PARTIAL HEAT RECOVERY CAPACITY
Mod. |
| 040 | 045 | 050 | 060 | 070 | 080 | 090 | 110 |
Partial heat recovery nominal capacity | kW | 9,5 | 12,8 | 13,0 | 15,0 | 15,3 | 18,5 | 21,5 | 24,8 |
Water flow | l/h | 1635 | 2200 | 2240 | 2580 | 2630 | 3190 | 3700 | 4270 |
Water pressure drops | kPa | 10 | 14 | 11 | 15 | 16 | 18 | 11 | 15 |
|
|
|
|
|
|
|
|
|
|
Mod. |
| 120 | 130 | 140 | 160 | 190 | 210 | 240 | 260 |
Partial heat recovery nominal capacity | kW | 27,5 | 30,0 | 34,0 | 37,0 | 43,0 | 49,0 | 55,0 | 61,5 |
Water flow | l/h | 4730 | 5160 | 5850 | 6360 | 7400 | 8430 | 9460 | 10570 |
|
|
|
|
|
|
|
|
|
|
Water pressure drops | kPa | 13 | 18 | 18 | 25 | 11 | 15 | 19 | 25 |
|
|
|
|
|
|
|
|
|
|
Mod. |
| 300 | 320 | 380 | 430 | 500 |
|
|
|
Partial heat recovery nominal capacity | kW | 69,0 | 76,0 | 91,5 | 102,8 | 114 |
|
|
|
Water flow | l/h | 11850 | 13000 | 15750 | 17700 | 19600 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Water pressure drops | kPa | 20 | 25 | 25 | 29 | 35 |
|
|
|
|
|
|
|
|
|
|
|
|
|
The nominal value refers to an ambient temperature 35°C and outlet water temperature 50°C (Dt 5°C).
1,5
1,4
1,3
1,2
1,1
1
0,9
0,8
40 | 41 | 42 | 43 | 44 | 45 | 46 | 47 | 48 | 49 |
Outlet water temperature °C
Ambient temperature 40°C
Ambient temperature 35°C
Ambient temperature 30°C
Ambient temperature 25°C
Ambient temperature 20°C
50
The heat recovery capacity in different conditions can be obtained multiplying the nominal capacity (See above), by the correction factor indicated in the table.
Warning Partial heat recovery can only work in cooling mode. In the heat pump version it is necessary to isolate the heat recovery circuit when in heating mode to prevent damage. Failure to comply with this will invalidate the warranty.
22 |