Minimum Target (Available when Startup Control Mode = Outdoor Reset)

Options: From 70ºF/21ºC to 170ºF/77ºC

Default: 140ºF/60ºC

Min Target:

SET /Set Point/<Out. Reset>/Min. Tgt

 

 

140 F

• The Minimum Target Temperature must be set to the boiler manufacturer’s specification.

 

The BCP-3 will calculate the Target based on the Outdoor temperature, the Reset Ratio, and the Offset value. The BCP-3 will control the boiler to hold the higher of either the calculated temperature or the Minimum Target Temperature.

• The Minimum Target Temperature must be at least 20°F lower than the Maximum Temperature (See next setting).

Maximum Target (Available when Startup Control Mode = Outdoor Reset)

Options: From 90ºF/38ºC to 240ºF/116ºC

Default: 200ºF/93ºC

Max Target:

SET /Set Point/<Out. Reset>/Max. Tgt

 

200 F

This is the highest Target Temperature the BCP-3 will circulate through the heating system.

When using a radiation system, it should be set according to the tubing or floor manufacturer’s specification.

The Maximum Temperature must be at least 20°F higher than the Minimum Temperature.

Stage Menu Options

/<Settings>/<Stage>

This menu is only available when multiple stages or multiple boilers are selected as the Output Mode from the Startup Menu.

Reaction Time: 5m

 

 

 

 

Purge

Delay:

--STAGE SETTINGS-

 

1.0m

 

 

 

 

 

 

Reaction

 

2m

 

 

 

Purge

0.0m

 

Minimum Runtime:

Min. Runtime

2m

 

 

2m

 

Lead

Output

1

 

 

 

 

 

Rotate

Time

 

 

 

<Back>

 

 

 

Lead

Boiler:

 

 

 

 

 

 

 

 

 

Output 1

Rotation

Period:

 

Lead

Rotation:

 

Time

 

24hrs

 

 

 

 

 

 

 

 

 

 

 

Manual

 

 

 

 

Reaction Time

 

Reaction Time:

Options: 1 to 10 minutes

Default: 2 minutes

2m

SET /<Settings>/<Stage>/Reaction

 

 

It is the amount of time it takes a single stage to affect the system.

After the BCP-3 turns on a stage trying to meet a set point, it will not turn on another stage until the reaction time has elapsed. Then, it will recalculate if an additional stage is need.

To determine the optimum time, in a heating system start with a hot system. Then, turn on a single stage and calculate how long it takes until the system begins to respond to that stage by rising an additional 2°F. That period should be set as the Reaction Time.

Purge

 

Purge Delay:

Options: 0.0 to 10 minutes

Default: 1.0 minutes

1.0m

SET /<Settings>/<Stage>/Purge

 

 

Most large units must go through a purge cycle before they are brought on line.

When the BCP-3 activates a unit (the lowest firing stage on a boiler), it does not start to calculate its output until the Purge Delay is over. This allows the boiler to fully come on and begin producing output.

The Purge Delay helps prevent short cycling of newly activated boilers. Once the lowest boiler stage is activated, it MUST run through the entire Purge Delay period before starting the Reaction Time calculation..

The Purge Delay setting MUST be set to the time required by the boiler's manufacturer specification.

11

Image 11
Contents Hydronic Multi-Stage Boiler Control BCP-3DHW Pump Operation Operation ConceptBoiler Operation System Pump OperationHeating System Sensor HSS Installation T1, COM WiringWiring Input Terminals Wiring Power InputWiring Outputs Wiring the System and DHW Pump Outputs Output Mode TableWiring the Boiler Output BCP-3 BCP-3 Output Modes WiringStartup Menu MenusStartup Options Button and Navigating MenusOperating Menu Options Click SET Button Setting the Control to Factory DefaultDefault Display Set Point Available when Startup Control Mode = Set PointSet Point/Cutoff SET /Set Point/Out. Reset/Cutoff Custom Reset RatioOptions From -40ºF/-22ºC to +40ºF/+22ºC Default 0ºF/0ºC Options Off, 30ºF/0ºC to 75ºF/25ºC, On Default 60ºF/16ºCStage Menu Options SET /Set Point/Out. Reset/Min. TgtSET /Set Point/Out. Reset/Max. Tgt Settings/StageSettings/Stage/Lead/Rotate Single On/Off Boiler and System Pump SettingsRun-On Not Available for 3-On/Off Output Mode Options Output 1, Output 2, or Output Default OutputBoost Enable/Disable Tstat InputDomestic Hot Water DHW Priority SetbackTroubleshooting BCP-3 Plumbing Diagrams Specifications