Empire Comfort Systems VF24FP2-1, VF24FP3-1 GAS Supply, Recommended Gas Pipe Diameter

Page 8

GAS SUPPLY

Check all local codes for requirements, especially for the size and type of gas supply line required.

Recommended Gas Pipe Diameter

Pipe Length

Schedule 40 Pipe

Tubing, Type L

 

Inside Diameter

Outside Diameter

 

Nat.

L.P.

Nat.

L.P.

0-10 feet

1/2”

3/8”

1/2”

3/8”

0-3 meters

12.7mm

9.5mm

12.7mm

9.5mm

10-40 feet

1/2”

1/2”

5/8”

1/2”

4-12 meters

12.7mm

12.7mm

15.9mm

12.7mm

40-100 feet

1/2”

1/2”

3/4”

1/2”

13-30 meters

12.7mm

12.7mm

19mm

12.7mm

100-150 feet

3/4”

1/2”

7/8”

3/4”

31-46 meters

19mm

12.7mm

22.2mm

19mm

Note: Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized.

Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.

Amanual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged forpressure test. Neverpressure test with appliance connected; control valve will sustain damage!

Agas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing. It is required by the National Fuel Gas Code that a drip line be installed near the gas inlet. This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect.

The use of the following gas connectors is recommended:

ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing and Fittings

ANS Z21.45 Assembled Flexible Appliance Connectors of Other

Than All-Metal Construction

The above connectors may be used if acceptable by the authority having jurisdiction. The state of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.

Pressure Testing of the Gas Supply System

1.To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T. plugged tapping, accessible for test gauge connection, must be placed immediately upstream of the gas supply connection to the appliance.

2.The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that

Page 8

system at test pressures in excess of 1/2 psig (3.5 kPa).

3.The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

Figure 3

Attention! If one of the above procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will result in a hazardous condition.

Checking Manifold Pressure

VF24FP3-1Natural gas will have a manifold pressure of approximately 3.5" w.c. (.871kPa) for maximum input or 1.7" w.c. (.423kPa) for minimum input at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 5.0" w.c. (1.120kPa) for the purpose of input adjustment to a maximum of 10.5" w.c. (2.614kPa). VF24FP2-1Natural gas will have a manifold pressure of approximately 6.0" w.c. (1.49kPa) at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 7.0" w.c. (1.74kPa) for the purpose of input adjustment to a maximum of 10.5" w.c. (2.615kPa).

VF24FP3-1Propane gas will have a manifold pressure approximately 10.0"w.c. (2.49kPa) for maximum input or 6.3"w.c. (1.568kPa) for minimum input at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 11.0"w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0"w.c. (3.237kPa). VF24FP2-1Propane gas will have a manifold pressure approximately 10.0"w.c. (2.49kPa) at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 11.0"w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0"w.c. (3.237kPa).

20248-2-0806

Image 8
Contents Installation Instructions Table of Contents Important Safety Information Do not Tamper with Pilot Light SafetyCarbon Monoxide Poisoning MAY Lead to DeathSafety Information for Users of LP-GAS LP-GAS Warning OdorIntroduction Specifications Water Vapor a BY-PRODUCT of Unvented Room HeatersVentilation Air From Inside Building OutdoorsVentilation AIR Ventilation Air From OutdoorsGAS Supply Recommended Gas Pipe DiameterClearances Combustible MaterialInstalling Fireplace in Mantel Installation of Fireplace Into MantelInstallation of Trim BUILT-IN Fireplace Installation Built-In Fireplace InstallationRough Opening for Installing in Wall Rough Opening for Installing in CornerLOG Placement Placement of Glowing Embers Rock WoolReplacement Loose Material glowing embers Part Number Operation INSTRUCTIONS/FLAME AppearanceVF24FP3-1 Lighting Instructions What to do if YOU Smell GASVF24FP2-1 Lighting Instructions Lighting InstructionsVF24FP2-1 Pilot Pilot Flame CharacteristicsVF24FP3-1 Pilot Bedroom Installation VF24FP2-1 Only Main Burner and Thermostat OperationVF24FP2-1 VF24FP3-1 Main Burner OperationCheck 750 Millivolt System Operation Remote ReceiverGas odor even when control knob is in OFF position Heater produces a whistling noise when main burner is litAppliance produces unwanted odors Appliance shuts off during use. Pilot stays onIndex Part Description Number Parts ListHOW to Order Repair Parts Parts View Parts List for EHL-24-1, Brick Liner KIT Optional Brick Liner Installation InstructionsInstalling Optional Brick Liner EHL-24-1 Optional Blower Installation Instructions Installing Optional Blower VFS-BK20248-2-0806 Optional Blower Installation Instructions Oiling Blower Motor WiringVFS-BK Parts List Parts List and Parts View for Optional Trim Kits VPF24SS Stainless SteelService Notes