PGS TC36 AR manual Mantel Clearance Chart, Ceiling, Support

Page 4

COMBUSTIBLE FRAMING AND

FINISH WALL ABOVE STANDOFFS

MAY USE COMBUSTIBLE FACING

MATERIAL IN THIS AREA

NON-COMBUSTIBLE

FINISH MATERIAL

SEE FIG #7

D

E

AF

B

C

TOP OF LINTEL BAR

FIREPLACE FRONT

Fig. # 2

STEEL FRAMING

STANDOFFS

NON-COMBUSTIBLE ZONE.

DO NOT INSTALL ANY

COMBUSTIBLE MATERIAL,

ELECTRICAL WIRING OR

GAS PLUMBING IN THIS

AREA.

MANTEL CLEARANCE CHART

REF.

MANTEL

REF.

*CLEARANCE

 

 

A

9"

D

B

6"

E

C

3"

F

**DEPTH 12"MANTEL

63/4"

1 1/2"

Minimum Clearances to Combustibles:

Side standoffs

0 in.

(0 mm)

Back standoffs

0 in.

(0 mm)

Top standoffs

0 in.

(0 mm)

Bottom of appliance

0 in.

(0 mm)

Adjacent sidewall

4 in.

(102 mm)

Ceiling to appliance

24 in.

(610 mm)

*Mantel to appliance

See Figure #2

**Maximum

 

 

Mantel extension

See Figure #2

Mantel support

4 in.

(102 mm)

Vertical vent pipe

1-3/4 in.

(45 mm)

Horizontal vent pipe

 

 

Top

1-3/4 in.

(45 mm)

Sides

1-3/4 in.

(45 mm)

Bottom

1-3/4 in.

(45 mm)

Fig. # 3

CEILING

MANTEL

ADJACENT

 

 

WALL OR

 

MANTEL

 

SUPPORT

UNIT MAY BE RECESSED UP TO 6" WITH NON-COMBUSTIBLE MASONRY TYPE MATERIAL

4 36ARB2

050505-36

Image 4
Contents Installation Operating Instructions What to do if YOU Smell GASContents Safety Fireplace DimensionsMantel Clearance Chart CeilingMantel Mantel ClearanceTOP Standoffs Installation RequirementsLocating the Fireplace Dimensions Steel Stud Framing KITTC36.BFRKITA Framing and FinishingInstallation Detail Concrete BoardReconnect Pilot Flame indicator wiring and reinstall Control BOXHearth Extension Window FrameControl BOX Location Framing Detail Not OverVenting Exterior wall openingWall thimble Wall Thimble and Vent Must not Protrude Beyond SidingTrim to Length Wall Shield Thimble TCVT.THIMA Insulated Collar ShieldVent pipe Wall vent terminalWall Roof Termination Roof Termination Venting Vent Pipe Roof Support BracketCeiling opening Ceiling firestopVent Pipe Mastic Storm Collar Vertical Termination CAPRoof vent terminal Vent Terminal Clearance Vent Terminal Minimum ClearancesVent Terminal Minimum Clearances to Adjacent Structures Vent Pipe Sealant Vent Pipe SealantInsulated Collar Shield Be USED. see Section BelowWall and Roof TerminationRestrictor PositionOptional Wall Switch Manual Millivolt ValveGAS Supply Max. LengthWindow Frame Removal Firebox Panels Installation Herringbone Panel SET ShownHerringbone Heritage REDFor Your Safety Read Before Lighting Lighting InstructionsTo Turn OFF GAS to Appliance First FireWall Thermostat Canada Only Optional GASC.THERMO HI-LO Flame AdjustmentExtend Shutdown Millivolt Pilot MaintenanceElectronic Pilot Replacement Parts DescriptionReplacement PARTS-MILLIVOLT Control Assembly Pilot Assembly NGReplacement Parts Electronic Control Assembly ELECTRONIC, Wire HarnessElectronic Valve Wiring Diagram Fig. #Wall Termination KIT Roof Termination KIT Vent Pipe Dimensions Pipe 10 1/4 16 1/4 10 15/16 22 1/4 46 1/4Pipe 23 1/4 27 5/8 PipeFlexible Connector With Shutoff Valve Various GAS Supply ConnectionsGastitetm Flex Line with Reducing Coupling Black Iron Pipe with UnionSafety Label Location For USE with Natural GAS LP GASEN Case D’EMPLOI Avec Made in CanadaAllenby Rd., Duncan, BC V9L Phone