GB100W NATURAL OR PROPANE BOILER

 

INSTALLATION AND OPERATING INSTRUCTIONS

CANADIAN SUPPLEMENT

DANGER

Only the boiler may be served by the vent damper. Do not use it to vent an additional appliance; this will cause a fire or carbon monoxide poisoning.

DANGER

LE VOLET DE VENTILATION DOIT SERVIR SEULE-MENT À LA CHAUDIÈRE. NE PAS L´UTILISER POUR VENTILER D´AUTRES APPAREILS; SINON CELA POURRAIT PROVOQUER UN INCENDIE OU CAUSER UN EMPOISONNEMENT PAR LE MONOXYDE DE CARBONE.

METHOD OF INSTALLATION FOR MOTORIZED VENT DAMPER

MÉTHOSE D´INSTALLATION POUR LE VOLET MOTORISÉ DE VENTILATION

The damper must be mounted as close as possible to the draft hood without modifying the draft hood or damper device.

Attach the lower portion of the vent damper to the draft hood with 1/2 in, 13 mm or shorter screws or pop rivets.

Do not install within 6 in, 152 mm, of combustible materials. Make sure the motor actuator and position indicator are readily visible and accessible.

Plug the Molex connector on the damper harness into the mating plug on the harness located inside the control compartment.

Determine the amperage draw of the gas control circuit and damper device. Check heat anticipator in comfort thermostat to determine that it’s properly adjusted.

To manually open the damper, follow instructions inside the damper cover.

WIRE HARNESS FOR

VENT DAMPER

FAISCEAU DE FILIS DU

VOLET DE VENTILATION

Le registre doit être installé aussi près que possible du coupe-tirage sans qu´une modification de ce coupe- tirage ou le registre ne soit nécessaire.

Attacher la partie inférieure du volet de ventilation au coupe-tirage à l´aide de vis de 13 mm ou plus courtes ou des rivets aveugles.

Ne pas installer le registre à moins de 152mm des matériaux de combustion. S´assurer que dispositif de commande du moteur est visible et facilement acces- sible.

Enficher la prise Molex sur le faisceau de fils du volet de ventilation dans la prise a l´interieur d´armoire de commande.

Dèterminer l´appel de courant en ampères du circuit du régulateur de gaz et du registre. Vérifier la résistance anticipatrice de chaleur du thermostat d´ambiance afin de déterminer si elle est correctement réglée.

Pour ouvrir manuellement le registre suivre les instructions apparaissant à l´intérieur du couverele.

DAMPER MUST BE IN OPEN POSI-

TION WHEN APPLIANCE MAIN

BURNERS ARE OPERATING.

LE REGISTRE DOIT ÊTRE EN

POSITION OUVERTE LORSQUE

LE BRULEÛR PRINCIPAL EST EN

MARCHE.

POSITION INDICATOR

DISPOSITIF DE COMMANDE

CONNECT WIRE HARNESS BRANCHER LE FAISCEAU DU FILIS

CLOSED

CLOS OPEN OUVERTE

FLOW DIRECTION

SENS DE DEBIT

Image 28
Contents GB100W Contents Before YOU StartBoiler Ratings and Capacities Boiler LocationClearances to Combustible Construction FrontCombustible Floor Option Vent and Chimney DimensionsCombustion AIR Vent Connections Combustion Air Duct SizingChimney Inspection & Sizing Common Vent SystemsVent Dampers Heating System Piping Heating System PipingCirculators Piping For Use With Cooling UnitsSystem Bypass Pumped BlendEquivalent Length Chart GAS Supply PipingReverse Acting Aquastats Gas Pipe CapacityElectrical Wiring Electrical Power ConnectionsThermostat Installation Vent DamperTheoriginalwire Bereplacedwith Ifanyof Itmust Fenwal/Honeywell Direct IgnitionWiththisappliancemust Thermoplasticwireorits Bereplaced EquivalentHoneywell Continuous Pilot Ignition Multi Zone Diagram Boiler SET UP Flame Roll-out Safety Shutoff SystemLighting Instructions For Your Safety Read Before OperatingWhat to do if YOU Smell GAS Pour Votre Sécurité Lisez Avant Dallumer Instructions DallumageComment Couper Ladmission DE GAZ DE Lappareil QUE Paire SI Vous Sentez UNE Odeur DE GAZOperating Instructions To Turn OFF GAS to AppliancePour Votre Sécurité Lisez Avant DE Mettre EN Marche QUE Faire SI Vous Sentez UNE Odeur DE GAZContinuous Pilot System Boiler OperationIntermittent & Direct Ignition Systems Boiler Checking & Adjustment Pilot AdjustmentGas Pressure Adjustment Input RateBoiler Maintenance Vent System Instructions to the InstallerControls Replacement Parts GB100 Series Repair PartsSpark Ignition Honeywell Canadian Supplement Limited Lifetime Warranty For Residential Water Boilers Shortness of breath Page North ELM Street WESTFIELD, MA 01085 TEL 562-9631 FAX 413