BCP-3
Hydronic Multi-Stage Boiler Control
INSTALLATION AND OPERATION INSTRUCTIONS
Hot Water Control with
Outdoor Reset, Set Point, and DHW for Hydronic Applications
2 Line Alphanumeric Display | Black (120VAC power) |
Displays sensor values and | Output Lights indicate |
menu settings | |
| output status |
BCP-3
SYSTEM | = | 147F | |
TARGET | = | 150F | |
|
|
| |
Boiler | SYS | DHW | |
Pump | Pump | ||
Output 1 | |||
Output 2 | Output 3 |
SET
Yellow (Output 1)
Blue (Output 2)
White (Output 3)
Display Section Locking Screws
The
Two sensors are used, one to monitor the outdoor temperature and one to monitor the circulating hot water temperature in the heating system. When the outdoor temperature falls below the outdoor cutoff setting, the heating system is activated and the target water temperature is increased proportionally to satisfy the load. Should it get warmer outdoors, the target water temperature is automatically lowered by the control. If the outdoor temperature continues to rise to the outdoor cutoff setting then the heating system is turned off.
Because of the many different physical characteristics of buildings including the type of radiation; i.e., baseboard or radiant, the heat loss varies. In one building, a
The installer fits the
WARNING This Weil McLain control is strictly an operating control; it should never be used as a primary limit or safety control. All equipment must have its own certified limit and safety
controls required by local codes. The installer must verify proper operation and correct any safety problems prior to the installation of this Weil McLain control.
Part Number