Quartz 06617645-02 technical manual Electrical Connections, Start UP, Before start-up, Start up

Page 28

ELECTRICAL CONNECTIONS

Disconnect the electrical supply before undertaking any work on the unit.

All electrical work must be undertaken by suitably qualified personnel.

The electrical supply must match the nominal electrical data (voltage, phase, frequency) shown on the label in the front panel of the unit. Power connections must be made in accordance to the wiring diagram enclosed with the unit and in accordance current local and national regulations. Power cable and line protection must be sized according to the specification stated on the wiring diagram enclosed with the unit.

The variation in line voltage must not be more than ±5% of the nominal value, whilst the voltage imbalance between phases must not exceed 2%. If those tolerances are likely to be exceeded, please contact TEV Ltd., as further protection devices are required.

Electrical supply must be as described, otherwise warranty will be invalid.

START UP

Before start-up

-Check that all power cables are connected in the correct sequence and that all terminals are tight.

-The voltage measured at the R Y B phase clamps must be 400 V ± 5% (or the value given on the rating plate for special voltages). If the voltage is incorrect, do not proceed.

-Check for any refrigerant leaks using a leak detector. Should a leak be found do not proceed. All leaks must be rectified and the unit re-charged by trained personnel.

-Check that the crankcase heaters are energised.

Crankcase heaters must be energised at least 12 hours before start up by switching on the unit at the main switch.

-Verify that heaters are working correctly. After a short warm up period, the compressor crankcase must be warm to the touch and must have a temperature at least 10K higher than ambient temperature.

-Check that all hydraulic connections have been made correctly and that all information given on the unit's labels have been observed.

-The system must be filled with water and bled to eliminate any air.

Caution: before starting the unit up, check that all cover panels are correctly located and securely fastened.

Start up

Please refer to the microprocessor manual enclosed with the unit.

If the unit fails to start:

Check that the control thermostat is set to the correct value.

Do not modify any internal wiring, otherwise warranty will be invalidated.

Controls during unit operation

Check the rotation of the fans. If the rotation is incorrect, disconnect the main switch and change over any two phases of the incoming main supply to reverse motor rotation:

Check that water temperature at evaporator inlet is near to the set point of the control thermostat.

For “K” version units (units with pumps and storage tank) if the motor driven pump is noisy, slowly close the discharge shut-off valve until normal working conditions are restored.

This trouble may occur when system pressure drop is significantly different from pump available pressure.

28

06617645-02

Image 28
Contents Qlac Index EC Declaration of Conformity Technical Features Evaporators Hydraulic circuit K versions onlyElectrics enclosure MicroprocessorsHeat Recovery Version Other VersionsHeat pump version HP Free cooling version FCWater Chillers and Heat Pumps Technical DataQlac / LS Low noise version 120 130 140 160 190 210 240 260 300 320 380 430 500 ### Qlac / XL Extra Low noise version206,1 040 045050 060070 080090 110120 130140 160190 210240 260Qlac / HP / LS LOW Noise Version Heating Capacities and Compressor Input Power TA C PC kW PA kW Evaporator Pressure Drops Water Pumps Available Static Pressure Free Cooling Capacity Partial Heat Recovery Capacity Mod 040 045 050 060 070 080 090 110Compressors Capacity Step Controls Correction Table Wfcf PdcfCorrection Tables Cccp IpcfSound Levels LOW Noise Version Electrical DataSound Levels Extra LOW Noise Version Inspection Lifting and site handling Installation Instructions GeneralLocation and Minimum Clearances Hydraulic Connections Operational Limits Ambient air temperatureEvaporator water flow rate Electrical Connections Start UPBefore start-up Start upControl Device SET Point Differential Reset Type Control and Safety Device SettingsCapacity Steps Control Device Every six months Maintenance and Periodic ChecksRefrigerant Circuit Repair Environmental Protection Dimensions 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02