WATER CHILLERS AND HEAT PUMPS
QLAC / LS (Low noise version)
TECHNICAL DATA
MOD. |
| 300 | 320 |
| 380 | 430 | 500 |
Refrigerant |
| R407C | R407C | R407C | R407C | R407C | |
|
|
|
|
|
|
|
|
Cooling capacity | kW | 290 | 321 |
| 383 | 432 | 481 |
Compressor input power | kW | 92,4 | 100,6 |
| 126,4 | 138,7 | 150,9 |
Water flow rate | l/h | 49880 | 55200 |
| 65800 | 74300 | 82700 |
|
|
|
|
|
|
|
|
Water pressure drop | kPa | 34 | 39 |
| 32 | 38 | 44 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Free cooling capacity | kW | 185 | 185 |
| 235 | 245 | 240 |
input power | kW | 12 | 12 |
| 16 | 16 | 16 |
|
|
|
|
|
|
|
|
Water flow rate | l/h | 49880 | 55200 |
| 65800 | 74300 | 82700 |
Water pressure drop | kPa | 107 | 121 |
| 113 | 121 | 141 |
|
|
|
|
|
|
|
|
Total input current (K version) | A | 201,4 | 220 |
| 279,2 | 301,7 | 324,2 |
Total peak current | A | 510 | 534 |
| 582 | 641 | 672,5 |
Maximum input current | A | 262,6 | 287,2 |
| 362 | 393,5 | 425 |
Power supply | V/Ph/Hz |
|
| 400/3/50 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Airflow | m°/h | 89000 | 88500 |
| 119000 | 118000 | 118000 |
Fans | n° x kW | 6x2 | 6x2 |
| 8x2 | 8x2 | 8x2 |
|
|
|
|
|
|
|
|
Compressors | type |
|
|
| Scroll |
|
|
n° | 4 | 4 |
| 6 | 6 | 6 | |
|
| ||||||
Refrigerant circuits | n° | 2 | 2 |
| 2 | 2 | 2 |
|
|
|
|
|
|
|
|
Control steps | n° | 4 | 4 |
| 6 | 6 | 6 |
|
|
|
|
|
|
| |
Sound power level (1) | dB(A) | 90 | 90 |
| 91 | 91 | 91 |
Sound pressure level (2) | dB(A) | 62 | 62 |
| 63 | 63 | 63 |
|
|
|
|
|
|
| |
Water pump (option) | kW | 4 | 5,5 |
| 7,5 | 7,5 | 7,5 |
Pump available pressure (option) | kPa | 160 | 172 |
| 210 | 190 | 160 |
|
|
|
|
|
|
|
|
Water tank capacity (option) | l | 670 | 670 |
| 670 | 670 | 670 |
|
|
|
|
|
|
|
|
Expansion vessel (option) | l | 25 | 25 |
| 50 | 50 | 50 |
|
|
|
|
|
|
| |
Length | mm | 4108 | 4108 |
| 4708 | 4708 | 4708 |
Width | mm | 2201 | 2201 |
| 2201 | 2201 | 2201 |
Height | mm | 2262 | 2262 |
| 2262 | 2262 | 2262 |
Weight (Standard configuration) | kg | 2750 | 2800 |
| 3100 | 3150 | 3210 |
Weight (with hydraulic kit) | kg | 3150 | 3220 |
| 3550 | 3610 | 3690 |
|
|
|
|
|
|
|
|
Performances are rated at:
Cooling: ambient air temperature 35 °C; evaporator water temperature in/out 12°C / 7 °C.
Free cooling: ambient air temperature 2 °C; water inlet temperature 15°C, glycol 20%, nominal waterflow, compressors switched off
(1): Sound power level according to ISO 3746.
(2): Sound pressure level measured at 10m from the unit in free field conditions: direction factor Q=2 (according to ISO 3746).
9 |