Desa K36EN Venting Installation Instructions, Continued, Installation For Vertical Termination

Page 13
INSTALLATION FOR VERTICAL TERMINATION

VENTING INSTALLATION INSTRUCTIONS

Continued

INSTALLATION FOR VERTICAL TERMINATION

Note: Vertical restrictor must be installed in all vertical installations.

1.Determine the route your vertical venting will take. If ceiling joists, roof rafters, or other framing will obstruct the venting system, consider an offset (see Figure 19) to avoid cutting load bearing members. Note: Pay special attention to these instal- lation instructions for required clearances (air space) to com- bustibles when passing through ceilings, walls, roofs, enclo- sures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum vertical rise of the venting system and any maximum horizontal offset limitations.

2.Set the fireplace in desired location. Drop a plumb line down from the ceiling to the position of the fireplace exit flue. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole at this point.

Drop a plumb line from the inside of the roof to the locating hole in the ceiling. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.

Roof Flashing

Wall Strap Flat Ceiling Installation

Manual background 45° Elbow

Manual background Ceiling Firestop

Figure 19 - Offset with Wall Strap and 45° Elbows

Flat Ceiling Installation

1.Cut a 10 3/4" square hole in the ceiling using the locating hole as a center point. The opening should be framed to 10 3/4"x10 3/4" (273 mm x 273 mm) inside dimensions, as shown in Figure 9 on page 8 using framing lumber the same size as the ceiling joists. If the area above the ceiling is an insulated ceiling or a room, nail firestop from the top side. This prevents loose insula- tion from falling into the required clearance space. Otherwise, install firestop below the framed hole. The firestop should be installed with no less than three nails per side (see Figure 20).

VENTING INSTALLATION INSTRUCTIONS

13

Installation for Vertical Termination

2.Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop. Be sure all pipe and elbow connections are fully twist-locked (see Fig- ure 8, page 8).

3.Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting hole in roof.) The 10 3/4"x10 3/4" hole must be measured on the horizontal; actual length may be larger depending on the pitch of the roof. There must be a 1" clearance from the vent pipe to combustible materials. Frame the opening as shown in Figure 9, page 8.

4.Connect a section of pipe and extend up through the hole.

Note: If an offset is needed to avoid obstructions, you must support the vent pipe every 3 feet. Use wall straps for this purpose (see Figure 19). Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the flow of the flue gases and intake air.

5.Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and fram- ing with roofing nails. Be sure roofing material overlaps the top edge of the flashing as shown in Figure 19. There must be a 1" clearance from the vent pipe to combustible materials.

6.Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements described in Figure 7 on page 6. Note: You must increase vent height for steep roof pitches. Nearby trees, adjoining rooflines, steep pitched roofs, and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem.

7.Twist-lock the vent cap onto the last section of vent pipe.

Note: If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclosure with standard construction material. Make sure and meet the minimum allowable clearances to combustibles. Do not fill any of the required air spaces with insulation.

If area above is a room, install

If area above is not a room, install

firestop above framed hole.

firestop below framed hole.

Figure 20 - Installing Firestop

Manual backgroundFor moreManual backgroundManual backgroundManual backgroundvisit www.Manual backgroundManual backgroundManual background.comManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

111924-01A

Image 13
Contents NATURAL GAS MODELS VK36EN SERIES PROPANE/LP GAS OWNER’S OPERATION AND INSTALLATION MANUALMODELS VK36EP SERIES DIRECT-VENTFIREPLACESAFETY INFORMATION TABLE OF CONTENTSLOCAL CODES PRODUCT IDENTIFICATIONContinued SAFETY INFORMATIONPRE-INSTALLATION PREPARATION PRODUCT FEATURESLOCATION AND SPACE REQUIREMENTS Continued PRE-INSTALLATION PREPARATIONCLEARANCES FRAMING AND FINISHINGD E B L LOCATION OF TERMINATION CAPV G V A LOCATION OF TERMINATION CAPINSTALLATION PRECAUTIONS VENTING INSTALLATION INSTRUCTIONSINSTALLATION PLANNING VENTING INSTALLATION INSTRUCTIONSHorizontal Termination Installation ContinuedVENTING INSTALLATION INSTRUCTIONS VENTING INSTALLATION INSTRUCTIONSContinued ExteriorHorizontal Termination Configurations VENTING INSTALLATION INSTRUCTIONSVENTING INSTALLATION INSTRUCTIONS ContinuedContinued VENTING INSTALLATION INSTRUCTIONSRecommended Applications Continued VENTING INSTALLATION INSTRUCTIONSVenting with Two 90 Elbows Venting with Two 90 ElbowsINSTALLATION FOR VERTICAL TERMINATION VENTING INSTALLATION INSTRUCTIONSFlat Ceiling Installation ContinuedVertical Termination Configurations VENTING INSTALLATION INSTRUCTIONSContinued Venting with Two 90 ElbowsHIGH ALTITUDE INSTALLATION VENTING INSTALLATION INSTRUCTIONSContinued Vertical VentingVENTING INSTALLATION INSTRUCTIONS FIREPLACE INSTALLATIONPARTS LISTS FOR VENTING KITS AND COMPONENTS Model BK InstallationModel BKT Installation FIREPLACE INSTALLATIONContinued INSTALLING GAS PIPING TO FIREPLACE LOCATION FIREPLACE INSTALLATIONBlower Wiring Diagram ContinuedInstallation Items Needed FIREPLACE INSTALLATIONPressure Testing Gas Supply Piping System ContinuedPressure Testing Fireplace Gas Connections FIREPLACE INSTALLATIONContinued Removing Louver PanelsCleaning Glass Door FIREPLACE INSTALLATIONSee Cleaning and Maintenance on page ContinuedINSTALLING LOGS, LAVA ROCK AND GLOWING EMBERS FIREPLACE INSTALLATIONWALL SWITCH INSTALLATION ContinuedFIREPLACE INSTALLATION WIRING DIAGRAMOPTIONAL REMOTE CONTROL INSTALLATION Model WRC ContinuedFOR YOUR SAFETY READ BEFORE LIGHTING OPERATING FIREPLACELIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCEOPERATING OPTIONAL BLOWER ACCESSORY INSPECTING BURNERSPILOT ASSEMBLY OPERATING FIREPLACEGLASS DOOR CLEANING AND MAINTENANCEPILOT AND BURNERS LOGSOBSERVED PROBLEM TROUBLESHOOTINGPOSSIBLE CAUSE REMEDYOBSERVED PROBLEM TROUBLESHOOTINGContinued POSSIBLE CAUSESERVICE HINTS REPLACEMENT PARTSTECHNICAL SERVICE SPECIFICATIONSMODELS VK36EN, VK36ENH, VK36EP, VK36EPH ILLUSTRATED PARTS BREAKDOWNILLUSTRATED PARTS BREAKDOWN PARTS LIST PARTS LISTILLUSTRATED PARTS BREAKDOWN PARTS LIST PARTS LIST111957-01 ACCESSORIES OWNERS REGISTRATION FORM TAPE Postage RequiredTAPE Page LIMITED WARRANTY DIRECT-VENTFIREPLACE WARRANTY INFORMATIONNOT A UPC