Enviro C-10794 owner manual Initial Installation, Qualified Installers only

Page 12

Initial Installation

QUALIFIED INSTALLERS ONLY

VENT TERMINATION RESTRICTIONS:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

O

D

E

 

 

 

 

 

H

 

 

B

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

L

B

Fixed

 

 

B

 

 

 

G

F

Closed

Openable

Fixed

 

 

G

 

 

Openable

Closed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

B

 

A

 

J

 

 

K

 

 

 

 

 

 

 

 

 

 

 

 

I

A

 

Termination Cap

 

Air Supply Inlet

 

 

 

 

G

Gas Meter

Restriction Zone

 

 

 

 

 

 

 

 

 

(Termination not allowed)

 

Figure 10. Vent Termination Restrictions, refer to Table 2.

Table 2: Vent termination clearances, refer to Figure 10.

Letter

Canadian Installation 1

US Installation2

Description

A

12 in (30 cm)

Clearance above grade, verandah, porch, deck, or balcony.

 

 

 

 

B

12 in (30 cm)

9 in (23 cm)

Clearance from window or door that may be opened.

 

 

 

 

C

12 in (30 cm)*

Clearance from permanently closed window (to prevent

 

 

 

condensation).

 

 

 

D

24 in (60 cm)*

Vertical clearance to ventilated soffit located above the

 

 

 

terminal, within a horizontal distance of 2 ft (60 cm) from

 

 

 

center line of terminal.

 

 

 

E

18 in (45 cm)*

Clearance to unventilated soffit.

 

 

 

F

12 in (30 cm)*

Clearance to outside corner.

 

 

 

G

12 in (30 cm)*

Clearance to inside corner.

 

 

 

 

H

3 ft (91 cm) within a height of

3 ft (91 cm) within a height of

Clearance to each side of center line extended above

 

15 ft (4.5 m) above the meter/

15 ft (4.5 m) above the meter/

meter/regulator assembly.

 

regulator assembly

regulator assembly*

 

 

 

 

 

I

3 ft (91 cm)

3 ft (91 cm)*

Radial clearance around service regulator vent outlet.

 

 

 

 

J

12 in (30 cm)

9 in (23 cm)

Clearance to non-mechanical air supply inlet to building, or

 

 

 

the combustion air inlet to any other appliance.

 

 

 

 

K

6 ft (1.83 m)

3 ft (91 cm) above if within 10

Clearance to mechanical air supply inlet.

 

 

ft (3 m) horizontally

 

 

 

 

 

L

7 ft (2.13 m)t

7 ft (2.13 m)*t

Clearance above paved sidewalk or paved driveway located

 

 

 

on public property.

 

 

 

 

M

12 in / 30 cm+

12 in / 30 cm*+

Clearance under verandah, porch, deck, or balcony.

N

12 in (30 cm)*

Clearance horizontally to any surface (such as an exterior

 

 

 

wall) for vertical terminations.

 

 

 

O

12 in (30 cm)

Clearance above roof line for vertical terminations.

 

 

 

 

1In accordance with the current CSA B149, Natural Gas and Propane Installation Code.

2 In accordance with the current ANSI Z223.1 NFPA 54, National Fuel Gas Code.

* These numbers are only estimates. Clearance in accordance with installation codes and the requirements of the gas supplier.

t A vent shall not terminate directly above a side walk or paved driveway that is located between two single family dwellings and it serves both dwellings. + Permitted only if verandah, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

NOTE: Venting terminals shall not be recessed into walls or siding.

12

Image 12
Contents For Your Safety WestportSafety Precautions GeneralTable of Contents Codes And Approvals TOP Vent DVRear Vent DV Specifications DimensionsFor Your Safetyread Before Operating Operating InstructionsGas valve Maintenance And Service Electronic Ignition Module LocationTo Replace Handles for Removing DoorTo be Installed by a Qualified Service Agency only StepConversion instructions Natural Gas Initial Installation Qualified Installers onlyVenting Terminals Cannot be Recessed Into a Wall or Siding Restrictor plate settings For sufficient vent height above the roof line. For two Pipes and fittings, are Installing Vent Cap with Vinyl Siding Stand Off Corner installation rear vented with Once Wall Framing for Hole for VerticalTwist-lock the vent cap Multi-Story Vent Pipe Installation Installation Instructions KIT ComponentsCut away of spacers on Flex Pipe Fire stop Assembly of Venting into a Class ‘A’ Chimney Turn the elbow to the rear vent position and re-fasten with Screws removed in see FigureCorner Installation Installation for Top Vented Horizontal TerminationInstallation Wiring DiagramCanadian Installations A. InstallationsGeneral Venting Information Venting of a Fireplace Fitted with the Drafthood AdaptorAutomatic Safety Shut Down Spill Switch ReplacementOptional Finishing GAS Line Connection To Test Valve PressuresWire Size Max. Length Wiring Diagram For Fan ControlSecondary Installation Optional Blower Fan InstallationComplete Log Placement Log Placement with Rock Wool Brick panel bracket, slots shown Trouble Shooting Problem Possible Cause SolutionParts List Cast Reference Number Part Description Part NumberCast Leg Each Painted Parts Diagram Cast Parts List Components Reference Part Description Part NumberParts List Components Parts Diagram Components Warranty To the DealerInstallation Data Sheet