Initial Installation
QUALIFIED INSTALLERS ONLY
down to the roof level, as shown in Figure 24. Tighten the clamp around the pipe section. Use a level to make sure the pipe is truly vertical. With roofing nails, secure the support straps to the roof. Seal the nails holes heads with
STEP 7. Slip the flashing over the pipe section protruding through the roof. Secure the base of the flashing to the roof with roofing nails. Use a
STEP 8. Continue to add pipe sections until the height of the vent cap meets the minimum code requirements. Refer to Figure 25 and Table 4. Note that for steep roof pitches, the vent height must be increased. In high wind conditions, nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors can result in poor draft, or down drafting. In these cases, increasing the vent height may solve the problem.
STEP 9. Slip the storm collar over the pipe, and push it down to the top of the roof flashing as shown in Figure 24. Use the
collar. |
|
|
|
|
| Roof Pitch | Minimum Height | ||
STEP 10. |
| |||
|
|
|
| |
|
| Feet | Meters | |
|
|
| ||
|
|
|
|
|
|
| Flat to 7/8 | 1 | 0.3 |
|
|
|
|
|
|
| Over 7/12 to 8/12 | 1.5 | 0.46 |
|
|
|
|
|
|
| Over 8/12 to 9/12 | 2 | 0.61 |
|
|
|
|
|
|
| Over 9/12 to 10/12 | 2.5 | 0.76 |
|
|
|
|
|
|
| Over 10/12 to 11/12 | 3.25 | 0.99 |
|
|
|
|
|
|
| Over 11/12 to 12/12 | 4 | 1.22 |
|
|
|
|
|
|
| Over 12/12 to 14/12 | 5 | 1.52 |
|
|
|
|
|
|
| Over 14/12 to 16/12 | 6 | 1.83 |
|
|
|
|
|
|
| Over 16/12 to 18/12 | 7 | 2.13 |
|
|
|
|
|
|
| Over 18/12 to 20/12 | 7.5 | 2.29 |
Figure 25: Height of Vertical Termination; | ||||
Reference Table 4. |
|
|
|
|
| Over 20/12 to 21/12 | 8 | 2.44 | |
|
| |||
|
|
|
|
|
NOTES: | Table 4: Minimum ‘H’ for Figure 25 |
|
(1)If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe every 3 feet (91 cm), to avoid excessive stress on the elbows, and possible separation. Wall straps are available for this purpose (see Figure 26).
(2)When ever possible, use 45° degree elbows instead of 90° degree elbows. The 45° degree elbow offers less restriction to the flow of flue gases and intake air.
NOTES:
(1)For multi story installations. A ceiling firestop is required at the second floor, and any subsequent floors (see Figure 27). The opening should be framed to 10” (25.4 cm) x 10” (25.4 cm) inside dimensions, in the same manner as shown in Figure 23.
20