Regency P33-LP4 installation manual Installation Procedures, For Regency Direct Vent System Flex

Page 13

INSTALLATION

INSTALLATION PROCEDURES

for Regency® Direct Vent System (Flex)

1)Locate the unit in the framing, rough in the gas (preferably on the right side of the unit) and the electrical (Junction block is on the left side) on the left. Locate the centerline of the termination and mark wall accordingly. Cut a 10"(254mm) hole in the wall (inside dimension).

Note: To make the installation more aestheticallypleasing,werecommend framing out a square to mount the terminal to.

Note: A 2-1/2" (64mm) horizontal top and 1-1/2" (38mm) horizontal sides & bottom clearance around the liner

*If this is an outside corner, the minimum distance between the vent and the outside corner is 6" (15cm) with AstroCap termination cap or 12" (30cm) with Dura-Vent termination cap. See "F" in the diagram in "Exterior Vent Trmination Locations" Section.

Minimum and Maximum Vent Clearances

must be maintained except that only a 1" (25mm) clearance is needed at the termination end. We recommend framing a 10"(254mm) x 10"(254mm) (inside dimensions) hole to give structural rigidity for mounting the termination.

Note: If installing termination on a siding covered wall, furring strips must be used to ensure that the termination is not recessed into the siding.

2) Levelthefireplaceandfastenittotheframing

using nails or screws through the nailing

strips.

5)Slip the assembled liner and termination assembly through the thimble making sure the termination cap faces up (there are markings on the cap that show which way is up). This will position the termination cap with proper down slope for draining water. Fasten the cap to the outer wall with the 4 supplied screws.

6)Pull the centre 4"(100mm) liner and outer 6-7/8"(175mm) liner out enough to slip over the fl ue collars of the fi replace.

7)Apply Mill Pac over the fi replace inner collar and slip the 4"(100mm) liner down over it and attach with 3 supplied screws.

8)Do the same with the 6-7/8"(175mm) liner.

9)Apply a bead of silicone between the thimble and termination and around the outer edge of the terminal at the wall in order to keep the water out.

IMPORTANT:Donotlocatetermination hood where excessive snow or ice buildup may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.

3) Assemble the vent assembly by applying

Mill Pac to the 4"(100mm) inner collar of the

terminationand slippingthe4"(100mm)liner

over it at least 1-3/8" (35mm). Fasten with

the3screws(drillingpilotholeswillmakethis

easier). Apply Mill Pac or high temperature

silicone to the 6-7/8"(175mm) fl ex pipe and

slip it over the 6-7/8" outer collar of the vent

terminal at least 1-3/8"(35mm) and fasten

with the 3 screws.

4) Separate the 2 halves of the wall thimble and

securely fasten the one with the tabs to the

outside wall making sure that the tabs are

on top and bottom. Fasten the other thimble

half to the inside wall. The thimble halves

slip inside each other and can be adjusted

for 2 x 4 or 2 x 6 walls. The liners must slip

over the collars a minimum of 1-3/8".

 

 

2” x 4” or 2” x 6”

4" (102mm)

 

(21mm x 102mm

 

or 21mm x 152mm)

dia. flue pipe

 

 

Termination Cap

with spring spacer

 

 

 

 

 

 

 

 

 

Screws

(3 per

connection)

6-7/8"

Screws

(175mm)

(4 per connection)

dia. air intake

 

Wall Thimble 2 pieces

 

(10" (254mm) Outer Diameter)

 

Regency® P33-4 Zero Clearance Direct Vent Gas Fireplace

13

Image 13
Contents P33-4 Zero Clearance To the New Owner Information for MOBILE/MANUFACTURED Homes After First SaleTable of Contents Safety Label Safety LabelFor the State of Massachusetts only RequirementsGeneral Safety Information InstallationImportant Message Before YOU StartUnit Dimensions Installation ChecklistLocating Your Fireplace Duct System OptionMantel LEG Clearances ClearancesVertical Termination or Vertical Rise with Horizontal Framing and FinishingRear Termination Top Standoff Assembly Unit Assembly Prior to InstallationVenting Introduction Top Facing Support Side Nailing Strips= Clearance to permanently closed window *min /30cm Exterior Vent Termination LocationsHorizontal Terminations Only Regency Direct Vent Flex SystemAlternate Without any joints or seamsFor Regency Direct Vent System Flex Installation ProceduresMinimum and Maximum Vent Clearances Vent Length Flat Wall InstallationThickness inches Required inches Max. WallDescription 6-5/8 Rigid Pipe Cross Reference Chart6-5/8 Rigid Pipe Cross Reference Chart Vertical Terminations Propane & Natural Gas Rigid Pipe Venting ArrangementsInstallation Regency Direct Vent System Flex Option + H1 Horizontal Venting with Two 2 90o ElbowsOption +H1+H2 Option +H1Vertical Venting with Two 2 90o Elbows Horizontal Venting with Three 3 90o ElbowsOption +V1 +H1 Option +V1Vertical Venting with Three 3 90o Elbows Required Parts Vertical Termination With CO-LINEAR Flex SystemDescription Alternate Approved CapsHorizontal Distance Feet Venting Arrangements Vertical TerminationsSnorkel Terminations Unit Installation with Horizontal TerminationGAS Line Installation Unit Installation With Vertical TerminationThis allows for small adjustments GAS Pipe Pressure Testing Pilot AdjustmentHigh Elevation T. Valve DescriptionConversion KIT# 434-969 from NG to LP For P33-4/H25-1 Using SIT 820 Nova Gas ValveGlow on logs Installation of the DC Sparker for the P33-4 Unit Only 251 250Optional Flush Trim Standard Flush DoorCutout 5th Grate TabDouble Screen Door Flush LouversOptional BAY Trim Optional BAY DoorFlush Louver Top Heat Shield BAY LouversBay Louver Top Heat Shield Burner ON/OFF Control boxCut-Out Oblong Hole Top Flange Bottom Full Screen DoorsCut-Outs Top Grill Hinge Location Bottom GrillWall Switch Remote ControlThermostat Wire Table Wall ThermostatDo not cut the ground terminal off under any circumstances Wiring DiagramsFor Propane Units and Units Equipped with DC Spark Boxes Secure the 2 boxes together With one screw Installing the Optional FANCopy of the Lighting Plate Instructions Operating InstructionsShutdown Procedure Lighting ProcedureAeration Adjustment Operating InstructionsNormal Operating Sounds Maintenance MaintenanceLOG Replacement GAS AppliancesBay Glass Replacement Flush Glass ReplacementThermopile Thermocouple Glass GasketDiagram 3 Lift out Valve Tray Assembly Installing ValveDiagram 2 Rear Log Stand & Valve Tray Assembly Removing ValveMain Assembly Parts ListDescription Parts List Part Description Burner & LOG AssemblyFlush Front & Louvers BAY Front & Louvers Conditions WarrantyInstaller Please complete the following information

P33-LP4 specifications

Regency P33-LP4 is an innovative and versatile propane gas fireplace designed to provide both warmth and ambiance while enhancing the aesthetic appeal of any living space. This model stands out for its combination of modern technology, functionality, and elegance, making it a popular choice among homeowners seeking an efficient heating solution without sacrificing style.

One of the key features of the P33-LP4 is its contemporary design. The fireplace presents a sleek, minimalist look that integrates seamlessly into both traditional and modern interiors. It offers a range of finishing options, including various trims and glass fronts, allowing homeowners to tailor the appearance of the fireplace to their personal taste and existing decor.

A hallmark of the Regency P33-LP4 is its advanced heating capabilities. With a powerful output of up to 33,000 BTUs, this fireplace can efficiently heat spaces of different sizes, making it suitable for both small cozy rooms and larger open areas. The unit also features a high-efficiency burner that maximizes heat production while reducing fuel consumption, which is ideal for energy-conscious users.

In terms of technology, the P33-LP4 boasts a user-friendly electronic ignition system that ensures reliable startups, even in colder temperatures. The fireplace can be controlled through a convenient remote or a wall switch, allowing users to adjust the flame height and heat settings with ease. Additionally, the unit incorporates a fan that circulates warm air throughout the room, enhancing overall heating efficiency and comfort.

Safety is paramount in the design of the Regency P33-LP4. The fireplace is equipped with a built-in safety shut-off feature that automatically turns off the gas supply in case of an unexpected accident. Moreover, the glass front remains cool to the touch, reducing the risk of burns and making it family-friendly.

Flexibility is another advantage of the P33-LP4, as it can be installed in various configurations, including as a built-in unit or a freestanding fireplace. The options for installation enable homeowners to create a unique focal point in their living space, adapting to different architectural layouts.

In conclusion, the Regency P33-LP4 combines contemporary design, efficient heating technology, and safety features, making it an excellent choice for those seeking a stylish and functional propane fireplace. Its versatility and reliability enhance the home environment while providing a warm and inviting atmosphere for family and guests.