Enviro C-10794 owner manual General Venting Information, Canadian Installations, A. Installations

Page 29

Initial Installation

GENERAL VENTING INFORMATION:

Canadian Installations

The venting system must be installed in accordance with the current CSA B149 installation code and/or local codes having jurisdiction.

U.S.A. Installations

The venting system must be installed in accordance with the current National Fuel Gas Code, ANSI Z223.1, and/or local codes having jurisdiction.

The minimum clearance to combustibles is 6” (150 mm) when using single wall venting and 1” (25 mm) when using “B-vent” venting.

We strongly recommend installing an approved chimney liner in an existing brick chimney. This will maximize the potential draft of the chimney and lessen the effects of slow chimney start-up.

VENTING OF A FIREPLACE FITTED WITH THE DRAFTHOOD ADAPTOR:

Note: Please refer to the chimney manufacturer’s installation instructions prior to commencing the installation.

This unit may be vented to an existing masonry chimney, or where no masonry chimney is available, an approved “B-vent” chimney, or any other approved constructed chimney/vent system (see Figure 40 & 41).

 

In either case, the fireplace may be connected to

 

the chimney/vent using a 4” (10 cm) single wall vent

 

connector.

 

When an existing masonry chimney

�� ������

is utilized for the venting, we

��������

recommend the vent connector be

����������

connected to an approved 4” (10

�����

�� ������

cm) diameter flue liner running the

full height of the chimney. In many

����

 

jurisdictions this flue liner may be

 

mandatory.

If 4” (10 cm) single wall vent is

 

used, a minimum of 6” (15 cm) must

 

be maintained between the vent

 

connector and any combustibles.

Figure 41: Unit rear

Figure 40: Unit top venting styles.

venting style.

 

If 4” (10 cm) “B-vent” is used a minimum of 1” (25 mm) must be

 

maintained between the vent connector and any combustibles.

����� ���� �����

CAUTION: A minimum vent height of 12’ (3.6 m) from the floor is

��������

 

�� ��� ��� ��� ��

required to effectively vent this fireplace.

 

SPILLAGE TEST:

 

A spillage test must be performed prior to leaving the installed fireplace

 

with the customer. Perform this test in the following manner:

 

1. Close all windows and doors in the room.

 

2. Start all exhaust fans in the house and the furnace blower.

 

3. Light the fireplace and set to maximum flame adjustment.

 

Figure 42: Draft test place.

29

Image 29
Contents Westport For Your SafetyGeneral Safety PrecautionsTable of Contents Rear Vent DV Codes And ApprovalsTOP Vent DV Dimensions SpecificationsOperating Instructions For Your Safetyread Before OperatingGas valve Electronic Ignition Module Location Maintenance And ServiceHandles for Removing Door To ReplaceStep To be Installed by a Qualified Service Agency onlyConversion instructions Natural Gas Qualified Installers only Initial InstallationVenting Terminals Cannot be Recessed Into a Wall or Siding Restrictor plate settings For sufficient vent height above the roof line. For two Pipes and fittings, are Installing Vent Cap with Vinyl Siding Stand Off Corner installation rear vented with Wall Framing for Hole for Vertical OnceTwist-lock the vent cap Multi-Story Vent Pipe Installation KIT Components Installation InstructionsCut away of spacers on Flex Pipe Fire stop Assembly of Venting into a Class ‘A’ Chimney Screws removed in see Figure Turn the elbow to the rear vent position and re-fasten withInstallation for Top Vented Horizontal Termination Corner InstallationWiring Diagram InstallationA. Installations Canadian InstallationsGeneral Venting Information Venting of a Fireplace Fitted with the Drafthood AdaptorOptional Finishing Automatic Safety Shut DownSpill Switch Replacement To Test Valve Pressures GAS Line ConnectionWiring Diagram For Fan Control Wire Size Max. LengthOptional Blower Fan Installation Secondary InstallationComplete Log Placement Log Placement with Rock Wool Brick panel bracket, slots shown Problem Possible Cause Solution Trouble ShootingReference Number Part Description Part Number Parts List CastCast Leg Each Painted Parts Diagram Cast Reference Part Description Part Number Parts List ComponentsParts List Components Parts Diagram Components To the Dealer WarrantyInstallation Data Sheet