INSTALLATION
Continued
NOTICE: Most building codes do not permit concealed gas connections. A flexible gas line is provided to allow accessibility fromthefireplace(seeFigure20). The flexible gas supply line con- nection to the equipment shutoff valve should be accessible.
4.Attach the flexible gas line to gas supply (see Figure 20). Check tightness of flexible gas line attached to gas regulator of fireplace (see Figure 20).
5.Check all gas connections for leaks. See Checking Gas Connections.
6.Replace log base assembly back into fireplace. Feed flexible gas line into fireplace base area while replacing log base assembly. Make sure the entire flexible gas line is in fireplace base area. Reattach log base assembly to fireplace with screws removed in step 2, page 14.
To Fireplace
Gas Regulator Equipment Shutoff Valve
Provided by Installer
Flexible Gas Line from
Fireplace Gas Regulator
Propane/LP
To External Regulator
Natural Gas
To Gas Meter
Figure 20 - Attaching Flexible Gas Lines
Together
CHECKING GAS CONNECTIONS
WARNING:Testallgaspiping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detec- tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.
CAUTION: Make sure exter- nal regulator has been installed between propane/LPsupply and fireplace. See guidelines under Connecting Fireplace to Gas Supply, page 14.
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1.Disconnect fireplace with its main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage fireplace regulator.
2.Cap off open end of gas pipe where equipment shutoff valve was connected.
3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.
4.Check all joints of gas supply piping system. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.
5.Correct all leaks at once.
6.Reconnect fireplace and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.