Weil-McLain BCP-3 manual Button and Navigating Menus, Startup Options

Page 8

BCP-3 Installation and Operation Manual

Button and Navigating Menus

The BCP-3 has three buttons.

The SET button function varies. When the Default Screen is displayed, pressing the SET Button views the MENU. When

in the Menus and settings, the SET Button accepts the selected

SET

entry or setting value.

 

When in the menus, pressing the Up and Down buttons will scroll through the menu options. They can be used to change the setting of a specific function. I.e., change the Set Point, Differential, or System Trim. In addition, when in the default screen, the Up and Down buttons will display the outdoor temperature and Outdoor Cutoff.

At the end of every operation menu there is a <Back> option that allows the user to go back one menu level. If the SET

Button was held down for three seconds on the <Back>

 

 

 

 

 

 

option, the display will go back to the default screen.

 

 

 

OUTPUT

MODE:

 

 

 

1-On/Off+1-Pump

 

 

 

 

Startup Options

F

 

 

1-On/Off+2-Pump

 

 

1-Lo/Hi+1-Pump

 

DISPLAY

UNIT:

2-On/Off+1-Pump

 

 

 

 

When the control is initiated for the first time or after a manual

C

 

 

3-On/Off

 

 

 

 

 

 

 

 

 

reset, it will start its operation with the Startup Menu. Later, the

CONTROL

MODE:

 

 

 

 

 

 

Startup menu can be accessed as an option from the operation

SENSOR

FAULT:

Outdoor

Reset

 

 

Output

On

menu. An option must be accepted in each screen in the Startup

 

Set Point

Output

Off

Menu to move to the next level.

 

 

 

 

 

 

 

 

 

Display Unit

 

 

 

DISPLAY

UNIT:

Options: ºF, ºC

 

Default: ºF

F

 

 

SET /<System Startup>/Display Unit

 

 

 

C

 

 

The BCP-3 will offer two different temperature display standards. If ºF is selected, all temperatures will display in Fahrenheit. If ºC is selected, all temperatures will display in Celsius.

Control Mode

Options: Outdoor Reset, Set Point

Default: Outdoor Reset

SET /<System Startup>/Display Unit/Control Mode

The new BCP-3 has two heating logics. Outdoor Reset; varies the system set point/target based on outdoor temperature. This selection adds several menu options to adjust and fine tune the reset curves: Reset Ratio, Offset, Min Water temp, Max Water temp, and Outdoor Cutoff. In addition, a customized reset ratio curve will be available for specialized applications.

Set Point; gives the installer the flexibility of selecting a fixed set point. The Outdoor Cutoff will be available if an outdoor sensor was installed.

CONTROL MODE:

Outdoor Reset

Set Point

Output Mode

Options: 1-On/Off+1-Pump, 1-On/Off+2-Pump, 2-On/Off+1-Pump, 3-On/Off

Default: 2-On/Off+1-Pump

SET /<System Startup>/Display Unit/Control Mode/Output Mode

The new BCP-3 has multiple operating Output Modes of heating. Each can be applied based on the number of boilers, stages, and pumps controlled. See Output Mode Table on page 4.

Sensor Fault

Options: Output On, Output Off

Default: Output On

SET /<System Startup>/..../Sensor Fault

 

The Sensor Fault will determine the operating status of the output relays when a sensor reads

Short or Open. On sensor fault, the Set Point will indicate FAULT TGT=ON or OFF to indicate the condition of the output and the faulty sensor will read OPEN or SHORT to indicate the condition of the sensor.

OUTPUT MODE:

1-On/Off+1-Pump

1-On/Off+2-Pump

2-On/Off+1-Pump

1-Lo/Hi+1-Pump

3-On/Off

SENSOR FAULT:

Output On

Output Off

8

Image 8
Contents BCP-3 Hydronic Multi-Stage Boiler ControlOperation Concept Boiler OperationSystem Pump Operation DHW Pump OperationWiring Wiring Input TerminalsWiring Power Input Heating System Sensor HSS Installation T1, COMWiring Outputs Wiring the System and DHW Pump Outputs Output Mode TableWiring the Boiler Output BCP-3 Output Modes Wiring BCP-3Menus Startup MenuButton and Navigating Menus Startup OptionsSetting the Control to Factory Default Default DisplaySet Point Available when Startup Control Mode = Set Point Operating Menu Options Click SET ButtonCustom Reset Ratio Options From -40ºF/-22ºC to +40ºF/+22ºC Default 0ºF/0ºCOptions Off, 30ºF/0ºC to 75ºF/25ºC, On Default 60ºF/16ºC Set Point/Cutoff SET /Set Point/Out. Reset/CutoffSET /Set Point/Out. Reset/Min. Tgt SET /Set Point/Out. Reset/Max. TgtSettings/Stage Stage Menu OptionsSingle On/Off Boiler and System Pump Settings Run-On Not Available for 3-On/Off Output ModeOptions Output 1, Output 2, or Output Default Output Settings/Stage/Lead/RotateEnable/Disable Tstat Input Domestic Hot Water DHW PrioritySetback BoostTroubleshooting BCP-3 Plumbing Diagrams Specifications