Vermont Casting DVHVAC36 manual + B = 17 5.2m Max

Page 14

DVHVAC36

It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.

The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall.

Horizontal plane means no vertical rise exists on this portion of the vent assembly.

For some installations, it may be desirable to have some amount of the horizontal vent run immediately after the fireplace. A vertical rise must be used but can be located anywhere in the vent system, to meet the parameters identified in the venting graph.

The maximum horizontal vent run is 20' (6 m) when the vertical vent rise is 7¹⁄₂' (2.3 m). (Fig. 18)

 

Maximum

 

Vertical Dimen-

20 ft. (6.1m)

 

sion 7¹⁄₂' (2.3m)

 

48"

Minimum when

12"

(1.2m)

Horizontal Run is

(305mm)

 

20' (6m)

15 ft.

 

 

 

 

(4.6m)

 

7.5'

(2.3m)

7TDVRT90 Elbow

CFM141

Fig. 18 Maximum number of 90° elbows is three.

The maximum number of 90° elbows per side wall installation is three (3).

The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.

When one (1) 90° elbow is installed directly onto another off the back of the fireplace the maximum horizontal vent length is 36" (914 mm). (Fig. 19)

For each 45° elbow installed in the horizontal run (while maintaining a constant horizontal plane), the length of the horizontal run MUST be reduced by 18" (457 mm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.

If a 90° elbow is used in the horizontal vent run (level height maintained) the maximum horizontal vent length is reduced by 36" (914 mm) (Fig. 20) This does not apply if the 90° elbows are used to increase or redirect a vertical rise.

14

Example: According to the vent chart the maximum horizontal vent length is 20' (6 m) when the vertical height is 7.5' (2.3 m) from fireplace base height. If one (1) 90° elbow is required in the horizontal vent, it must be reduced to 17' (5.2 m).

The maximum number of elbow degrees in a sys- tem is 270°. (This does not include transition elbow from rear vent to vertical vent.) (Fig. 21)

Maximum 3' (914mm)

7TDVRT90 Elbow

CFM142

Fig. 19 Maximum horizontal vent run with 90° elbows directly off back of unit.

 

 

 

B

 

 

 

7'

 

 

 

(2.1m)

A

 

 

 

10'

 

 

 

(3m)

 

 

 

7' 6"

A + B = 17' (5.2m) Max.

(2.3m)

 

 

 

 

 

 

CFM147

Fig. 20 Maximum vent run with elbows.

Sample:

 

 

4

Elbow 1

=

90°

Elbow 2

=

45°

 

Elbow 3

=

45°

 

Elbow 4

=

90°

 

Total angular variation

=

270°

 

1 + 2 + 3 + 4 = 270o

 

3

2

1

CFM132

Fig. 21 Maximum number of elbows.

10001195

Image 14
Contents Rear Direct Vent Model DVHVAC36 Table of Contents Installation & Operating Instructions Please Review the Following CarefullyFireplace Dimensions DVHVAC36Clearance to Combustibles Unit AssemblyLocating Your Gas Fireplace Mantel Framing and FinishingSupply Air Duct Systems Return Air PlenumHearth Gas Line InstallationFinal Finishing Gas Inlet & Manifold PressuresTypical gas supply installation Electrical SpecificationsLocation of Vent Termination ElectricalGeneral Venting Canadian Installations1 US Installations2 General Venting Information Termination LocationGeneral Information Assembling Vent Pipes Canadian InstallationsUSA Installations Twist Lock PipesRear Wall Installations How to Use the Vent GraphCorner Installation Sidewall Venting GraphVertical Sidewall Applications Locate vent opening on wall+ B = 17 5.2m Max Vertical Sidewall Installations Zero clearance sleeve is only required for combustible wallsBelow Grade Installation Always install Horizontal vent Ing on a level PlaneVertical Through-the-Roof Installation Vertical Through-the-Roof ApplicationsTypical Ceil Twist Lock Venting Components Operating Instructions Flame Characteristics Setting Temperature RiseFlame Adjustment Lava RockInspecting the Venting/Heating Exchange System Ceramic Refractory InstallationInspecting the Venting System Mortar lines must be alignedWhat to do if YOU Smell GAS Lighting & Operating InstructionsTo Turn Off Gas To Heater Troubleshooting the Gas Control System SIT Nova 825 Millivolt ValveMaintenance Cleaning the Standing Pilot Control SystemDVHVAC36 DescriptionDVHVAC36 Do not remove existing window frame as- sembly Optional AccessoriesDecorative Bay Window Remove all plastic from brass trimsDVHVAC36 Page Limited Lifetime Warranty Product Covered by this WarrantyEfficiency Ratings AFUE%