Desa CGCFTP, CGCFTN Installation, Ventilation AIR, Ventilation Air From Inside Building

Page 8

Air For Combustion

and Ventilation

Continued

If the actual Btu/Hr used is less than the maxi- mum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 4). You can also remove door into adjoining room (see option 3, Figure 4). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat- controlled power vent. Heated air entering the attic will activate the power vent.

 

Outlet

Ventilated

 

Attic

 

Air

 

 

Outlet

 

 

Air

 

To Attic

 

 

 

 

To

 

 

Crawl

Inlet

 

Space

 

 

Air

 

 

 

Inlet Air

Ventilated

 

Crawl Space

 

 

Figure 5 - Ventilation Air from Outdoors

Shown with Optional Mantel

Installation

NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri- mary heat source. If you have a central heating system, you may

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.

12"

Figure 4 - Ventilation Air from Inside Building Shown with Optional Mantel

WARNING: A qualified ser- vice person must install fire- place. Follow all local codes.

www.desatech.com111044-01J

Image 8
Contents 14,000 to 26,000 Btu/Hr with Thermostat Shown with Optional Cabinet Mantel/Hearth Base AccessoryHDCFTP, HDCFTN, Cgcftp and Cgcftn Table of Contents Safety InformationSafety Information Poisoning may lead to deathProvide adequate clearances around air openings Local CodesProduct Information Unpacking Product FeaturesAssembly Assembly Air For Combustion VentilationProviding Adequate Ventilation Assembling HoodDetermining if You Have a Confined or Unconfined Space Determining FRESH-AIR Flow for fireplace LocationConfined and Unconfined Space Installation Ventilation AIRVentilation Air From Inside Building Ventilation Air From OutdoorsLocating Fireplace Installation ItemsCheck GAS Type Built-In Fireplace Installation Fireplace pilot and burner must be at least 18 above floorChecking Gas Connections, If you have not assembled firebox, follow instructions onCheck all gas connections for leaks. See Mantel Clearances for Built- In Installation Optional Mantel InstallationInstalling blower accessory GA3450TA Removing Upper Louver AssemblyInstalling Blower Assembly Models Cgcftp and CgcftnConnecting to GAS Supply For Built-In InstallationReinstall valve cover shield Extension CordAccessories, Natura LConnecting Equipment shutoff valve to heater control Installation Items NeededChecking GAS Connections Checking Gas ConnectionsTest Pressures Equal To or Less Than Psig 3.5 kPa Pressure Testing Fireplace Gas ConnectionsCorrect all leaks at once Lighting Instructions For Your Safety Read Before LightingOperating Fireplace Manual Lighting Procedure Operating FireplaceTo Turn OFF GAS To Appliance Thermostat Control OperationCleaning Maintenance Inspecting BurnerPilot Flame Pattern Burner Flame PatternExterior CabinetAir Passageways Troubleshooting Observed Problem Possible Cause RemedyTroubleshooting MaintenanceSee Cleaning and Mainte Maintenance,Gas leak. See Warning See Checking Gas ConnecSpecifications Service HintsTechnical Service Replacement PartsAccessories Equipment Shutoff Valve GA5010Brass Trim KIT GA6095 THERMOSTATICALLY-CONTROLLED Blower KIT GA3450TA14 29 Parts List Parts Centrals 111044-01J Warranty Information Keep this WarrantyLimited Warranty VENT-FREE Compact fireplace