GSW 319594-000 manual Installations, Local Codes

Page 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ventilated Space Air Requirements for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(a)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U.S. Installations

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to Figure 5 (a), (b), (c) or (d) for proper sizing and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

location of combustion air ducts and openings. CHECK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PERMANENT

 

 

 

LOCAL CODES.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPENINGS

 

 

 

a) Equipment located in ventilated spaces; all air from

 

 

 

VENTILATED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNCONFINED

 

 

 

 

inside the building.

 

 

 

 

SPACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Two permanent openings shall be provided connecting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to ventilated space (e.g. closet, small room) with the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unconfined space. Each opening shall be equal or

 

 

 

 

 

 

 

 

EQUIPMENT LOCATED IN VENTILATED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

greater than 645cm2 (100 in2.) with a width to height

 

 

 

 

SPACES; ALL AIR FROM INSIDE THE BUILDING.

 

 

 

 

 

 

 

 

 

 

 

 

 

ratio of 2:1. The top opening shall be located close to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the ceiling.

 

 

 

(b)

 

 

 

 

 

VENTILATED

 

COMBUSTION

 

 

 

 

 

 

 

 

 

PERMANENT

 

 

 

 

 

 

 

 

 

 

 

 

 

300mm

 

 

VENTILATION

 

 

Note: The opening shall not be lower than the top of the

 

 

 

 

 

 

 

 

SPACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR DUCT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(12 in.)

 

 

 

 

 

 

 

 

 

 

 

AIR.

 

 

heater. The location of the bottom opening shall be 150-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

450mm (6-18 in.) above floor level.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(12 in.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ABOVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GRADE

 

 

 

b) Basement installation, equipment located in ventilated

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SNOW

 

 

 

 

spaces; all air from outdoors.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LINE

 

 

 

 

Refer to the latest edition of the "National Fuel Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GRADE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Code" ANSI Z223.1 for air supply duct sizes and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

c) Equipment located in ventilated spaces; all air from out-

 

 

 

 

BASEMENT INSTALLATION, EQUIPMENT LOCATED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300mm

 

 

 

 

 

 

doors.

 

 

 

 

IN VENTILATED SPACES; ALL AIR FROM OUTDOORS

(12 in.)

 

 

 

 

 

 

Refer to the latest edition of the "National Fuel Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Code" ANSI Z223.1 for air supply duct sizes and

 

 

 

(c)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOORS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

restrictions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR DUCT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300mm (12 in.)

 

 

d) Equipment located in ventilated spaces; all air from out-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

doors through ventilated attic.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to the latest edition of the "National Fuel Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Code" ANSI Z223.1 for air supply duct sizes and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

restrictions.

 

 

VENTILATED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENTILATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMBUSTION

 

 

 

 

 

 

 

 

 

 

 

SPACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Ensure sufficient ventilation air to prevent elevat-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ed temperatures in closets and ventilated spaces.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When an exhaust fan is installed in the same room as the

 

 

 

 

 

 

 

 

EQUIPMENT LOCATED IN VENTILATED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

water heater, the supply air openings must be of sufficient

 

 

 

 

 

 

 

 

 

 

 

 

300mm (12 in.)

 

 

 

 

 

 

 

 

 

 

 

SPACES; ALL AIR FROM OUTDOORS.

 

 

 

 

 

 

capacity to prevent a backflow of air through the water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heater exhaust venting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(d)

 

 

 

 

ATTIC LOUVERS TO OUTDOORS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTLET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INLET AIR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DUCT

 

 

 

 

 

 

 

 

 

 

 

 

 

VENTILATED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300mm (12 in.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Burn Hazard

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not touch vent.

 

 

 

 

EQUIPMENT LOCATED IN VENTILATED SPACES; ALL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR FROM OUTDOORS THROUGH VENTILATED ATTIC.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Doing so can result in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 5 Combustion Air Supply Openings And Ducts

 

 

 

 

burns.

 

 

 

 

 

(U.S.A.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 –

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 10
Contents For Your Safety What to do if YOU Smell GASViii Troubleshooting Guide Page Introduction User ResponsibilitiesFor Installations in the United States II SafetyFor Installations in Canada Safety Warning Flammable VapoursLocation Requirements Relief Valve Requirements T&PFlooding/Freezing Valves For Hot Water Supply Systems, Ansi Z21.22/CSACloset Installation & Floor Surfaces Clearances and AccessibilityEarthquake Zones Gas line purging Gas Leak TestingGas Supply Pressure Gas Operating PressuresAir Requirements Canadian InstallationsVentilated Space Air Requirements for Installations Local CodesExhaust Venting Venting terminations and sizing General Venting LayoutDo not use near flame or open fire Use of Solvent Cement and PrimerUse only in well-ventilated areas Use only the Solvent Cement and PrimerVent pipe connection to blower Filling the Water Heater Piping Installation Water SupplyClosed System/Thermal Expansion Temperature and Pressure T&P Relief ValveTemperature and Pressure Relief Valve Discharge Line/DriptubeWiring Diagram White-Rodgers Control Flammable Vapour Sensor Flammable Vapour Sensor exploded viewResettable Lockout Water Heater OperationInstallation Checklist Risk of scalding IV Operating Instructions CautionMixing Valves Hot water can produce third degree burnsLighting Instructions Robertshaw Gas Control/Thermostat System Error CodesHeater Shutdown Lighting Instructions White-Rodgers Control is adjusted to its lowest temperature setting Temperature AdjustmentApproximately 21C 70F when shipped from factory Intelli-VentTMSystem Error Codes Heater Shutdown Symptom Possible Causes Corrective ActionSymptom Possible Causes Corrective Action Operational Conditions VI MaintenanceOperation Burner Flames Draining and FlushingRoutine Preventative Maintenance Anode Rod ReplacementGas Control Blower Maintenance System Requirements InstallationVII Combo Heating Tice such as Ashrae Handbooks, HraiViii Troubleshooting Guide Robertshaw 2000WDER and White-Rodgers Intelli-VentTMIX Reference Parts Reference Parts ListingInterchangeable Items not supplied with the water heater Parts Reference Illustration Robertshaw and White-Rodgers systems are not InterchangeableLimited Warranty WHO is CoveredHOW the Original Owner can Make a Warranty Claim