Regency 510-994, 946-523/P Rigid Pipe Venting, Venting Arrangements Vertical Terminations

Page 6

Gas Fireplaces

Rigid Pipe Venting

Horizontal or Vertical Terminations

Alternate Horizontal

Termination Caps

If required by the external termination location the listed alternate termination caps may be used. (Refer to Page 11)

Venting Arrangements - Vertical Terminations

Rigid Pipe System

(Propane & Natural Gas)

The P33 is approved for a maximum 40 ft. straight vertical, with Rigid Pipe vent systems for Propane and Natural Gas.

The lightly shaded area,

, in the diagram shows allowable venting

configurations with a maximum two 45° elbows.

The darker shaded area,

, in the diagram shows allowable venting

configurations using one 45° and one 90° elbow.

Vent must be supported at offsets.

Horizontal sections must be supported every 3 feet.

Firestops are required at each floor level and whenever passing through a wall.

Maintain clearances to combustible materials.

Minimum of 1’ pipe section between elbows.

Note: Must use optional rigid pipe adapter when using Rigid Pipe (Part # 510-994).

*Unit must be raised by 1” when using Contemporary Faceplate

August 2008 Product Specifications Book

P33 Gas Fireplace

 

0

2

4

6

8

10

12

14

 

40

 

 

 

 

 

 

 

 

38

 

 

 

 

(12.2m)ft.40

 

 

 

34

 

 

 

 

 

 

 

36

 

 

 

 

 

 

 

 

32

 

 

 

 

Maximum:

 

 

 

30

 

 

 

 

 

 

 

 

28

 

 

 

 

 

 

 

 

26

 

 

 

 

 

 

 

 

24

 

 

 

 

 

 

 

(Feet)

22

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

Height

 

 

 

 

 

 

(8.2m)

 

 

 

 

 

 

 

Vertical

18

 

 

 

 

 

 

27Maximum:ft.

 

 

 

 

 

 

 

 

 

16

 

 

 

 

 

 

 

14

 

 

12

 

 

10

 

 

8

 

 

6

8’6”(2.6m)

9’6”(2.9m)

 

4

Minimum

Minimum

 

2

 

 

0

 

 

Minimum 12” (305mm)

Max. 10’ (3m)(centerline to centerline)

 

33

Gas Fireplaces

Image 6
Contents Model P33-NG4 P33-LP4 August 2008 Product Specifications BookApproved Venting Systems P33-NG4 w P33-LP4 w Model August 2008 Product Specifications BookContemporary Faceplate Combustible Mantels Framing and FinishingClearance Requirements Mantel Leg ClearancesClearance Dimension Measured From Mantel Leg Clearances with Contemporary FaceplateFlue Clearances to Combustibles Horizontal Terminations Only FPI Direct Vent System FlexSnorkel Terminations Snorkel TerminationsAlternate Horizontal Termination Caps Rigid Pipe VentingVenting Arrangements Vertical Terminations Horizontal or Vertical TerminationsElbows is required OptionMinimum of 1 foot between Option + H1Venting Arrangements Horizontal Terminations Vent Termination LocationsElbows is MinimumFoot between RequiredVertical termination with co-linear flex system Required Parts DescriptionAlternate Approved Caps