Weil-McLain BCP-3 manual Wiring Outputs

Page 4

BCP-3 Installation and Operation Manual

 

IMPORTANT

 

Determining the proper location for the Outdoor Sensor is very important.

 

The BCP-3 will base the heat on the outdoor temperature information it

Sensor Clip

Outdoor Sensor

receives from this location. If the sensor is in the sun, or covered with

 

ice, its reading will be different from the actual outdoor temperature.

 

Outdoor Sensor Installation (T2, COM)

 

 

• The Outdoor Sensor must be used when Outdoor Reset is selected as the Control Mode

 

 

from the Startup menu. However, in Set Point mode, the Outdoor Sensor is optional.

 

 

When connected in that mode, it will be used as an input for the Outdoor Cutoff only.

 

 

• Only use the Weil McLain sensor included with the unit.

10' Minimum

 

• Place the sensor in the shade on the north side of the building.

 

 

• Be sure the location is away from doors, windows, exhaust fans, vents, or other heat

 

 

sources.

 

 

• The sensor should be mounted approximately 10' feet above ground level.

 

 

• Mount the sensor clip base to the outside of the building. Insert the sensor in the middle

 

 

and snap close the second clip on the sensor.

 

 

• The sensor wires can be extended up to 500' using shielded 2-conductor cable.

 

 

• Cut the shield and do not connect it at the sensor end. Only connect it at the control end

 

Low Voltage

using the outdoor terminal marked COM.

 

 

Sensor Wires

• Do not run sensor wires in conduit with line voltage wiring.

 

 

Wiring the Domestic Hot Water Call DHW (T3+, T3-)

 

 

• A DHW call will raise system Set Point to 200°F or Maximum Target temperature,

 

 

whichever is lower.

 

DHW Call

• When "1-On/Off+2-Pump" is selected as the Output Mode from the Startup menu, the BCP-3 can control the

operation of the Domestic Hot Water (DHW) pump using Output 3. See Output Mode Table on page 4.

Wiring

 

• DHW Call terminals are dry contact N.O. terminals.

 

 

• Wire an aquastat or another control to provide dry contact closure on the DHW Call terminals.

T1 COM T2 COM T3+ T3- EXT+ EXT-

Wiring the Enable/Disable (TSTAT) (EXT+, EXT-)

The EXT terminals can be used to enable or disable the heat to the system by connecting it to a thermostat, external control, or a switch. It accepts dry contact input only.

If no thermostat or control is connected to the EXT terminals, leave the jumper supplied connected.

No outputs will be active unless the EXT terminals are closed/shorted.

Wiring the Setback/Boost (P+, P-)

The Setback feature can be used to provide the BCP-3 with a lower temperature Set Point when less heat is required during night or unoccupied periods.

The Setback is activated by closing/shorting the P+ and P- terminals using an external control, i.e. timer or switch.

Enable/Disable

Wiring

COM T3+ T3- EXT+ EXT- P+ P- COM

Wiring Outputs

Wire Colors and Output Lights

 

 

Setback/Boost

The BCP-3 has a three S.P.S.T. (N.O.) output relays. Each relay is rated at 1A Inductive load (1/8 HP).

 

 

 

 

 

Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The BCP-3 has three LED lights that follow the output relays' operation. When a relay energizes, its LED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

will turn on. When the relay de-energizes, its LED will turn off.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3+ T3- EXT+ EXT- P+ P- COM 24VAC

The outputs are dry contacts only. They do not source any power.

The two Yellow wires represent Output 1 relay and the left LED.

The two Blue wires represent Output 2 relay and the middle LED.

• The two White wires represent Output 3 relay and the right LED.

Depending on the Output Mode of operation selected during the Startup, the function of each

SYS DHW

output will vary. See Output Mode Table for output wire colors and functions on page 4. Boiler Pump Pump

Output 1 Output 2 Output 3

4

Image 4
Contents BCP-3 Hydronic Multi-Stage Boiler ControlOperation Concept Boiler OperationSystem Pump Operation DHW Pump OperationWiring Wiring Input TerminalsWiring Power Input Heating System Sensor HSS Installation T1, COMWiring Outputs Wiring the Boiler Output Output Mode TableWiring the System and DHW Pump Outputs BCP-3 Output Modes Wiring BCP-3Menus Startup MenuButton and Navigating Menus Startup OptionsSetting the Control to Factory Default Default DisplaySet Point Available when Startup Control Mode = Set Point Operating Menu Options Click SET ButtonCustom Reset Ratio Options From -40ºF/-22ºC to +40ºF/+22ºC Default 0ºF/0ºCOptions Off, 30ºF/0ºC to 75ºF/25ºC, On Default 60ºF/16ºC Set Point/Cutoff SET /Set Point/Out. Reset/CutoffSET /Set Point/Out. Reset/Min. Tgt SET /Set Point/Out. Reset/Max. TgtSettings/Stage Stage Menu OptionsSingle On/Off Boiler and System Pump Settings Run-On Not Available for 3-On/Off Output ModeOptions Output 1, Output 2, or Output Default Output Settings/Stage/Lead/RotateEnable/Disable Tstat Input Domestic Hot Water DHW PrioritySetback BoostTroubleshooting BCP-3 Plumbing Diagrams Specifications