Initial Installation
GENERAL VENTING INFORMATION:
Canadian Installations
The venting system must be installed in accordance with the current CSA B149 installation code and/or local codes having jurisdiction.
U.S.A. Installations
The venting system must be installed in accordance with the current National Fuel Gas Code, ANSI Z223.1, and/or local codes having jurisdiction.
The minimum clearance to combustibles is 6” (150 mm) when using single wall venting and 1” (25 mm) when using
We strongly recommend installing an approved chimney liner in an existing brick chimney. This will maximize the potential draft of the chimney and lessen the effects of slow chimney
VENTING OF A FIREPLACE FITTED WITH THE DRAFTHOOD ADAPTOR:
Note: Please refer to the chimney manufacturer’s installation instructions prior to commencing the installation.
This unit may be vented to an existing masonry chimney, or where no masonry chimney is available, an approved
| In either case, the fireplace may be connected to | |
| the chimney/vent using a 4” (10 cm) single wall vent | |
| connector. | |
| When an existing masonry chimney | |
�� ������ | is utilized for the venting, we | |
�������� | recommend the vent connector be | |
���������� | connected to an approved 4” (10 | |
����� | ||
�� ������ | cm) diameter flue liner running the | |
full height of the chimney. In many | ||
���� | ||
| jurisdictions this flue liner may be | |
| mandatory. |
If 4” (10 cm) single wall vent is |
| |
used, a minimum of 6” (15 cm) must |
| |
be maintained between the vent |
| |
connector and any combustibles. | Figure 41: Unit rear | |
Figure 40: Unit top venting styles. | venting style. | |
| ||
If 4” (10 cm) |
| |
maintained between the vent connector and any combustibles. | ����� ���� ����� | |
CAUTION: A minimum vent height of 12’ (3.6 m) from the floor is | ||
�������� | ||
| �� ��� ��� ��� �� | |
required to effectively vent this fireplace. |
| |
SPILLAGE TEST: |
| |
A spillage test must be performed prior to leaving the installed fireplace |
| |
with the customer. Perform this test in the following manner: |
| |
1. Close all windows and doors in the room. |
| |
2. Start all exhaust fans in the house and the furnace blower. |
| |
3. Light the fireplace and set to maximum flame adjustment. |
| |
Figure 42: Draft test place. |
29