Desa CGCFTP, CGCFTN Connecting to GAS Supply, For Built-In Installation, Extension Cord

Page 14

INSTALLation

Continued

For Built-In Installation

WARNING: A licensed elec- trician must connect the wiring harness to electrical supply following all local codes. Electri- cian must provide a clamp on the box cover to secure the wiring. Wiring should be routed through the bushing in the hole on the outer casing of heater.

Follow instructions in Removing Valve Cover Shield, page 12, then

1.Install a snap bushing found in hardware kit into one of the holes found on rear of valve cover shield. The other hole is for a strain relief clamp (not supplied) to secure incoming electrical supply.

2.Follow steps 2 through 6 in Installing Blower Assembly, page 12. Also remove black wire from middle switch terminal 2.

3.Remove black plastic strain relief and power cord from switch plate. The power cord supplied will not be used in built-in installations. Pop in the plastic snap bushing found in hardware kit into the hole left by supply cord/strain relief.

4.A licensed electrician must follow the wiring diagram to connect incoming electrical supply to fan kit wiring harness (see Figure 16).

5.Plug power cord to the outlet receptacle (not provided) as shown in Figure 17. Wind the extra cable in power cord and tie it up with the plastic wire strap (see Figure 17). Set the cable bundle between the burner bracket and outer casing, away from the burner.

6.Reinstall valve cover shield.

 

Fan Switch

 

 

 

 

 

 

 

 

(Auto/Off/On)

 

 

 

 

 

 

 

 

 

1 Auto

 

 

 

 

 

 

 

 

Off

2

 

 

 

 

 

 

 

 

 

 

 

3

Blue

 

Thermostat

 

 

 

On

 

 

 

Switch

 

 

 

 

 

 

(N.O.)

110/115

 

 

Red

 

 

 

 

Blue

V.A.C.

 

 

 

 

 

Blower

 

Black

 

 

 

 

 

 

 

 

Motor

 

 

 

 

 

 

 

Red

 

 

White

 

 

 

 

 

 

White

 

 

Green

 

 

 

 

 

 

Green

Figure 16 - Wiring Diagram For Blower

Accessory Built-In Installation

7.Test to make sure the blower is working properly.

8.Reinstall upper louver assembly and hood if previously removed, (see Figure 13, page 12). Close lower louver door.

Blower Bracket

Wire

Assembly

Harness

Screw

 

 

Switch

Power

 

Switch

 

Cord

 

Plate

Outlet

 

Receptacle

Blue

 

 

Red

 

 

Plastic Wire

 

 

Strap

 

 

Valve Cover

Box

Wire

Cover

Clamp Harness

Shield

 

Connector

 

 

(not included)

Figure 17 - Installing Blower Bracket

Assembly

Extension Cord

Use extension cord if needed. The cord must have a three-prong, grounding plug and a three-hole receptacle. Make sure cord is in good shape. It must be heavy enough to carry the current needed. An un- dersized cord will cause a drop in line voltage. This will result in loss of power and overheating. Use a No. 16 AWG cord for lengths less than 50 feet.

Connecting TO GAS SUPPLY

WARNING: This appliance requires a 45° male flare fitting 5/8"-18 UNF (Unified National FineThread)inletconnectionand the flexible gas line provided.

WARNING:Aqualifiedservice person must connect fireplace to gas supply. Follow all local codes.

14

www.desatech.com

111044-01J

Image 14
Contents 14,000 to 26,000 Btu/Hr with Thermostat Shown with Optional Cabinet Mantel/Hearth Base AccessoryHDCFTP, HDCFTN, Cgcftp and Cgcftn Table of Contents Safety InformationSafety Information Poisoning may lead to deathProvide adequate clearances around air openings Local CodesProduct Information Unpacking Product FeaturesAssembly Providing Adequate Ventilation AssemblyAir For Combustion Ventilation Assembling HoodDetermining if You Have a Confined or Unconfined Space Determining FRESH-AIR Flow for fireplace LocationConfined and Unconfined Space Ventilation Air From Inside Building InstallationVentilation AIR Ventilation Air From OutdoorsLocating Fireplace Installation ItemsCheck GAS Type Built-In Fireplace Installation Fireplace pilot and burner must be at least 18 above floorChecking Gas Connections, If you have not assembled firebox, follow instructions onCheck all gas connections for leaks. See Installing blower accessory GA3450TA Mantel Clearances for Built- In InstallationOptional Mantel Installation Removing Upper Louver AssemblyInstalling Blower Assembly Models Cgcftp and CgcftnReinstall valve cover shield Connecting to GAS SupplyFor Built-In Installation Extension CordAccessories, Natura LChecking GAS Connections Connecting Equipment shutoff valve to heater controlInstallation Items Needed Checking Gas ConnectionsTest Pressures Equal To or Less Than Psig 3.5 kPa Pressure Testing Fireplace Gas ConnectionsCorrect all leaks at once Lighting Instructions For Your Safety Read Before LightingOperating Fireplace To Turn OFF GAS To Appliance Manual Lighting ProcedureOperating Fireplace Thermostat Control OperationPilot Flame Pattern Cleaning MaintenanceInspecting Burner Burner Flame PatternExterior CabinetAir Passageways Troubleshooting Observed Problem Possible Cause RemedyTroubleshooting MaintenanceSee Cleaning and Mainte Maintenance,Gas leak. See Warning See Checking Gas ConnecTechnical Service SpecificationsService Hints Replacement PartsBrass Trim KIT GA6095 AccessoriesEquipment Shutoff Valve GA5010 THERMOSTATICALLY-CONTROLLED Blower KIT GA3450TA14 29 Parts List Parts Centrals 111044-01J Limited Warranty Warranty InformationKeep this Warranty VENT-FREE Compact fireplace