FREE COOLING CAPACITY
| 3 |
|
|
|
|
|
|
| 2,5 |
|
|
|
|
|
|
factor FCC | 2 |
|
|
|
|
|
|
| 7°C | 12°C |
|
|
|
| |
correction |
|
|
|
|
| ||
1,5 | 5°C | 10°C |
|
|
|
| |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
capacity |
|
|
|
| Return water temperature 15°C |
| |
|
|
|
|
|
|
| |
Free cooling | 1 |
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 0,5 |
|
|
|
|
|
|
| 0 |
|
|
|
|
|
|
| 0 | 5 | 10 |
Ambient air temperature (°C)
Mod. |
| 040 | 045 | 050 | 060 | 070 | 080 | 090 | 110 |
Nominal Free cooling capacity | kW | 43 | 43 | 43 | 45 | 70 | 72 | ||
|
|
|
|
|
|
|
|
|
|
Mod. |
| 120 | 130 | 140 | 160 | 190 | 210 | 240 | 260 |
Nominal Free cooling capacity | kW | 72 | 72 | 94 | 94 | 110 | 115 | 135 | 135 |
Mod. |
| 300 | 320 | 380 | 430 | 500 |
|
|
|
Nominal Free cooling capacity | kW | 185 | 185 | 235 | 245 | 240 |
|
|
|
|
|
|
|
|
|
|
|
|
|
The nominal Free Cooling capacity is obtained when all compressors are OFF, the return water temperature from the system is 15°C and the ambient temperature is 2°C. to calculate the free cooling capacity in different conditions please refer to the above diagram. To obtain free cooling duty multiply the nominal Free Cooling capacity by the CFC factor obtained.