Desa VSGF33NRA, EFS33NRA installation manual Ventilation AIR, Ventilation Air From Inside Building

Page 7

AIR FOR COMBUSTION

AND VENTILATION

Continued

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2,560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maxi- mum Btu/Hr the space can support)

Example: 2,560 cu. ft. (volume of space) x 20 = 63,360 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

__________ Btu/Hr

Gas water heater*

__________ Btu/Hr

Gas furnace

__________ Btu/Hr

Vented gas heater

__________ Btu/Hr

Gas fireplace logs

__________ Btu/Hr

Other gas appliances*

+__________ Btu/Hr

Total

=__________ Btu/Hr

*Do not include direct-vent gas appliances. Di- rect-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

40,000

Gas water heater

__________ Btu/Hr

Vent-free fireplace

33,000

+__________ Btu/Hr

Total

73,000

=__________ Btu/Hr

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an uncon- fined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________Btu/Hr (maximum the space can support)

_________ Btu/Hr (actual amount of Btu/Hr used)

Example: 63,360 Btu/Hr (maximum the space can support)

73,000 Btu/Hr (actual amount of Btu/Hr used)

Ventilation

 

Grills

 

Into

Or

Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

 

Room,

 

Option

 

3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

The space in the example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide ad- ditional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

12"

Figure 3 - Ventilation Air from Inside

Building

107172-01K

www.desatech.com

7

Image 7
Contents What to do if YOU Smell GAS Table of Contents Safety Information Product Identification Log Base AssemblyLocal Codes Product FeaturesUnpacking Providing Adequate Ventilation AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Inside Building Ventilation AIRCheck GAS Type InstallationVentilation Air From Outdoors Electrical Hookup Installing HoodAssembling and Attaching Optional Brass Trim Conventional Fireplace Installation Installation ClearancesInstalling Cabinet Mantel BUILT-IN Fireplace InstallationRaise the mantel to an accept- able height Remove the mantel Installation Items Needed Installing GAS Piping to Fireplace LocationPropane/LP Connecting Fireplace to GAS SupplyNatural Gas Checking GAS ConnectionsTest Pressures In Excess Of 1/2 Psig 3.5 kPa Pressurize supply piping system by either Test Pressures Equal To or Less Than 1/2 Psig 3.5 kPaInstalling Front Log Front Log Notch Grate Prongs Metal Grate Bars Operating Fireplace For Your Safety Read Before LightingLighting Instructions Shutting Off Heater Manual Lighting ProcedureTo Turn GAS OFF To Appliance Optional HAND-HELD Remote OperationON/OFF Series Models Ghrcb and Cghrcb Auto Thermostatic ModeManual Mode Auto Shutoff FeaturePilot Flame Pattern Key Pad Lock FeatureInspecting Burners Optional Blower OperationFront Burner Flame Pattern Cleaning MaintenanceBurner Injector Holder and Pilot AIR Inlet Hole Specifications Wiring DiagramObserved Problem Possible Cause Remedy TroubleshootingSee Cleaning and Mainte Maintenance, Stalling Logs, Gas leak. See WarningParts Under Warranty Replacement PartsService Hints Technical ServiceIllustrated Parts Breakdown Parts List Illustrated Parts Breakdown KEY Part Number Description QTY Accessories Corner Hearth Base Perimeter Trim AccessoryReceiver and Remote Control KIT Ghrcb Cghrcb WALL-MOUNT ON/OFF SwitchKeep this Warranty Warranty InformationLimited Warranty VENT-FREE GAS Fireplace