Quartz 06617645-02 technical manual ###, Qlac / XL Extra Low noise version

Page 10

WATER CHILLERS AND HEAT PUMPS

QLAC / XL (Extra Low noise version)

TECHNICAL DATA

MOD.

 

040

045

050

060

070

080

090

110

Refrigerant

 

 

 

R407C

R407C

R407C

R407C

R407C

R407C

Cooling capacity

kW

###

###

52

58

64

78

90

104

Compressor input power

kW

 

 

17,2

19,3

21,5

25,8

29,9

33,9

 

 

 

 

 

 

 

 

 

 

Water flow rate

l/h

 

 

9290

10320

11520

13590

15650

18400

Water pressure drop

KPa

 

 

31,5

23,3

30,1

30,4

27,6

26,5

 

 

 

 

 

 

 

 

 

 

Heating capacity

kW

 

 

55,0

62,0

68,0

83,0

95,0

107,0

 

 

 

 

 

 

 

 

 

 

Compressor input power

kW

 

 

17,3

19,5

21,7

26,4

30,3

34,2

Water flow rate

l/h

 

 

9460

10665

11695

14275

16340

18400

Water pressure drop

kPa

 

 

32,6

24,8

31,0

33,5

30,0

26,5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total input current (K version)

A

 

 

37,4

40,1

42,8

52,6

62

67,5

Total peak current

A

 

 

154,4

194,4

194

235,4

265,1

275,1

Maximum input current

A

 

 

49,4

54,4

59,4

69,4

81,1

91,1

Power suppy

V/Ph/Hz

 

 

 

400/3/50

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

m³/h

 

 

24000

24000

24000

23600

35000

35000

 

 

 

 

 

 

 

 

 

 

Fans

n° x kW

 

 

2 x 1.23

2 x 1.23

2 x 1.23

2 x 1.23

3 x 1.23

3 x 1.23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressors

type

 

 

 

Scroll

 

 

 

 

 

2

2

2

2

2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant circuits

 

 

1

1

1

1

1

1

Control steps

 

 

2

2

2

2

2

2

 

 

 

 

 

 

 

 

 

 

Sound power level (1)

dB(A)

 

 

76

76

78

78

79,5

79,9

Sound pressure level (2)

dB(A)

 

 

48

48

50

50

51,5

51,9

 

 

 

 

 

 

 

 

 

 

Water pump (option)

kW

 

 

1,1

1,1

1,1

1,5

1,5

2,2

 

 

 

 

 

 

 

 

 

 

Pump available pressure (option)

kPa

 

 

141

125

110

150

130

150

Water tank capacity (option)

l

 

 

300

300

300

300

530

530

Expansion vessel (option)

l

 

 

18

18

18

18

18

18

 

 

 

 

 

 

 

 

 

 

Length

mm

 

 

2608

2608

2608

2608

3608

3608

Width

mm

 

 

1105

1105

1105

1105

1105

1105

Height

mm

 

 

1842

1842

1842

1842

1842

1842

 

 

 

 

 

 

 

 

 

 

Weight (Standard configuration)

kg

 

 

710

725

760

810

1070

1150

Weight (with hydraulic kit)

kg

 

 

880

895

930

980

1280

1360

## # XL Models in these sizes are available as a special unit. Contact QUARTZ technical department for details. Performances are rated at:

Cooling: ambient air temperature 35 °C; evaporator water temperature in/out 12°C / 7 °C.

Heating: ambient air temperature 8.3 °C db, 6.1 °C wb ; condenser water temperature in/out 40°C / 45 °C.

(1): Sound power level according to ISO 3746.

(2): Sound pressure level measured at 10m from the unit in free field conditions: direction factor Q=2 (according to ISO 3746).

10

06617645-02

Image 10
Contents Qlac Index EC Declaration of Conformity Technical Features Electrics enclosure EvaporatorsHydraulic circuit K versions only MicroprocessorsHeat pump version HP Heat Recovery VersionOther Versions Free cooling version FCWater Chillers and Heat Pumps Technical DataQlac / LS Low noise version 120 130 140 160 190 210 240 260 300 320 380 430 500 ### Qlac / XL Extra Low noise version206,1 050 040045 060090 070080 110140 120130 160240 190210 260Qlac / HP / LS LOW Noise Version Heating Capacities and Compressor Input Power TA C PC kW PA kW Evaporator Pressure Drops Water Pumps Available Static Pressure Free Cooling Capacity Partial Heat Recovery Capacity Mod 040 045 050 060 070 080 090 110Correction Tables Compressors Capacity Step Controls Correction TableWfcf Pdcf Cccp IpcfSound Levels LOW Noise Version Electrical DataSound Levels Extra LOW Noise Version Inspection Lifting and site handling Installation Instructions GeneralLocation and Minimum Clearances Hydraulic Connections Operational Limits Ambient air temperatureEvaporator water flow rate Before start-up Electrical ConnectionsStart UP Start upControl Device SET Point Differential Reset Type Control and Safety Device SettingsCapacity Steps Control Device Every six months Maintenance and Periodic ChecksRefrigerant Circuit Repair Environmental Protection Dimensions 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02