Regency F2100M, S2100M Residential Installation, Room AIR, Modular Installation Options

Page 9

INSTALLATION

RESIDENTIAL

INSTALLATION

1)Read all instructions before installing your Regency Stove. Install and use only in accordance with these installation and operating instructions. Be aware that local Codes and Regulations may override some items in this manual. Check with your local inspector.

2)Select a position for your Regency Stove. Consult the minimum clearance chart for your model and set the stove in place. For close clearance installation use listed dou- ble wall connector systems (see page 15).

3)To insure vertical alignment, suspend a plumb bob from the ceiling over the exact center of your stove flue and mark a spot on the ceiling to indicate the center of the chimney.

4)Check that the area above the ceiling is clear for cutting. Re-confirm the clearance from the stove to combustibles to insure that they are within the prescribed limits.

5)Install chimney according to chimney man- ufacturers instructions. The performance of your woodstove is governed to a very large part by the chimney system. Too short a chimney can cause difficult start-up, dirty glass, backsmoking when door is open, and even reduced heat output. Too tall a chim- ney may prompt excessive draft which can result in very short burn times and exces- sive heat output. The use of an inexpensive flue pipe damper may be helpful in reducing excessive draft.

CAUTION: The chimney should be the same size as the flue outlet on the stove. The

chimney must be listed as suitable for use with solid fuels. For other types of chim- neys check with your local building code officials. Do not confuse a chimney with a type “B” Venting System used for gas appliances as suitable for a wood burning appliance. For Mobile Home installations refer to that section on page 14.

6)Mark the location of the pedestal base or legs on the floor, then move the stove aside and mark the position of the floor protector.

7)The floor protector must be of non-combus- tible material and must extend 16" in front of the door opening and 6" to the sides and rear of the unit. Some areas may require a larger size floor protector. See your local inspector. For outside air installation refer to Mobile Home installation instructions on page 14.

NOTE: In Canada, floor protection must extend 18" to the front and 8" to each side of the stove.

8)When the floor protection is complete, po- sition the stove with the flue collar centered under the installed chimney.

9)In seismically active areas, Regency rec- ommends that your unit is secured to the floor by using the bolt down holes inside the pedestal (the same ones used in Mobile Home installations).

10)For residential installations using "C" Vent (single wall) the chimney connector must be at least 24 gauge steel. Do not use galvanized pipe. For Mobile Home installa- tion refer to the Mobile Home installation instructions on page 14.

11)Do not connect this unit to a chimney serv- ing another appliance unless approved by

your local building authority.

12)A chimney connector cannot pass through an attic or roof space, closet or similar concealed space, or a floor, ceiling, wall or partition of combustible construction. In Canada, if passage through a wall, or par- tition of combustible construction is de- sired, the installation shall conform to CAN/ CSA-B365, Installation Code for Solid-Fuel- Burning Appliances and Equipment.

13)Your Regency Woodstove is not to be connected to any air distribution duct.

Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.

ROOM AIR

IMPORTANT

For installation using room air for combustion, remove knockout from the pedestal, and/or from the bottom if using a heat shield.

Mobile home installations require the use of outside air.

On pedestal units there are two locations where outside air may be adapted to the unit. If using the bottom of the pedestal, do not remove knockout from the rear of the pedestal. Only remove rear knockout if outside air will be brought in from the rear.

On leg units outside air can only be brought in from the bottom of the heat shield.

Note: Once the knockout is removed there are two tabs remaining. Bend both tabs out for ease of installa- tion when attaching outside air.

MODULAR INSTALLATION OPTIONS

The following items are required when assembling your Regency Stove. F1100, F2100, and F3100 units - the Rear Heat Deflector is supplied with the stove, but if you choose not to use it you must use the Airmate instead.

 

Modular Part

Things to consider when choosing options:

 

F1100, F2100 and

Clearances are different. See the chart on pages 10 and 11. Generally you can get closer clearances with the airmate

 

F3100 only:

than with the rear heat deflector.

 

Airmate OR

Convection heat with Airmate vs. Radiant Heat with Rear Heat Deflector. The airmate pushes heat forward and into

 

Rear Heat Deflector

 

the room, the rear heat deflector deflects the heat upward. See installation instructions on pages 11 and 12.

 

 

 

 

 

 

(all units)

There are no performance differences with either the pedestal or legs. It is primarily a personal preference. Legs

 

Pedestal OR

can be either painted steel, painted cast, or gold plated cast.

 

 

 

Legs

 

 

Leg installation requires the bottom shield. See installation instructions on page 13.

 

 

 

 

 

OPTIONS: These can be installed at time of installation or added later:

 

 

 

 

Modular Option

Things to consider when choosing options

 

Blower/Fan

Adding the blower will increase the area heated by the stove, it can move warm air beyond the room where the stove

 

is installed. Installation instructions on page 18.

 

 

 

 

Ash Drawer Kit

Adding the Ash Drawer Kit makes cleaning ashes out of the stove easier and cleaner. Installation instructions on page

 

17.

 

 

 

 

 

 

 

 

Regency Freestanding Woodstove

9

Image 9
Contents Freestanding Woodstoves Modular Parts RegencyfireplaceproductTable of Contents Safety Label 20022001 APR MAY JUN JUL AUG Sept 101Model Regency Large Freestanding Stove F3100L Tested to 102NOV Do not Remove this Label DECSept MARSafety Label Residential Installation InstallationModular Installation Options Room AIRMinimum Clearance to Combustible Materials Residential Installation C Vent Single WallFloor Protection Minimum Alcove Clearance to Combustible MaterialsAirmate Assembly for F1100 F2100, and F3100 Stove Assembly Prior to InstallationS2100M & S3100L Side Shield Adjustment Small & Medium 850-105 Large 850-305Leg and Bottom Shield Assembly Step by Step Chimney Connector InstallationRecommended Heights for Woodstove Flue Mobile Home InstallationBrick Flue Baffle & Secondary AIR Tube Installation Listed Components For Mobile Home InstallationInstallation Canadian InstallationsSmall Stoves F1100S Medium Stoves F2100M and S2100MGlass Installation Brick Installation Door HandleOptional Accessories Pedestal Ash Drawer KitBlower/Fan Wiring Diagram Operating Instructions Operating InstructionsDraft Control First FireMaintenance Safety GuidelinesSafety Precautions ASH DisposalCreosote Latch Adjustment Glass Maintenance MaintenanceMaintenance GOLD-PLATED Doors Door GasketParts List F1100 & F3100 Stove Main AssemblyDescription F2100 Stove Main Assembly S2100 & S3100 Step Stove Main Assembly PEDESTAL, Bottom Shield & LEG Options Firebrick Warranty Lifetime WarrantyInstaller Please complete the following information