INSTALLATION

REMOTE CONTROL

WALL SWITCH

WALL THERMOSTAT

Use the Regency Remote Control Kit approved for this unit. Use of other systems may void your warranty.

The remote control kit comes with a hand held transmitter, a receiver and a wall mounting plate.

1)Choose a convenient location on the wall to install the receiver and the receptacle box (protection from extreme heat is very important). Run wires from the fireplace to that location. Use Thermostat Wire Table.

2)Connect the two wires to the gas valve. See diagram below.

CAUTION

Do not wire millivolt remote control wires to 120V wire.

3)Install 3AAAalkaline batteries in transmitter and 4 AA alkaline batteries in the receiver. Install the receiver and its cover in the wall. Switch the remote receiver to "remote" mode. The remote control is now ready for operation.

1)Run the wire through the right or left side inlet opening. Be careful not to damage the wire.

Note: We recommend a maximum of 15' of wire but if you wish to go with a longer run, use the Thermostat Wire Table.

2)Connect the wire to the supplied wall switch and install into the receptacle box.

CAUTION

Do not wire millivolt

wall switch wire

to 120V wire.

A wall thermostat may be installed if desired, connect the wires as per the wiring diagram. Use table below to determine the maximum wire length.

Note: Preferable if the thermostat is installed on an interior wall.

Regency offers an optional programmable thermostat but any 250-750 millivolt rated non- anticipator type thermostat that is CSA, ULC or UL approved may be used.

CAUTION

Do not wire millivolt wall thermostat wires to 120V wire.

Thermostat Wire Table

Recommended Maximum Lead Length

(Two-Wire) When Using Wall

Thermostat (CP-2 System)

Wire Size

Max. Length

 

14 GA.

50

Ft.

 

16 GA.

32

Ft.

 

18 GA.

20

Ft.

 

20 GA.

12

Ft.

 

22 GA.

9

Ft.

 

26

Regency® E21-3 Gas Fireplace Insert

Image 26
Contents E21 Gas Insert Congratulations Table of Contents Safety Label Duplicate Serial NoRequirements MA Code CO DetectorImportant Message Save These Instructions InstallationGeneral Safety Information Before YOU StartInstallation Checklist Minimum Fireplace ClearancesClearances to Combustibles Combustible boardGAS Connection High ElevationWiring Diagrams Lug DetailFlue Connector Installation For Propane Units and Units Equipped with DC Spark BoxesVenting GAS Pipe Pressure TestingOffset Flue Adaptor Test for Flue Spillage Valve DescriptionGAS Insert Aeration System Optional Brick Panel27-26 LOG SET Installation27-23 27-30 27-27 27-24 27-28 27-25 27-2327-27 27-26 27-24 27-26 27-2527-27 27-25 27-23 27-27 27-29 27-24 27-26 27-29 27-2827-30 27-23 Ensure not to cover any burner ports 27-27 27-23 27-24 27-30 27-29 27-26 27-25Faceplate & Trim Installation DiagramFlush Glass Flush Louvers Use of substitute glass will Void all product warrantiesOptional BAY Front BAY LouversQty Description LPG Conversion Kit Contains Qty DescriptionDC Sparker Kit Contains Installation of the DC Sparker Heat Shield Full Screen Doors Screen Door Hinge Location Bottom Frame Remote Control Wall Switch Wall ThermostatOperating Instructions Copy of Lighting Plate Instructions Maintenance Disconnect the power Door Glass ReplacementRemoving Valve Assembly Removing the FANParts List Main AssemblyBurner Assembly & LOG SET Bay Door Flush DoorFaceplate Assembly Warranty ConditionsInstaller Please complete the following information