Regency CS1200 installation manual Combustible Wall Chimney Connector PASS-THROUGHS

Page 11

INSTALLATION

COMBUSTIBLE WALL CHIMNEY

CONNECTOR PASS-THROUGHS

Method A: 12" (304.8 mm) Clearance to Combustible Wall Member:

Using a minimum thickness 3.5" (89 mm) brick and a 5/8" (15.9 mm) minimum wall thickness clay liner, construct a wall pass-through. The clay liner must conform to ASTM C315 (Standard Specification for Clay Fire Linings) or its equivalent. Keep a minimum of 12" (304.8

mm)of brick masonry between the clay liner and wall combustibles. The clay liner shall run from the brick masonry outer surface to the inner surface of the chimney flue liner but not past the inner surface. Firmly grout or cement the clay liner in place to the chimney flue liner.

Method B: 9" (228.6 mm) Clearance to Combustible Wall Member:

Using a 6" (152.4 mm) inside diameter, listed, factory-built Solid-Pak chimney section with insulation of 1" (25.4 mm) or more, build a wall pass-through with a minimum 9" (228.6 mm) air space between the outer wall of the chimney length and wall combustibles. Use sheet metal supports fastened securely to wall surfaces on all sides, to maintain the 9" (228.6 mm) air space. When fastening supports to chimney length, do not penetrate the chimney liner (the inside wall of the Solid-Pak chimney). The inner end of the Solid-Pak chimney section shall be flush with the inside of the masonry chimney flue, and sealed with a non-water soluble refractory cement. Use this cement to also seal to the brick masonry penetration.

Method C: 6" (152.4 mm) Clearance to Combustible Wall Member:

Starting with a minimum 24 gage (.024" [.61 mm]) 6" (152.4 mm) metal chimney connector, and a minimum 24 gage ventilated wall thimble which has two air channels of 1" (25.4 mm) each, construct a wall pass-through. There shall be a minimum 6" (152.4) mm separation area containing fiberglass insulation, from the outer surface of the wall thimble to wall combustibles. Support the wall thimble, and cover its opening with a 24-gage minimum sheet metal support. Maintain the 6" (152.4 mm) space. There should also be a support sized to fit and hold the metal chimney connector. See that the supports are fastened securely to wall surfaces on all sides. Make sure fasteners used to secure the metal chimney connector do not penetrate chimney flue liner.

Method D: 2" (50.8 mm) Clearance to Combustible Wall Member:

Start with a solid-pak listed factory built chimney section at least 12" (304 mm) long, with insulation of 1" (25.4 mm) or more, and an inside diameter of 8" (2 inches [51 mm] larger than the 6" [152.4 mm] chimney connector). Use this as a pass-through for a minimum 24-gage single wall steel chimney connector. Keep solid-pak section concentric with and spaced 1" (25.4 mm) off the chimney connector by way of sheet metal support plates at both ends of chimney section. Cover opening with and support chimney section on both sides with 24 gage minimum sheet metal supports. See that the supports are fastened securely to wall surfaces on all sides. Make sure fasteners used to secure chimney flue liner.

Minimum

12 in. (304.8mm) to combustibles

Minimum chimney clearance to brick and combustibles 2 in. (50.8mm)

 

Minimum clearance

 

12 in. (304.8mm)

Flue

of brick

 

Chimney

connector

 

Chimney

 

Fire clay

Masonry chimney

liner

 

Regency CS1200 Freestanding Wood Stove

11

Image 11
Contents CS1200 Alterra Freestanding Wood Stove Regency Fireplace Product Safety Label Table of Contents Unit Dimensions DimensionsRoom AIR Residential InstallationModular Installation Options Minimum Clearance to Combustible Materials Minimum Alcove Clearance to Combustible Materials Minimum Alcove Clearance to Combustible MaterialsStep by Step Chimney Connector Installation Factory Built Chimney Masonry ChimneyMasonry Fireplace Combustible Wall Chimney Connector PASS-THROUGHS # of Elbows Recommended Heights for Woodstove FlueMobile Home Installation Installation Listed Components for Mobile Home InstallationDoor Handle Baffle and Tube Installation Brick InstallationStainless Steel Panels Side Panel InstallationAsh drawer Lid ASH Drawer OptionLeft to Right Side Opening Lower Surround Door ReversalCast Door Reversal Left to Right Side Opening Wood Storage Optional Ashlip InstallationFAN Operation BLOWER/FAN InstallationFAN Wiring First Fire Operating InstructionsDraft Control ASH Disposal Safety PrecautionsFAN Maintenance Safety GuidelinesCreosote MaintenanceDoor Catch Adjustment Glass ReplacementMain Assembly Parts ListFire Brick FAN AssemblyRegency CS1200 Freestanding Wood Stove Regency CS1200 Freestanding Wood Stove Regency CS1200 Freestanding Wood Stove Warranty Installer Please complete the following information