the vent down protects it from freezing rain or sleet.

CAUTION: Use only new, black iron or steel pipe. Inter- nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" or greater diameter to allow proper gas volume to fireplace. If pipe is too small, undue loss of volume will occur.

Installation must include an equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 19).

IMPORTANT: Install an equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on and shutting off the gas to the appliance.

Check your building codes for any special re- quirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves.

WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

We recommend that you install a sediment trap in supply line as shown in Figure 19. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and fireplace. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into fire- place controls. If sediment trap is not installed or is installed wrong, fireplace may not run properly.

Propane/LP

Supply Tank

External

Regulator

Vent Pointing Down

Figure 18 - External Regulator with Vent

Pointing Down

CSA Design-Certified

Equipment Shutoff Valve With 1/8" NPT Tap*

 

 

 

PROPANE/LP

 

 

 

From External

 

 

 

Regulator (11"

 

 

 

W.C. to 14" W.C.

3" Minimum

 

Pressure)

 

 

 

 

 

NATURAL

Pipe

Cap

Tee

From Gas Meter

Nipple

 

Joint

(5" W.C. to 10.5"

 

 

 

W.C. Pressure)

Sediment Trap

 

Figure 19 - Gas Connection

*Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See

Accessories, page 27.

111044-01J

www.desatech.com

15

Image 15
Contents Shown with Optional Cabinet Mantel/Hearth Base Accessory HDCFTP, HDCFTN, Cgcftp and Cgcftn14,000 to 26,000 Btu/Hr with Thermostat Safety Information Table of ContentsPoisoning may lead to death Safety InformationLocal Codes Product InformationProvide adequate clearances around air openings Product Features AssemblyUnpacking Assembling Hood AssemblyAir For Combustion Ventilation Providing Adequate VentilationDetermining FRESH-AIR Flow for fireplace Location Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space Ventilation Air From Outdoors InstallationVentilation AIR Ventilation Air From Inside BuildingInstallation Items Check GAS TypeLocating Fireplace Fireplace pilot and burner must be at least 18 above floor Built-In Fireplace InstallationIf you have not assembled firebox, follow instructions on Check all gas connections for leaks. SeeChecking Gas Connections, Removing Upper Louver Assembly Mantel Clearances for Built- In InstallationOptional Mantel Installation Installing blower accessory GA3450TAModels Cgcftp and Cgcftn Installing Blower AssemblyExtension Cord Connecting to GAS SupplyFor Built-In Installation Reinstall valve cover shieldNatura L Accessories,Checking Gas Connections Connecting Equipment shutoff valve to heater controlInstallation Items Needed Checking GAS ConnectionsPressure Testing Fireplace Gas Connections Correct all leaks at onceTest Pressures Equal To or Less Than Psig 3.5 kPa For Your Safety Read Before Lighting Operating FireplaceLighting Instructions Thermostat Control Operation Manual Lighting ProcedureOperating Fireplace To Turn OFF GAS To ApplianceBurner Flame Pattern Cleaning MaintenanceInspecting Burner Pilot Flame PatternCabinet Air PassagewaysExterior Observed Problem Possible Cause Remedy TroubleshootingMaintenance TroubleshootingMaintenance, See Cleaning and MainteSee Checking Gas Connec Gas leak. See WarningReplacement Parts SpecificationsService Hints Technical ServiceTHERMOSTATICALLY-CONTROLLED Blower KIT GA3450TA AccessoriesEquipment Shutoff Valve GA5010 Brass Trim KIT GA609514 29 Parts List Parts Centrals 111044-01J VENT-FREE Compact fireplace Warranty InformationKeep this Warranty Limited Warranty