WATER CHILLERS AND HEAT PUMPS

QLAC / LS (Low noise version)

TECHNICAL DATA

MOD.

 

120

130

140

160

190

210

240

260

Refrigerant

 

R407C

R407C

R407C

R407C

R407C

R407C

R407C

R407C

 

 

 

 

 

 

 

 

 

 

Cooling capacity

kW

115,5

128

142

156

181

206,1

232

256

Compressor input power

kW

38

42,1

47,3

51,7

59,7

67,8

76

84,2

Water flow rate

l/h

20640

22190

24600

27180

31990

36290

41450

45240

 

 

 

 

 

 

 

 

 

 

Water pressure drop

kPa

29,4

30,0

30,8

36,0

39,6

42,7

49,0

51,2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating capacity

kW

120

132

150

165

189

217

242

267

Compressor input power

kW

38,5

42,9

48,1

52,8

60,6

68,4

77,1

85,8

 

 

 

 

 

 

 

 

 

 

Water flow rate

l/h

20640

22700

25800

28380

32510

37320

41620

45920

Water pressure drop

kPa

29,4

31,3

33,8

39,2

40,9

45,1

49,4

52,7

 

 

 

 

 

 

 

 

 

 

Total input current (K version)

A

76,4

85,5

96,3

104,7

126,6

144,0

160,2

178,4

 

 

 

 

 

 

 

 

 

 

Total peak current

A

322,1

333,1

290

304

351

369

431

453

Maximum input current

A

102,1

113,1

119,9

138,3

167,6

185,6

211,6

233,6

Power supply

V/Ph/Hz

 

 

 

400/3/50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

m°/h

25920

25920

36000

34920

55800

55800

58800

58800

Fans

n° x kW

3 x 0,69

3 x 0,69

4 x 0,69

4 x 0,69

3 x 2,0

3 x 2,0

4 x 2,0

4 x 2,0

 

 

 

 

 

 

 

 

 

Compressors

type

 

 

 

Scroll

 

 

 

2

2

4

4

4

4

4

4

 

Refrigerant circuits

1

1

2

2

2

2

2

2

 

 

 

 

 

 

 

 

 

 

Control steps

2

2

4

4

4

4

4

4

 

 

 

 

 

 

 

 

 

 

Sound power level (1)

dB(A)

82,9

83,1

83,5

84

86

86

89

89

Sound pressure level (2)

dB(A)

54,9

55,1

55,5

56

58

58

61

61

 

 

 

 

 

 

 

 

 

 

Water pump (option)

kW

2,2

2,2

2,2

3,0

3,0

3,0

4,0

4,0

Water pump input current

A

5,3

5,3

5,3

8,5

8,5

8,5

9,9

9,9

 

 

 

 

 

 

 

 

 

 

Pump available pressure (option)

kPa

120

130

105

180

140

110

170

155

 

 

 

 

 

 

 

 

 

 

Water tank capacity (option)

l

530

530

530

670

670

670

670

670

Expansion vessel (option)

l

18

18

18

18

18

18

18

18

 

 

 

 

 

 

 

 

 

 

Length

mm

3608

3608

4108

4108

4708

4708

4708

4708

Width

mm

1105

1105

1105

1105

1105

1105

1105

1105

Height

mm

1759

1759

2179

2179

2262

2262

2262

2262

Weight (Standard configuration)

kg

1200

1230

1650

1700

1960

2050

2160

2480

 

 

 

 

 

 

 

 

 

 

Weight (with hydraulic kit)

kg

1410

1440

1860

2000

2260

2350

2460

2780

Performances are rated at:

Cooling: ambient air temperature 35 °C; evaporator water temperature in/out 12°C / 7 °C.

Heating: ambient air temperature 8.3 °C db, 6.1 °C wb ; condenser water temperature in/out 40°C / 45 °C.

(1): Sound power level according to ISO 3746.

(2): Sound pressure level measured at 10m from the unit in free field conditions: direction factor Q=2 (according to ISO 3746).

8

06617645-02

Image 8
Contents Qlac Index EC Declaration of Conformity Technical Features Evaporators Hydraulic circuit K versions onlyElectrics enclosure MicroprocessorsHeat Recovery Version Other VersionsHeat pump version HP Free cooling version FCQlac / LS Low noise version Technical DataWater Chillers and Heat Pumps 120 130 140 160 190 210 240 260 300 320 380 430 500 ### Qlac / XL Extra Low noise version206,1 040 045050 060070 080090 110120 130140 160190 210240 260Qlac / HP / LS LOW Noise Version Heating Capacities and Compressor Input Power TA C PC kW PA kW Evaporator Pressure Drops Water Pumps Available Static Pressure Free Cooling Capacity Partial Heat Recovery Capacity Mod 040 045 050 060 070 080 090 110Compressors Capacity Step Controls Correction Table Wfcf PdcfCorrection Tables Cccp IpcfSound Levels Extra LOW Noise Version Electrical DataSound Levels LOW Noise Version Location and Minimum Clearances Installation Instructions GeneralInspection Lifting and site handling Hydraulic Connections Evaporator water flow rate Ambient air temperatureOperational Limits Electrical Connections Start UPBefore start-up Start upCapacity Steps Control Device Control and Safety Device SettingsControl Device SET Point Differential Reset Type Refrigerant Circuit Repair Maintenance and Periodic ChecksEvery six months Environmental Protection Dimensions 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02 06617645-02