Desa CGCFTP, CGCFTN Assembly, Air For Combustion Ventilation, Providing Adequate Ventilation

Page 6

ASSEMBLY

Continued

Assembling Hood

1. Locate four black phillips sheet metal screws from the hardware packet.

2. Rotate hood as shown in Figure 3. Make sure hood tabs point toward fireplace.

3. Insert hood tabs between baffle and louvers (see Figure 3).

4. Gently rotate hood to upright position. Make sure hood tabs are behind louvers and hood is resting on firebox top (see Figure 3).

5. Align screw holes on hood with screw holes on firebox top.

6. Insert screws as shown in Figure 3. Tighten screws firmly.

Louver

Hood Tab

Baffle

Hood

Firebox

Top

Sheet

Metal Hood

Screws Tabs

Figure 3 - Assembling Hood

Air For Combustion

and Ventilation

WARNING: This heater shall not be installed in a confined space or unusually tight con- struction unless provisions are provided for adequate combus- tion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.

Today’s homes are built more energy efficient than ever. New materials, increased insulation and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.

While it is good to make your home energy effi- cient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.

Exhaust fans, fireplaces, clothes dryers and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.

PROVIDING ADEQUATE

VENTILATION

The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three fol- lowing ventilation classifications:

1.Unusually Tight Construction

2.Unconfined Space

3.Confined Space

The information on pages 6 through 8 will help you classify your space and provide adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

www.desatech.com111044-01J

Image 6
Contents Shown with Optional Cabinet Mantel/Hearth Base Accessory HDCFTP, HDCFTN, Cgcftp and Cgcftn14,000 to 26,000 Btu/Hr with Thermostat Table of Contents Safety InformationSafety Information Poisoning may lead to deathLocal Codes Product InformationProvide adequate clearances around air openings Product Features AssemblyUnpacking Providing Adequate Ventilation AssemblyAir For Combustion Ventilation Assembling HoodDetermining FRESH-AIR Flow for fireplace Location Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building InstallationVentilation AIR Ventilation Air From OutdoorsInstallation Items Check GAS TypeLocating Fireplace Built-In Fireplace Installation Fireplace pilot and burner must be at least 18 above floorIf you have not assembled firebox, follow instructions on Check all gas connections for leaks. SeeChecking Gas Connections, Installing blower accessory GA3450TA Mantel Clearances for Built- In InstallationOptional Mantel Installation Removing Upper Louver AssemblyInstalling Blower Assembly Models Cgcftp and CgcftnReinstall valve cover shield Connecting to GAS SupplyFor Built-In Installation Extension CordAccessories, Natura LChecking GAS Connections Connecting Equipment shutoff valve to heater controlInstallation Items Needed Checking Gas ConnectionsPressure Testing Fireplace Gas Connections Correct all leaks at onceTest Pressures Equal To or Less Than Psig 3.5 kPa For Your Safety Read Before Lighting Operating FireplaceLighting Instructions To Turn OFF GAS To Appliance Manual Lighting ProcedureOperating Fireplace Thermostat Control OperationPilot Flame Pattern Cleaning MaintenanceInspecting Burner Burner Flame PatternCabinet Air PassagewaysExterior Troubleshooting Observed Problem Possible Cause RemedyTroubleshooting MaintenanceSee Cleaning and Mainte Maintenance,Gas leak. See Warning See Checking Gas ConnecTechnical Service SpecificationsService Hints Replacement PartsBrass Trim KIT GA6095 AccessoriesEquipment Shutoff Valve GA5010 THERMOSTATICALLY-CONTROLLED Blower KIT GA3450TA14 29 Parts List Parts Centrals 111044-01J Limited Warranty Warranty InformationKeep this Warranty VENT-FREE Compact fireplace