Regency 946-523/P, 510-994 Minimum, Foot between, Elbows is, Required, Option + H1 + H2

Page 9

Gas Fireplaces

P33 Gas Fireplace

Horizontal Venting with Two (2) 90° Elbows - Initial vertical section.

Two 45° elbows = One 90° elbow

Option

V

H+ H1

Maximum total pipe: length, of

 

 

 

all sections, must not exceed

A)

1’ Min.

3’ Max.

30 feet.

 

 

 

B)

2’ Min.

4’ Max.

Total horizontal sections must

 

 

 

not exceed 8 feet.

C)

3’ Min.

5’ Max.

Minimum of 1 foot between

 

 

 

D)

4’ Min.

6’ Max.

90° elbows is required.

E)

5’ Min.

7’ Max.

 

 

 

 

 

F)

6’ Min.

8’ Max.

 

Horizontal Venting with Two (2) 90° Elbows - Initial horizontal section.

Two 45° elbows = One 90° elbow

Option

H

V

H + H1

Maximum total pipe: length, of

 

 

 

 

all sections, must not exceed

A)

1’ Max.

1’ Min.

3’ Max.

30 feet.

 

 

 

 

B)

2’ Max.

2’ Min.

5’ Max.

Total horizontal sections must

 

 

 

 

not exceed 8 feet.

C)

3’ Max.

4’ Min.

6’ Max.

Minimum of 1 foot between

 

 

 

 

D)

4’ Max.

6’ Min.

7’ Max.

90° elbows is required.

 

 

 

 

 

E)

5’ Max.

8’ Min.

8’ Max.

 

 

 

 

 

 

36

Gas Fireplaces

Horizontal Venting with Three (3) 90° Elbows - Initial vertical section.

Two 45° elbows = One 90° elbow

Option

V

H

V+ V1

H + H1

Maximum total

 

 

 

 

 

pipe: length, of

A)

2’ Min.

1’ Max.

3’ Min.

4’ Max.

all sections, must

 

 

 

 

 

B)

3’ Min.

2’ Max.

4’ Min.

5’ Max.

not exceed 30

 

 

 

 

 

feet.

C)

4’ Min.

3’ Max.

6’ Min.

6’ Max.

Total horizontal

 

 

 

 

 

D)

5’ Min.

4’ Max.

8’ Min.

7’ Max.

sections must not

 

 

 

 

 

exceed 8 feet.

E)

6’ Min.

5’ Max.

10’ Min.

8’ Max.

Minimum of 1

F)

7’ Min.

6’ Max.

12’ Min.

9’ Max.

foot between

90° elbows is

 

 

 

 

 

 

 

 

 

 

required.

Horizontal Venting with Three (3) 90° Elbows - Initial horizontal section.

Two 45° elbows = One 90° elbow

Option

H

V

H + H1 + H2

Maximum total pipe:

 

 

 

 

length, of all sections,

A)

1’ Max.

1’ Min.

3’ Max.

must not exceed 30

 

 

 

 

feet.

B)

2’ Max.

3’ Min.

5’ Max.

Total horizontal sections

 

 

 

 

must not exceed 7

C)

3’ Max.

5’ Min.

6’ Max.

feet.

 

 

 

 

 

 

 

 

Minimum of 1 foot

D)

4’ Max.

7’ Min.

7’ Max.

between 90° elbows

 

 

 

 

 

 

 

 

is required.

E)

5’ Max.

9’ Min.

8’ Max.

 

 

 

 

 

 

F)

6’ Max.

11’ Min.

9’ Max.

 

 

 

 

 

 

August 2008 Product Specifications Book

Image 9
Contents Model P33-NG4 P33-LP4 August 2008 Product Specifications BookApproved Venting Systems P33-NG4 w P33-LP4 w Model August 2008 Product Specifications BookContemporary Faceplate Clearance Requirements Framing and FinishingCombustible Mantels Mantel Leg ClearancesClearance Dimension Measured From Mantel Leg Clearances with Contemporary FaceplateFlue Clearances to Combustibles Snorkel Terminations FPI Direct Vent System FlexHorizontal Terminations Only Snorkel TerminationsVenting Arrangements Vertical Terminations Rigid Pipe VentingAlternate Horizontal Termination Caps Horizontal or Vertical TerminationsMinimum of 1 foot between OptionElbows is required Option + H1Vent Termination Locations Venting Arrangements Horizontal TerminationsFoot between MinimumElbows is RequiredVertical termination with co-linear flex system Required Parts DescriptionAlternate Approved Caps