Evaporators
The plate evaporators are made of 316 stainless steel,
Hydraulic circuit (K versions only)
QLAC chillers can be supplied with an optional built in hydraulic kit that includes:
Water tank: various capacities (depending on the size of the unit), factory insulated with flexible
Water pump: centrifugal type, is available in single (K1) or double configuration (K2). In the K2 version, one pump is running and one pump is in
Electrics enclosure
Access to the electrics enclosure is achieved by switching the mains isolator to "OFF" and removing the front cover.The electrics conform to electromagnetic compatibility norms CEE 73/23 and 89/336. Moisture protection is IP55.
All QLAC units have installed, as standard, a compressor sequence relay, which disables compressor operation if the power supply phase sequence is incorrect (scroll compressors can be damaged if they operate in reverse). The following components are also installed as standard:
Mains switch, | |
Compressor fuses | Control circuit automatic breakers |
Compressor contactors | Fan contactors, pump contactors. |
The terminal board is supplied with volt free contacts for remote
Microprocessors
QLAC units are supplied with microprocessor controls as standard. The specific controller used depends upon the unit size, number of features and use of optional features e.g. electronic expansion valves.The microprocessor controls the following basic functions:
regulation of the water temperature antifreeze protection compressor timing
compressor automatic starting sequence alarm reset
volt free contact for remote common alarm alarms and leds.
Any microprocessor can, on request, be connected to a BMS system for remote control and management. Typically, solutions can be found for MODBUS, LONWORKS, BACNET or TREND protocols.
Control and protection devices
All units are supplied with the following control and protection devices:
Return water temperature sensor, installed on the return water line from the plant (12°C) Antifreeze protection sensor installed on the outlet water temperature (7°C)
High pressure switch with manual reset Low pressure switch with automatic reset High pressure safety valve Compressor thermal overload protection Fan thermal overload protection
Flow switch. (std versions supplied loose, K versions factory fitted)