VHX SERIES STEAMER - ELECTRICAL OPERATION

ELECTRICAL OPERATION

WATER LEVEL CONTROLS

Low Level Cut-Off & Differential Control

The steamer is equipped with three water level sensing probes (high, low and low level cut-off) and a single water level control board (solid state). The water level control board performs two functions: 1) Provide low level cut-off protection to shut off the heat source in case the water level drops below the low level cut-off (LLCO) probe. 2) Perform as a differential level control to maintain the water level between the low and high water level probes.

The water level control (WLC) has input voltage (120VAC) across terminals 11 and 12 which powers the primary side of the transformer. On one side of the transformer secondary, power is provided to the control by a series path through chassis ground (terminal 10). The other side of the transformer secondary (12VAC) is attached to the probe that directs power to the other side of board relay coils (LLCO and HL) and to the Inverse Latching Relay (ILR) electronic circuit on the board. As water enters the boiler, it becomes part of the water level control’s circuit. When the water level in the boiler reaches a probe, that circuit is completed.

The inverse latching relay of the board is de- energized, leaving the ILR-1 (N.O.) and ILR-2 (N.C.) contacts in their shelf state.

When the main power switch is turned ON, power is supplied to the WLC board which energizes the high level (HL) relay, closes HL-3 normally open contacts, and illuminates the HL relay LED. With the HL-3 contacts closed, the boiler fill solenoid is energized and water begins filling the boiler.

When the water level reaches the low level cut-off (LLCO) probe, the LLCO relay is energized and illuminates the LLCO LED. With the LLCO-2 contacts closed the heat source is then energized. The LLCO relay will remain energized and its LED will stay lit until the water level in the boiler drops below the LLCO probe. NOTE: Auxiliary control(s) in the heating circuit must also be satisfied before heating can start.

When the water level reaches the low level (LL) probe, power to terminal 2 on the WLC board is present but no switching occurs.

After the water level reaches the high level (HL) probe, the inverse latching relay of the board is energized and locked through the low level probe

(LL)and ILR-1 contacts. With ILR-2 contacts open, this de-energizes the HL relay and the HL LED goes out. With the HL-3 contacts open, the boiler fill solenoid is de-energized, stopping the flow of water

into the boiler.

When the water level drops below the low level (LL) probe, power is removed from the inverse latching relay, the HL relay energizes through ILR-2 and HL contacts change state. The fill solenoid is energized through HL-3 to refill the boiler and the HL LED is lit. The HL relay and LED will toggle ON and OFF during a cooking cycle as needed.

Page 41 of 68

 

F24700 (October 2001)

 

Page 41
Image 41
Vulcan-Hart VHX24G5, MHB24G manual Electrical Operation, Low Level Cut-Off & Differential Control